Eclipse continued.
Recovery Capacities Recovery at various temperature rises
|
|
|
|
|
| TEMPERATURE RISE |
|
|
| ||
INPUT | EQUIVALENT |
| 40°F | 50°F | 60°F | 70°F | 80°F | 90°F | 100°F | 110°F | 120°F |
KW | BTU/HR | UNITS | (22°C) | (28°C) | (33°C) | (39°C) | (45°C) | (50°C) | (56°C) | (61°C) | (67°C) |
12.4 | 42,309 | GPH | 126 | 100 | 84 | 72 | 63 | 55 | 50 | 45 | 42 |
|
| LPH | 478 | 379 | 318 | 273 | 239 | 209 | 190 | 171 | 159 |
18 | 61,420 | GPH | 186 | 149 | 124 | 106 | 93 | 83 | 74 | 68 | 62 |
|
| LPH | 705 | 565 | 470 | 402 | 352 | 315 | 280 | 258 | 235 |
24 | 81,893 | GPH | 248 | 199 | 165 | 142 | 124 | 110 | 99 | 90 | 83 |
|
| LPH | 940 | 754 | 625 | 538 | 470 | 417 | 375 | 341 | 315 |
Electrical Characteristics
|
|
|
|
|
|
| FULL LOAD CURRENT – IN AMPERES |
| |||
INPUT | NUMBER | ELEMENT | NUMBER | NUMBER | 208V | 240V | 277V | 480V | |||
KW | OF ELEMENTS | WATTAGE | OF FUSES | OF THERMOSTATS | PHASE 1 | PHASE 3 | PHASE 1 | PHASE 3 | PHASE 1 | PHASE 1 | PHASE 3 |
12.4 | 4 | 3100 | 8 | 2 | 60 | 39 | 52 | 34 | 45 | 26 | 17 |
18 | 4 | 4500 | 8 | 2 | 87 | 57 | 75 | 50 | 65 | 38 | 25 |
24 | 4 | 6000 | 8 | 2 | 115 | 76 | 100 | 66 | 87 | 50 | 35 |
Dimensional Information All dimensions shown in English and Metric
MODEL |
| A | B | C | D | APPROX. SHIP. |
NUMBER | UNITS | WEIGHT | ||||
ME85 | inches | 170 lbs. | ||||
| mm | 718 | 1683 | 1784 | 114 | 77 kgs. |
ME105 | inches | 185 lbs. | ||||
| mm | 768 | 1689 | 1797 | 114 | 84 kgs. |
Recommended Specifications:
Water heater(s) shall be model _____________, manufactured by
having electrical input of __________ kW and a recovery rate of _____________ GPH
at a 100°F temperature rise. Water heater(s) shall have a storage capacity of
__________ gallons. Water heater(s) shall have the UL seal of certification and be
factory equipped with an AGA/ASME rated temperature and pressure relief valve. Water heater(s) shall meet or exceed the energy factor requirements of ASHRAE. Tanks shall have a working pressure rating of 150 psi, and shall be completely assembled. Tanks shall be insulated with
D
B C
A
Limited Warranty
This product features a ten year limited warranty against tank leaks. Please refer to
Commercial Warranty Information brochure for complete warranty information.
C O M M E R C I A L
W A T E R H E A T E R S
In keeping with its policy of continuous progress and product improvement,
Rheem Water Heaters • 101 Bell Road, Montgomery, Alabama
Rheem Canada Ltd./Ltée,128 Barton Street West, Hamilton, Ontario L8N 3P3
P R I N T E D I N U . S . A | 1 1 / 0 6 W P | F O R M N O . R R 1 0 2 C E - 6 R ev. 3 |