General Configuration
The cooling group configuration options are set during the commissioning of the cooling units in the cooling group.
Caution: This procedure must be performed by APC authorized personnel only. Changing the settings incorrectly can cause malfunctions to your cooling unit.
Cooling unit configuration
Path: Main > Configure Unit > General
Use the General menu to set the following:
Idle On Leak. When set to Yes, the cooling unit will enter idle mode if a Water Detection Fault activates. Set to No to disable the cooling unit from entering idle mode if a leak is detected.
Note: The leak sensor (APC part number AP9325) is optional.
Note: There are three alarms that will cause the cooling unit to enter idle mode:
•Water Detection Fault (when Idle On Leak is set to Yes)
•Condensate Pump Fault
•Cooling Failure
InRow SC Operation | 11 |