Desa VFRMV18NB Check GAS Type, Installation and Clearances for vent-free operation, Ceiling

Page 9

Installation

Continued

WARNING: Seal any fresh air vents or ash clean-out doors located on floor or wall of fire- place. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney flue damper.

WARNING: Never install the heater

in a bedroom or bathroom unless installed as a vented appliance, see page 12

in a recreational vehicle

where curtains, furniture, clothing or other flammable objects are less than 42" from the front, top or sides of heater

in high traffic areas

in windy or drafty areas

CAUTION: This heater cre- ates warm air currents. These currents move heat to wall sur- faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning flu- ids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.

IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 6.

CHECK GAS TYPE

Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install in fireplace. Call dealer where you bought the appliance for proper type of appliance.

WARNING: This appliance is equipped for (natural or pro- pane/LP) gas. Field conversion is not permitted.

INSTALLATION AND CLEARANCES for vent-free operation

WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling and adjoining wall.

MINIMUM FIREPLACE CLEARANCE TO

COMBUSTIBLE MATERIALS

SIDE WALL

 

 

16"

 

 

CEILING

 

 

42"

 

 

 

FLOOR

 

 

5"

 

 

 

 

 

 

 

 

LOG SIZING REQUIREMENTS

 

 

 

 

 

 

 

 

MINIMUM FIREBOX SIZE

LOG

 

 

 

 

 

FRONT

REAR

SIZE

HEIGHT

DEPTH

WIDTH

WIDTH

18"

 

18"

 

14"

30"

20.5"

 

 

 

 

 

 

 

24"

 

18"

 

14"

35"

24.5"

*Measured at 14" depth

Allow adequate clearances for accessibility for purposes of servicing and proper operation

Carefully follow the instructions below. This will ensure safe installation into masonry, UL127- listed manufactured fireplace or listed vent-free firebox.

Minimum Clearances For Side Combustible Material, Side Wall and

Ceiling

A. Clearances from the side of the fireplace cabinet to any combustible material and wall should follow diagram in Figure 4, page 10. Example: The face of a mantel, bookshelf, etc. is made of combustible material must be 4" from the side of the fireplace to the cabinet (see Figure 4, page 10).

B. Clearances from the top of the fireplace open- ing to the ceiling should not be less than 42".

116412-01Bwww.desatech.com

Image 9 Contents
Ansi Z21.11.2b-2004 Ansi Z21.60-2003 Models VFRMV18NB, VFRMV18PB VFRMV24NB and VFRMV24PBTable of Contents Safety Information Safety Information Product Features Optional Remote Control AccessoriesProduct Identification Local CodesProviding Adequate Ventilation Air For Combustion VentilationDetermining FRESH-AIR Flow For Appliance LocationAIR for Combustion Ventilation Ventilation AIRVentilation Air From Inside Building Ventilation Air From Outdoors InstallationInstallation and Clearances for vent-free operation Check GAS TypeCeiling Minimum Noncombustible Material Clearances Safe InstallationFloor Clearances Mantel ClearancesInstalling Remote Control Accessory bracket Installing Damper Clamp Accessory for Vented OperationInstalling Heater Assembly Masonry Manufactured FireplaceFireplaceInstallation Items Needed Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Propane/LP FromPressure Testing Heater Gas Connections Piping System Test Pressures In Excess Of 1/2 Psig KPaTest Pressures Equal To or Less Than Psig 3.5 kPa For Your Safety Read Before Lighting Operating HeaterLighting Instructions To Turn OFF GAS To Appliance Operating HeaterPropane/LPNatural Shutting Off HeaterOptional Hand-Held Manual Lighting ProcedureRemote Operation On/Off Series Model HRC100Auto Shutoff Feature Safety FeaturesKey Pad Lock Feature Inspecting BurnersCleaning Maintenance Burner Flame PatternBurner Injector Holder Pilot Air Inlet Hole Wiring Diagram Cleaning MaintenanceTechnical Service Propane/LPObserved Problem Possible Cause Remedy TroubleshootingMaintenance, TroubleshootingOperation Processes and logs curing Hours of operation Checking Gas Connections Gas leak. See warningReplacement Parts SpecificationsService Hints AccessoriesAccessories Models VFRMV18NB, VFRMV18PB, VFRMV24NB Shown and VFRMV24PB Illustrated Parts BreakdownParts List 116412-01B 116412-01B Warranty Information Keep this WarrantyLimited Warranty VENT-FREE GAS LOG Heaters