Bradford-White Corp BMT2V Locating Vent & Combustion Air Terminals, Side Wall Vent Terminal

Page 9

Brute Deluxe (500-2000)

Page 9

 

lation Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe. Horizontal runs must slope downwards not less than ¼ inch per foot (2 cm/m) from the unit to the vent terminal. Reference Table 1 for the size of the Category III vent system. Up to three elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable linear feet (3.0m) for every additional elbow used.

WARNING

The outdoor vent terminal gets hot. Unit must be installed in such a way as to reduce the risk of burns from contact with the vent terminal.

2.3Locating Vent & Combustion Air Terminals

2.3.1 Side Wall Vent Terminal

The appropriate side wall vent hood must be used, and is listed in the installation and operation manual. The terminal provides a means of installing the vent piping through the building wall, and must be located in accordance with ANSI Z223.1/NFPA 54 and applicable local codes. In Canada, the installation must be in accordance with CSA B149.1 or .2 and local applicable codes. Consider the following when installing the terminal:

1.Figure 4 shows the requirements for mechanical vent terminal clearances for the U.S. and Canada.

2.Vent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway, or over an area where condensate or vapor could create a nuisance or hazard.

3.Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets.

4.Locate the vent terminal so that vent gases cannot enter the building through doors, windows, gravity inlets or other openings. When possible, locations under windows or near doors should be avoided.

5.Locate the vent terminal so that it cannot be blocked by snow. The National Fuel gas code requires that it be at a minimum of 12" above grade. In a location that has the possibility of snow accumulation, it is critical the installer places the vent at least 12" higher than the maximum potential snow line. Seek local municipalities and their codes for appropriate installation techniques.

6.Locate the terminal so the vent exhaust does not settle

TERM

DESCRIPTION

 

 

Pipe

Must comply with UL Standard 1738

 

such as Type 29-4C Stainless Steel

 

(either insulated or non-insulated).

Joint

Follow vent manufacturer’s instructions

Sealing

 

 

 

Table 5. Required Horizontal Venting Material.

on building surfaces or other nearby objects. Vent products may damage such surfaces or objects.

7.If the boiler or water heater uses ducted combustion air from an intake terminal located on the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.

2.3.2 Side Wall Combustion Air Terminal

The side wall combustion air terminal (see Table 2) must be used when the unit takes its combustion air through a duct from a side wall. Consider the following when installing the terminal:

1.Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning fluid, chlorinated compounds, etc.)

2.Locate the terminal so that it will not be subject to damage by accident or vandalism.

3.Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel gas code requires that it be at a minimum of 12" above grade. Depending on local conditions, the installer should ensure that it remains at least 12" above the maximum potential snow line. Seek local municipalities and their codes for appropriate installation techniques.

WARNING: It is critical that the combustion air intake and the vent terminals remain at least 12" above the maximum potential snow line. If either the vent terminal or the air terminal is blocked by snow, there may be potential for the unit to produce excess carbon monoxide and or recirculate flue gasses into the building/dwelling. Personal injury or DEATH may occur. Natural snowfall, drifting, and banking should all be taken into account when locating the terminals in a potential snow environment.

4.If the Brute Deluxe is side-wall vented to the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal (see Figure 4).

2.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 3). Seek local municipalities and their codes for appropriate installation techniques.

