SERVICE PROCEDURE E32-I

Heating Element Testing

Testing For Open Or Burned Out Element.

Step 1. TURN OFF POWER TO WATER HEATER.

Step 2. Remove thermostat/element access cover(s) from front of water heater. Remove insulation and plastic cover from thermostat.

Step 3. Disconnect wires from heating element. Step 4. Set multi-meter to “ohms” setting.

Step 5. Touch probes of multi-meter to screw terminals of heating element

(see illustration 1).

Step 6. Reading should be 12.8 ohms (±6%) for a 240 volt, 4500 watt element, see table below:

Ohms = Volts2 Watts

WARNING

High voltage exposure. Be sure power is turned

OFF to water heater prior to performing this

procedure.

A reading outside the range using the formula above (±6%), indicates a bad element and the element must be replaced.

Ohms of electrical Resistance

Element

 

Voltage Rating of Element

 

208

240

480

Wattage

2000

21.6

28.8

115.2

3000

14.4

19.2

76.8

4000

10.8

14.4

57.6

4500

9.6

12.8

51.2

5000

8.7

11.5

46.1

6000

7.2

9.6

38.4

Testing For Heating Element Short Circuit To Ground.

Step 1. TURN OFF POWER TO WATER HEATER.

Step 2. Remove access cover(s) from front of water heater. Remove insulation and plastic cover from thermostat.

Step 3. Disconnect wires from heating element. Step 4. Set multi-meter to “ohms” setting.

Step 5. Touch one probe of multi-meter to either screw terminal of heating element and the other on the element flange (see illustration 2). There should be no reading on the ohm meter. Any reading indicates a grounded element and the element must be replaced. Repeat this step for the other screw terminal.

Element Screw Terminals

 

Illustration 1

NOTE

Disconnect

 

 

element

 

Wires

NOTE

Disconnect

element

Wires

Element Screw Terminal

Meter Probe

Element Flange

Illustration 2

Page 11

Image 11
Contents Commercial Electric Energy Saver E32 Medium Duty Commercial Electric Water Heaters Service ProcedureRED General InformationRED Black RED Input Kw 208V 240V 277V 380V 415V 480V Full Load Amperes-Phase 1/PhaseSequence of Operation Sequence of OperationField Conversion for E32 Series Phase Conversion Rating Plate Overlay Kits Electrical Phase ConversionThree-Phase to Single-Phase Single-Phase to Three-PhaseBradford White Corporation Rating Plate ModificationTroubleshooting Injury Making voltage checks to avoid personalOFF to water heater prior to performing this Service Procedure E32-IHeating Element Testing High voltage exposure. Be sure power is turnedLine Voltage Testing Service Procedure E32-IILine Voltage Testing High voltage exposure. Use caution to avoid Service Procedure E32-IIIFuse Testing Personal injury during this procedureWater Temperature In Tank Is Above Thermostat Setting Service Procedure E32-IVThermostat Testing Thermostat Replacement Service Procedure E32-VHigh voltage exposure. Be sure power is OFF when performing this procedureHeating Element Removal Heating Element ReplacementAnode Inspection and Replacement Service Procedure E32-VIIDip Tube and Anode Inspection Replacement Asse Approved Mixing Valve optional Page Parts@bradfordwhite.com Techserv@bradfordwhite.com
Related manuals
Manual 12 pages 60.05 Kb

Commercial Electric Energy Saver Medium Duty E32 Series Models, E32-80R, E32-50S, E32-120R specifications

Bradford-White Corporation offers a range of high-efficiency water heaters, including the E32 series models: E32-120R, E32-50S, and E32-80R. These models fall under the Commercial Electric Energy Saver Medium Duty category, designed for various commercial applications that require reliable hot water delivery.

The E32 series is built to meet the demands of commercial environments while ensuring energy efficiency. The E32-120R model features a 120-gallon capacity, making it ideal for establishments with high hot water usage. Similarly, the E32-50S offers a 50-gallon capacity, suitable for smaller commercial operations, while the E32-80R provides an 80-gallon option for medium-sized applications. Each model is designed to deliver hot water on demand, with recovery rates optimized for commercial settings.

A notable feature of the E32 series is its Energy Saver technology. These models are equipped with high-efficiency insulation and advanced heating components that minimize heat loss and reduce energy consumption. This not only leads to lower utility bills but also contributes to a reduced carbon footprint, aligning with contemporary environmental standards.

The integration of an advanced electronic control system in the E32 series allows for precise temperature control and monitoring. Users can easily set and adjust water temperatures to meet specific needs, enhancing comfort and safety. Additionally, these models are designed with user-friendly installation features, allowing for straightforward setup and integration into existing systems.

Durability is a hallmark of the E32 series, with each model constructed using high-quality materials that withstand the rigors of commercial use. The tanks are designed to resist corrosion, ensuring a long lifespan and reliable performance. Furthermore, these heaters come with warranties that reflect Bradford-White’s commitment to quality and customer satisfaction.

Maintenance is easy with the E32 series, featuring replaceable heating elements and accessible anodes. This reduces downtime and increases the longevity of the units. Moreover, they comply with all safety and performance regulations, providing peace of mind for business owners.

In summary, the Bradford-White E32-120R, E32-50S, and E32-80R models are versatile, energy-efficient, and durable solutions for commercial hot water needs. Their combination of advanced technology, user-centric features, and robust construction make them a reliable choice for various commercial applications.