through 13. These diagrams are meant only as a guide. Components required by local codes must be properly installed.

The minimum inlet water temperature for the Brute Deluxe is 120°F (49°C) to avoid condensing on the copper coils.

4B.2 Hot Water Supply Piping — Water Heater

Follow the tank manufacturer’s guidelines for completion of the hot water system connections.

NOTE: A listed temperature and pressure relief valve listed as complying with the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems (ANSI Z21.22 / CSA 4.4) of suitable discharge capacity must be installed in the separate storage tank system.

If the Brute Deluxe water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold water supply line, the relief valve may discharge periodically, due to thermal expansion. Means (such as a properly-sized expansion tank) shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situation.

4B.3 Water Flow Requirements — Water Heater

In a water heating application (an open system), new water is constantly being introduced. With the new water comes a fresh supply of minerals that can be deposited on the unit’s heat exchanger. This is commonly known as scaling. The amount of minerals will depend upon the hardness of the water. Water can also be aggressive, and can erode metals, including copper, if the water is moved too quickly. The water flow requirements for the Brute Deluxe water heater are based upon the hardness of the water. The water flow is kept high enough to prevent scaling, but low enough to prevent tube erosion. For extremely soft or hard water, cupro-nickel tubes are available. Contact a Representative if you have questions or concerns about water quality.

Pump-mounted water heaters can be ordered with standard pumps for soft or normal water or with pumps for hard water. The pumps used are sized for the headloss through the heater, plus 30 feet (9.1m) of full- sized piping (same size as heater outlet) and a normal number of fittings.

Table 9 specifies water flow rates for water heaters, which will enable the user to size a pump. The headloss shown is for the heater only, and the user will need to add the headloss of the piping system to properly size the pump.

4B.4 Combined Water Heating (potable) and Space Heating — Water Heater

NOTE: These systems are not allowed in the Commonwealth of Massachusetts.

Piping and components connected to this water heater for the space heating application shall be suitable for use with potable water.

Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.

This water heater when used to supply potable water shall not be connected to any heating system or component(s) previously used with a non-potable water heating appliance.

When the system requires water for heating at temperatures higher than required for other uses, an anti-scald mixing or tempering valve shall be installed to temper the water for those uses in order to reduce scald hazard potential.

4B.5 Freeze Protection – Water Heater

Although Brute Deluxe water heaters are design- certified for outdoor installations, such installations are not recommended in areas subject to freezing temperatures, unless proper precautions are taken.

Power outage, interruption of gas supply, failure of system components, activation of safety devices, etc., may prevent a heater from firing. Any time a heater is sub- jected to freezing conditions, and the heater is not able to fire, and/or the water is not able to circulate, there is a risk of freezing in the heater or in the pipes in the system. When water freezes, it expands. This can result in bursting of pipes in the system, or damage to the heater, which could result in leaking or flooding conditions.

Contact the local factory representative or for additional information.

SECTION 5.

Electrical Connections

WARNING

The appliance must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electrical Code, Part 1, in Canada. Do not rely on the gas or water piping to ground the metal parts of the boiler. Plastic pipe or dielectric unions may isolate the boiler electrically. Service and maintenance personnel, who work on or around the boiler, may be standing on wet floors and could be electrocuted by an ungrounded boiler.

Single pole switches, including those of safety controls and protective devices must not be wired in a grounded line.

