LIGHTING THE WATER HEATER

TEST THE WATER HEATER AFTER INSTALLATION

The operation of the water heater must be thoroughly checked by the installer.

The burner flame must light smoothly and quickly from the pilot flame, and must go out quietly and completely.

The main burner flame must be stable, although slight lifting at the front edge of the burner is acceptable when the burner is cold.

The main burner flame should be blue, with a clearly defined inner cone - luminous yellow or "floating" flames are not acceptable, and must be corrected by opening the air shutter (refer to “Air Shutter” on page 26).

Check the test point pressure and compare with the rating label. The pressure regulator is not adjustable and if the test point pressure is not within 5% of the specified value, refer to Rheem or their Accredited Service Agent.

If unable to get the water heater working properly, contact the nearest Rheem Service Department or their Accredited Service Agent.

When satisfied everything is working properly instruct the user in the correct method of operation.

AIR SHUTTER

The air shutter is a hinged flap in the burner aeration tube. It may require adjustment on installation.

For a Propane and Butane model, the air shutter should be fully open.

For a Town and TLP model, the air shutter should be within 10 mm of the top of the burner aeration tube.

The shutter is held in place by a screw on the side of the burner aeration tube.

Note: A Natural gas model does not have an air shutter.

26

Image 26
Contents Owners Guide Installation Instructions Patents Contents Model Type Temperature AdjustmentAbout Your Water Heater HOW HOT should the Water BE?Safety To Turn OFF the Water HeaterHOW Long will the Water Heater LAST? To Turn on the Water HeaterDoes the Water Quality Affect the Water HEATER? Anode ProtectionPiezo Ignition HOW Your Water Heater WorksMains Pressure Pilot IgniterRegular Care Expansion Control Valve ServicingWater not HOT Enough Save a Service CallNot Enough HOT Water or no HOT Water Continuous dribble Temperature Pressure Relief Valve RunningNormal Operation Steady flows for long period often at nightHigh GAS Bills CAN’T Light the Pilot FlameWater Heater Appears to be Leaking Installation Water Heater LocationSafe Tray Mains Water SupplyTank Water Supply HOT Water DeliveryTemperature Limiting Device Circulated HOT Water Flow and Return SystemSaddling Pipe Work Reducing Heat LossesAnode Types Dimensions and Technical Data Gas DetailsTypical Installation Indoor Location Water Inlet and Outlet Connections PlumbingConnection Sizes Relief Valve GAS InletPipe Sizes Relief Valve Drain GAS Inlet Pressure CommissioningTo Fill and Turn on the Water Heater Lighting the Water Heater For Your Safety Read Before LightingSafety Information Using the gas control light the water heater as follows Lighting InstructionsTest the Water Heater After Installation AIR ShutterClose Down Procedure Draining the Water Heater This page is intentionally blank Saturation Index Water SuppliesAnode Warranty Conditions Warranty ExclusionsWarranty Rheem will