Image 9
Contents Brute Deluxe Table of Contents General Information IntroductionModel Identification Dimensions WarrantyLocating the Appliance Clearances45¾ 33¾ 16¾ 42522¾ 505 57¾22¾ 58¼ 16¾ 46¼28¾ 70¼ 34¼ 10¼ 80¾Combustion Air Venting and Combustion AirCombustion Air From Room Intake Combustion AirVent Categories VentingCategory I Vent Common Venting SystemsSide Wall Vent Terminal Locating Vent & Combustion Air TerminalsSide Wall Combustion Air Terminal Vertical Vent TerminalCombustion Air and Vent Through Side Wall Vertical Combustion Air Terminal Common Vent Test BoilersVent Terminals for Outdoor Units Gas Supply and PipingNatural Propane Natural4A.1 Heating System Piping Hot Supply Connections Boiler Water Connections Boiler4A.2 Cold Water Make-Up Boiler Water Connections Water Heater4A.3 Water Flow Requirements Boiler 4A.4 Freeze Protection Boiler4B.2 Hot Water Supply Piping Water Heater Electrical Connections4B.3 Water Flow Requirements Water Heater 4B.5 Freeze Protection Water HeaterHydronic Piping Multiple Boilers, Primary Secondary System Hydronic Piping One Boiler, Multi-Temperature System Water Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Flow Requirements BMT2V Water Heater Piping Multiple Heaters, Multiple TanksField Wiring Main PowerBrute Deluxe 1000 Wiring Diagram Brute Deluxe 500-750 Connection Diagram Brute Deluxe 1000 Connection Diagram Brute Deluxe 1250-2000 Connection Diagram Operating Instructions External Staging Control WiringSequence of Operation Filling the SystemOperating the Burner and Set Up Operating Temperature ControlSet Up for 0 to 2500 Feet Altitude External Boiler OperationsHigh Altitude Adjustment and Set Up System Maintenance MaintenanceAppliance Maintenance Component Description Shutting Down the Brute DeluxeTemperature Control Manual Reset High Limit ControlFlow Switch FilterTrouble Shooting Delayed Ignition Possible CausesResolving Lockouts Short Cycling Water Heater Parts List see next Replacement PartsShort Cycling Boiler High Gas ConsumptionInternal Components See Figure Sheet Metal Components See FigureGas Train Components See Figure Heat Exchanger Components See Figure Electrical Components See Figure Sheet Metal Components Internal Components Brute Deluxe Water Heater Brute Deluxe Hydronic BoilerElectrical Components

BMT2H, BMT2V, Hydronic Boiler, Water Volume Heater specifications

Bradford-White Corporation, a leader in the water heating and hydronic heating industries, offers an impressive range of products designed to meet diverse residential and commercial needs. Among their notable innovations are the BMT2V and BMT2H series hydronic boilers and water volume heaters, which combine state-of-the-art technology with user-friendly features.

The BMT2V and BMT2H models are designed to deliver high-efficiency heating solutions for various applications. One of the key features of these boilers is their superior thermal efficiency, which reduces fuel consumption while ensuring optimal output. With a range of BTU inputs suitable for different heating needs, these boilers can provide efficient heating for residential, commercial, and industrial applications.

Both the BMT2V and BMT2H units are built with advanced combustion technology, allowing for cleaner and more efficient burning of fuel. This not only contributes to lower emissions but also ensures that the boilers operate quietly and reliably. The integrated draft inducer further enhances the efficiency of the combustion process by optimizing airflow, leading to improved overall performance.

Another standout characteristic of these models is their robust construction. Made with high-quality materials, the BMT2V and BMT2H boilers are designed to endure harsh operational conditions while providing long-lasting performance. The tanks are lined with corrosion-resistant coatings, which significantly extend the lifespan of the unit and reduce maintenance requirements.

Both models are also equipped with smart control systems that enable precise temperature regulation and easy monitoring of system performance. These controls allow users to adjust settings remotely or via integrated digital interfaces, further enhancing user convenience. Additionally, the integration of safety features, such as pressure relief valves and automated shut-off systems, ensures safe operation.

The BMT2 series also emphasizes ease of installation and maintenance. Compact designs and flexible venting options allow for versatile installation in various environments. Serviceability is streamlined through easily accessible components, ensuring that technicians can perform maintenance tasks efficiently.

In summary, Bradford-White's BMT2V and BMT2H hydronic boilers and water volume heaters embody efficiency, durability, and advanced technology. With their focus on sustainability and high performance, these models are ideal choices for anyone looking to invest in reliable heating solutions.