Desa CCL3930PTB, CCL3018PTA Checking GAS Connections, Pressure Testing Gas Supply Piping system

Page 12

12

INSTALLATION

Connecting to Gas Supply (Cont.) Checking Gas Connections

INSTALLATION

Continued

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 16).

IMPORTANT: Install equipment valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 16. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

Propane/LP Supply Tank

External

Regulator

Vent Pointing

Down

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all

Figure 15 - External Regulator With Vent Pointing Down

joints. Bubbles forming show a leak. Correct all leaks at once.

PROPANE/LP -

From External

Regulator (11" W.C.

**to 14" W.C. Pressure) NATURAL - From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)

CSA Design-Certified

Equipment Shutoff Valve

With 1/8" NPT Tap*

Approved Flexible Gas Hose (if allowed by local codes)

CAUTION: Make sure external regulator has been installed between propane/LP supply and heater. See guidelines under Connecting to Gas Supply, page 11.

Pressure Testing Gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

Tee Joint

Pipe Nipple

3" Minimum

Gas

Cap

Regulator

 

Sediment Trap

 

Figure 16 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 26.

**Minimum inlet pressure for purpose of input adjustment.

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping sys- tem. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncor- rosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

For..com

111160-01B

Image 12
Contents What to do if YOU Smell GAS 18, 24, and 30 VariableCRL2718P/N CRL3124P/NTable of Contents Safety InformationProduct Identification Product Features AIR for Combustion and Ventilation Local CodesUnpacking Determining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceDetermining if You Have a Confined or Uncon- fined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Installation Check GAS TypeIf Using Mantel Minimum Noncombustible Material Clearances Determining Minimum Mantel Clearance When Using a Hood Mantel Clearances Floor Clearances Determining Minimum Mantel ClearanceInstalling Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyInstallation Items Needed Connecting to GAS Supply Attaching Flexible Gas Hose to Heater Gas RegulatorPressure Testing Gas Supply Piping system Checking GAS ConnectionsInstalling Logs Pressure Testing Heater Gas ConnectionsInstalling Back Log #1 Installing Middle Log #2 CCL3930PTB/NTB Shown Installing Crossover Log #6 CCL3930PTB/NTB Shown Single Burner Seasonal Oak Models CRL2718P/N, CRL2718P/NOperating Heater Lighting InstructionsVariable Control Operation To Turn OFF GASTo Appliance Shutting Off HeaterManual Lighting Procedure InstructionsInspecting Burners To Turn OFF GAS To ApplianceThermostat Control Operation Pilot Flame PatternCleaning Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleBurner Primary AIR Holes Main BurnerTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement Optional Positioning of Thermostat Sensing Bulb For Masonry and Factory-built Metal FireplaceReplacement Parts AccessoriesService Hints Technical ServiceSpecifications Dual Burner Smoky Mountain OAK ModelsDual Burner Biltmore Split OAK Models Single Burner Seasonal OAK ModelsIllustrated Parts Breakdown Parts List Variable MANUALLY-CONTROLLED Biltmore Split OAK ModelsModels CGD3018PT, CGD3018NT, CGD3924PT and CGD3924NT THERMOSTATICALLY-CONTROLLED Smoky Mountain OAK Models Models CCL3018PTA and CCL3018NTA THERMOSTATICALLY-CONTROLLED Biltmore Split OAK Models KEY Part Number CCL3018PTA CCL3018NTA Description QTYModels CCL3924PTA, CCL3924NTA, CCL3930PTB and CCL3930NTB Parts List Variable Manually Controlled Seasonal OAK CRL3124P and CRL3124NVariable MANUALLY-CONTROLLED Seasonal OAK Models Description QTYParts Central Owners Registration Form Postage Required 111160-01B Warranty Information Keep this Warranty