All electrical connections are made in the field

Image 15
Contents Brute Deluxe Table of Contents General Information IntroductionModel Identification Clearances WarrantyDimensions Locating the Appliance57¾ 33¾ 16¾ 42545¾ 22¾ 50534¼ 10¼ 80¾ 16¾ 46¼22¾ 58¼ 28¾ 70¼Intake Combustion Air Venting and Combustion AirCombustion Air Combustion Air From RoomCommon Venting Systems VentingVent Categories Category I VentVertical Vent Terminal Locating Vent & Combustion Air TerminalsSide Wall Vent Terminal Side Wall Combustion Air TerminalCombustion Air and Vent Through Side Wall Vertical Combustion Air Terminal Common Vent Test BoilersNatural Gas Supply and PipingVent Terminals for Outdoor Units Natural Propane4A.1 Heating System Piping Hot Supply Connections Boiler Water Connections Boiler4A.4 Freeze Protection Boiler Water Connections Water Heater4A.2 Cold Water Make-Up Boiler 4A.3 Water Flow Requirements Boiler4B.5 Freeze Protection Water Heater Electrical Connections4B.2 Hot Water Supply Piping Water Heater 4B.3 Water Flow Requirements Water HeaterHydronic Piping Multiple Boilers, Primary Secondary System Hydronic Piping One Boiler, Multi-Temperature System Water Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Flow Requirements BMT2V Water Heater Piping Multiple Heaters, Multiple TanksField Wiring Main PowerBrute Deluxe 1000 Wiring Diagram Brute Deluxe 500-750 Connection Diagram Brute Deluxe 1000 Connection Diagram Brute Deluxe 1250-2000 Connection Diagram Filling the System External Staging Control WiringOperating Instructions Sequence of OperationExternal Boiler Operations Operating Temperature ControlOperating the Burner and Set Up Set Up for 0 to 2500 Feet AltitudeHigh Altitude Adjustment and Set Up Shutting Down the Brute Deluxe MaintenanceSystem Maintenance Appliance Maintenance Component DescriptionFilter Manual Reset High Limit ControlTemperature Control Flow SwitchTrouble Shooting Delayed Ignition Possible CausesResolving Lockouts High Gas Consumption Replacement PartsShort Cycling Water Heater Parts List see next Short Cycling BoilerInternal Components See Figure Sheet Metal Components See FigureGas Train Components See Figure Heat Exchanger Components See Figure Electrical Components See Figure Sheet Metal Components Internal Components Brute Deluxe Water Heater Brute Deluxe Hydronic BoilerElectrical Components

BMT2H, BMT2V, Hydronic Boiler, Water Volume Heater specifications

Bradford-White Corporation, a leader in the water heating and hydronic heating industries, offers an impressive range of products designed to meet diverse residential and commercial needs. Among their notable innovations are the BMT2V and BMT2H series hydronic boilers and water volume heaters, which combine state-of-the-art technology with user-friendly features.

The BMT2V and BMT2H models are designed to deliver high-efficiency heating solutions for various applications. One of the key features of these boilers is their superior thermal efficiency, which reduces fuel consumption while ensuring optimal output. With a range of BTU inputs suitable for different heating needs, these boilers can provide efficient heating for residential, commercial, and industrial applications.

Both the BMT2V and BMT2H units are built with advanced combustion technology, allowing for cleaner and more efficient burning of fuel. This not only contributes to lower emissions but also ensures that the boilers operate quietly and reliably. The integrated draft inducer further enhances the efficiency of the combustion process by optimizing airflow, leading to improved overall performance.

Another standout characteristic of these models is their robust construction. Made with high-quality materials, the BMT2V and BMT2H boilers are designed to endure harsh operational conditions while providing long-lasting performance. The tanks are lined with corrosion-resistant coatings, which significantly extend the lifespan of the unit and reduce maintenance requirements.

Both models are also equipped with smart control systems that enable precise temperature regulation and easy monitoring of system performance. These controls allow users to adjust settings remotely or via integrated digital interfaces, further enhancing user convenience. Additionally, the integration of safety features, such as pressure relief valves and automated shut-off systems, ensures safe operation.

The BMT2 series also emphasizes ease of installation and maintenance. Compact designs and flexible venting options allow for versatile installation in various environments. Serviceability is streamlined through easily accessible components, ensuring that technicians can perform maintenance tasks efficiently.

In summary, Bradford-White's BMT2V and BMT2H hydronic boilers and water volume heaters embody efficiency, durability, and advanced technology. With their focus on sustainability and high performance, these models are ideal choices for anyone looking to invest in reliable heating solutions.