Rheem RMTG2-53(PVN)(PVP)(XN)(XP) warranty Venting Through Closed Spaces, Appliance Vent Adapter

Page 11

Venting Through Closed Spaces

1/4" per foot

Wall Thimble

downward slope

 

 

 

 

 

Fire

Stop

Vent Pipe

Ceiling

 

Board

 

Inspection

Inspection

Access Panel #1

Access

 

 

Panel #2

If the vent piping passes through a closed space, a minimum clearance of 8” (20 cm) when installed horizontally or 6” (15 cm) when installed vertically should be maintained between the vent pipe and combustibles and noncombustibles. Be sure to follow local codes and vent manufacturer’s installation instructions.

For maintenance and inspection purposes, the following access panels are required.

Two (2) inspection access panels large enough to allow access for venting inspection. One (1) of these access panels should be close to where the vent pipe enters the ceiling. The other access panel should be near the vent termination.

A ventilation access panel with a 16 in2 (103 cm2) opening should be provided every 10 ft (3 m).

CAUTION: Ensure that the appliance vent adapter is securely attached to the water heater collar.

Exhaust

Flow

Appliance Vent Adapter

The water heater must be installed with a UL 1738 approved Category III Stainless Steel appliance vent adapter.

Read the following instructions before installation.

Slide adapter end “A” down over heater

collar “B” as far as it will go.

Tighten the clamp around the collar.

Inspect the inside of the adapter to verify

that the collar and adapter are sealed. If

High Temp. Sealant

Appliance

Vent Adapter

A Clamp

Test fit the adapter over the water heater

collar before proceeding. Adjust clamp as

needed.

With an alcohol wipe, clean inside surface

“A” of adapter and outside surface “B” of

heater collar.

more sealant is required, apply sealant to a

flat tool, then spread around the collar edge

on inside of adapter.

Ensure that the clamp does not interfere

with the damper shaft.

B Collar

Water Heater

Apply 1/4” (6 mm) wide bead of high

temperature silicone (500°F [260°C])

around outside of heater collar “B”.

NOTICE: Follow the appliance vent adapter manufacturer’s instructions.

CAUTION: Condensate is known to be acidic; refer to local, state (provincial) or federal codes for proper handling and discharge methods.

CAUTION: Condensate must drain away from the water heater and should not be allowed to drain back into any part of the vent system.

WARNING: Failure to provide a vent condensate drain close to the appliance could allow acidic flue gas condensate to enter into appliance flueways, causing premature failure of the appliance.

Draining the Condensate

Provision should be made to collect and dispose of condensate from venting systems.

When a water heater is vented horizontally, the vent pipe can have a DOWNWARD or UPWARD slope towards the termination. If an UPWARD slope is used, a condensate trap must be installed as close as practical to the water heater in order to prevent condensate from draining back into the water heater. See Examples A and B on page 14 for DOWNWARD and UPWARD slope for horizontally vented water heaters.

When a water heater is vented vertically, an UPWARD slope must always be used. A condensate trap must be installed in the horizontal section of the vent and as close as practical to the water heater in order to prevent condensate from draining back into the water heater. See the diagram on page 15 showing UPWARD slope for vertically vented water heaters.

Always attach a drain hose to the drain fitting and plumb the hose to a sanitary sewer drain.

A high temperature silicone tubing suitable for use with acidic condensate and appropriate for the temperature range should be used.

The drain tube is fashioned into a “pigtail” trap and must be filled with water to prevent flue gases from emitting into the building prior to operating the appliance.

11

Image 11
Contents Tankless Water Heater Injury You can find them on a label on the applianceThat will result in death or serious Install and Properly Vent the Water HEATER… N G E R Natural GAS and Liquefied Petroleum Models Read and Follow this Safety Information Carefully Location of the Outdoor water heater Installing the Outdoor water heater Location of Indoor Water Heater Installing the Indoor water heaterInspect Shipment Combustion and Ventilation Air Indoor Water Heater OnlyCorrosive Atmospheres Minimum Vent Length The venting VentingVenting Lengths Maximum Vent LengthDraining the Condensate Venting Through Closed SpacesAppliance Vent Adapter Horizontal Vent Terminal Location Installing the water heaterAdditional Considerations Outdoor Water HeaterIndoor Water Heater Vent Horizontal Wall Thimble Installation Vertical Vent Termination Location Vertical Vent InstallationWater Supply Connections Mounting the Water HeaterThermal Expansion Water Filter Clean Water Inlet Check Valve Nipple Relief Valve High Altitude Leak TestingPressure Testing the Gas Supply System Gas SupplyDescription Range Number Remote Control InstallationControl ModelRemote Control ExtensionWall CablePenetration Suitable Indoor or Outdoor water heaters Electrical ConnectionIndoor water heaters only Outdoor Models Indoor ModelsDo’s Hot and Cold Pipe Insulation InstallationDuring Installation of this water heater… Insulation BlanketsInstallation Check List To Turn OFF GAS to Appliance Lighting the water heaterOperating the water heater Safety PrecautionsWater Temperature Setting Time/Temperature Relationship in ScaldsWater Temperature Setting… Drain heater. See Draining Water Heater section on Routine Preventative MaintenanceHousekeeping Condensate Trap Inspection Venting System InspectionBurner Inspection Vacation and Extended Shut-DownFreeze Protection Draining the Water HeaterBefore You Call For Service… Outdoor Water Heater Only Indoor Water Heater OnlyInstructions For Placing a Parts Order Replacement PartsTemperature Setting DIP Switch Adjustment If YOU Need Service