Troubleshooting
Display | Cause | Solution |
|
|
|
E9 | Temperature limiter opened circuit | Check connections.* |
| (overheat). Trips at 220F (104C). | Check heat exchanger condition.* |
|
|
|
EA | No ionization during safety time (safety time | Check gas pressure.* |
| out). | Check that gas is not diluted with air, as a result |
|
| from recent gas pipeline rework.*. |
|
| Check if vent terminal is blocked (especially when |
|
| the appliance starts up for some seconds and then |
|
| looses ionization signal).* |
|
| Check ionization electrode.* |
|
| Check for a proper ground.* |
|
|
|
FA | Leakage error (gas valves do not close gas | Check gas valve and control unit.* |
| circuit). |
|
|
|
|
F7 | Ionization error (flame sensing at | Check control unit.* |
|
|
|
E0 | Internal software/hardware failure. | Check control unit.* |
|
|
|
A7 | Hot water temperature sensor/receiver | Check water temperature sensor/receiver and |
| defect (from control unit). | connections.* |
|
| Check room area temperature where heater is |
|
| located, it must be above 36°F (2°C) |
|
|
|
A9 | Hot water temperature sensor/receiver mis- | Check that the water temperature sensor/receiver is |
| assembled (from control unit). | properly assembled in the water pipe.* |
|
| Check if vent terminal is blocked or if vent terminal is |
|
| according with chapter 2.9.* |
|
| In case of high altitude installation confirm that |
|
| necessary adjustment steps have been taken.* |
|
|
|
C1 | FAN rotation too low at | Check supply voltage.* |
| control unit). | Check fan and connections.* |
|
| Check control unit.* |
|
| Check if vent terminal is blocked or if vent terminal is |
|
| according with chapter 2.9. * |
|
| Check CO2 levels (see chapter 9).* |
|
|
|
C6 | FAN rotation too low at operation (from | Check supply voltage.* |
| control unit). | Check fan and connections.* |
|
| Check control unit.* |
|
| Check if vent terminal is according with |
|
| chapter 2.9.* |
|
|
|
C7 | No rotational speed sensor signal from FAN | Check fan and connections.* |
|
| Check control unit.* |
|
| Check CO2 levels (see chapter 9).* |
CA | Water flow signal over specified maximum | Check water valve and flow sensor.* |
| value |
|
|
|
|
E2 | Inlet temperature sensor fault | Check water temperature sensor/receiver and |
|
| connections.* |
|
| Check room area temperature where heater is |
|
| located, it must be above 36°F (2°C) |
|
|
|
A2 | Overheat protection fault | Check connections to the overheat protection.* |
|
| Check sensor continuity.* |
|
| Check heat exchanger sealings and walls.* |
|
|
|
Table 5
* By installer or service technician only.
26 | 6 720 607 072 |