Rheem 300 series installation instructions Relief Valve Drain, Expansion Control Valve

Page 22

CONNECTIONS – PLUMBING

RELIEF VALVE DRAIN

A copper drain line must be fitted to the relief valve to carry the discharge clear of the water heater. Connect the drain line to the relief valve using a disconnection union. The pipe work from the relief valve to the drain should be as short as possible and fall all the way from the water heater with no restrictions. It should have no more than three right angle bends in it. Use DN15 pipe.

The outlet of the drain line must be in such a position that flow out of the pipe can be easily seen (refer to AS/NZS 3500.4) - but arranged so hot water discharge will not cause injury, damage or nuisance. The drain line must discharge at an outlet or air break not more than 9 metres from the relief valve.

In locations where water pipes are prone to freezing, the drain line must be insulated and not exceed 300 mm in length. In this instance, the drain line is to discharge into a tundish through an air gap of between 75 mm and 150 mm.

Warning: As the function of the temperature pressure relief valve on this water heater is to discharge high temperature water under certain conditions, it is strongly recommended the pipe work downstream of the relief valve be capable of carrying water exceeding 93°C. Failure to observe this precaution may result in damage to pipe work and property.

EXPANSION CONTROL VALVE

Local regulations may make it mandatory to install an expansion control valve (ECV) in the cold water line to the water heater. In other areas, an ECV is not required unless the saturation index is greater than +0.4 (refer to “Water Supplies” on page 30). However, an ECV may be needed in a corrosive water area where there are sufficient quantities of silica dissolved in the water.

The expansion control valve must always be installed after the non return valve and be the last valve installed prior to the water heater (refer to diagram on page 20). A copper drain line must be run separately from the drain of the relief valve.

22

Image 22
Contents Owners Guide Installation Instructions Patents Contents Model Type Temperature AdjustmentAbout Your Water Heater HOW HOT should the Water BE?Safety To Turn OFF the Water HeaterHOW Long will the Water Heater LAST? To Turn on the Water HeaterDoes the Water Quality Affect the Water HEATER? Anode ProtectionPiezo Ignition HOW Your Water Heater WorksMains Pressure Pilot IgniterRegular Care Expansion Control Valve ServicingNot Enough HOT Water or no HOT Water Save a Service CallWater not HOT Enough Continuous dribble Temperature Pressure Relief Valve RunningNormal Operation Steady flows for long period often at nightWater Heater Appears to be Leaking CAN’T Light the Pilot FlameHigh GAS Bills Installation Water Heater LocationSafe Tray Mains Water SupplyTank Water Supply HOT Water DeliveryTemperature Limiting Device Circulated HOT Water Flow and Return SystemAnode Types Reducing Heat LossesSaddling Pipe Work Dimensions and Technical Data Gas DetailsTypical Installation Indoor Location Connection Sizes Connections PlumbingWater Inlet and Outlet Pipe Sizes GAS InletRelief Valve Relief Valve Drain To Fill and Turn on the Water Heater CommissioningGAS Inlet Pressure Safety Information For Your Safety Read Before LightingLighting the Water Heater Using the gas control light the water heater as follows Lighting InstructionsTest the Water Heater After Installation AIR ShutterClose Down Procedure Draining the Water Heater This page is intentionally blank Anode Water SuppliesSaturation Index Warranty Conditions Warranty ExclusionsWarranty Rheem will