5.Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

7.Any improper operation of the common venting system should be corrected so that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes.

2.5 Vent Terminals for Outdoor Units

For outdoor applications, the vent and combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from falling into the Brute Deluxe.

If local codes allow, outdoor installations may use 1' of appropriately sized galvanized single wall or B- Vent and a rain cap for exhaust vent termination in the default configuration (venting out of the top). Note that some local codes may require a higher vertical vent height, extending above any perimeter fencing, etc. In installations where the appearance of the vent is objectionable, the low profile vent terminals in Table 6 may be used.

Combustion air inlets consist of appropriately sized galvanized pipe and elbows to allow the open end to face down aside the boiler. This is available as a Commercial Kit from the manufacturer.

Part numbers for the low profile terminals to cover the vent and combustion air openings are shown in Table 6.

SECTION 3.

Gas Supply and Piping

 

OUTDOOR VENT

OUTDOOR

SIZE

COMBUSTION

TERMINAL

 

AIR TERMINAL

 

 

500

20254703

D2007900

750

20254705

D2007900

1000

20254705

D2008000

 

 

 

1250

D2007700

D2008000

1500

D2007700

D2008000

1750

D2007800

D2008000

2000

D2007800

D2008200

 

 

 

3.1 Gas Supply and Piping

Gas piping should be supported by suitable hangers or floor stands, not by the appliance.

Brute Deluxe’s gas train allows the user to pipe the gas from either the right side or the left side of the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side. If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on the right side may be moved to the left.

Review the following instructions before proceeding with the installation.

1.Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Brute

SIZE

DISTANCE FROM GAS METER

OR LAST STAGE REGULATOR

AND

GAS TYPE

0-100'

100-200'

200-300'

500 natural

1½"

2"

2"

500 propane

1"

1½"

1½"

750 natural

2"

2"

2½"

750 propane

1½"

1½"

2"

1000 natural

2"

2½"

3"

1000 propane

1½"

2"

2½"

1250 natural

2½"

2½"

3"

1250 propane

2"

2"

2½"

1500 natural

2½"

3"

3"

1500 propane

2"

2½"

2½"

1750 natural

2½"

3"

3"

1750 propane

2"

2½"

2½"

2000 natural

3"

3"

3½"

2000 propane

2½"

2½"

3"

Metric Equivalent

 

 

 

 

 

SIZE

DISTANCE FROM GAS METER

OR LAST STAGE REGULATOR

AND

GAS TYPE

0-31m

31-61m

61-91m

500 natural

3.8cm

5.1cm

5.1cm

500 propane

2.5cm

3.8cm

3.8cm

750 natural

5.1cm

5.1cm

6.4cm

750 propane

3.8cm

3.8cm

5.1cm

1000 natural

5.1cm

6.4cm

7.6cm

1000 propane

3.8cm

5.1cm

6.4cm

1250 natural

6.4cm

6.4cm

7.6cm

1250 propane

5.1cm

5.1cm

6.4cm

1500 natural

6.4cm

7.6cm

7.6cm

1500 propane

5.1cm

6.4cm

6.4cm

1750 natural

6.4cm

7.6cm

7.6cm

1750 propane

5.1cm

6.4cm

6.4cm

2000 natural

7.6cm

7.6cm

8.9cm

2000 propane

6.4cm

6.4cm

7.6cm

NOTES: 1.

These figures are based on 1/2" (0.12kPa) water column

 

pressure drop.

2.

Check supply pressure and local code requirements

 

before proceeding with work.

3.

Pipe fittings must be considered when determining gas

 

pipe sizing.

Table 6. Vent Terminals for Outdoor Units.

Table 7. Gas Piping Sizes.

Image 12
Contents Brute Deluxe Table of Contents General Information IntroductionModel Identification Warranty DimensionsLocating the Appliance Clearances33¾ 16¾ 425 45¾22¾ 505 57¾16¾ 46¼ 22¾ 58¼28¾ 70¼ 34¼ 10¼ 80¾Venting and Combustion Air Combustion AirCombustion Air From Room Intake Combustion AirVenting Vent CategoriesCategory I Vent Common Venting SystemsLocating Vent & Combustion Air Terminals Side Wall Vent TerminalSide Wall Combustion Air Terminal Vertical Vent TerminalCombustion Air and Vent Through Side Wall Common Vent Test Boilers Vertical Combustion Air TerminalGas Supply and Piping Vent Terminals for Outdoor UnitsNatural Propane NaturalWater Connections Boiler 4A.1 Heating System Piping Hot Supply Connections BoilerWater Connections Water Heater 4A.2 Cold Water Make-Up Boiler4A.3 Water Flow Requirements Boiler 4A.4 Freeze Protection BoilerElectrical Connections 4B.2 Hot Water Supply Piping Water Heater4B.3 Water Flow Requirements Water Heater 4B.5 Freeze Protection Water HeaterHydronic Piping Multiple Boilers, Primary Secondary System Hydronic Piping One Boiler, Multi-Temperature System Water Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Heater Piping Multiple Heaters, Multiple Tanks Water Flow Requirements BMT2VMain Power Field WiringBrute Deluxe 1000 Wiring Diagram Brute Deluxe 500-750 Connection Diagram Brute Deluxe 1000 Connection Diagram Brute Deluxe 1250-2000 Connection Diagram External Staging Control Wiring Operating InstructionsSequence of Operation Filling the SystemOperating Temperature Control Operating the Burner and Set UpSet Up for 0 to 2500 Feet Altitude External Boiler OperationsHigh Altitude Adjustment and Set Up Maintenance System MaintenanceAppliance Maintenance Component Description Shutting Down the Brute DeluxeManual Reset High Limit Control Temperature ControlFlow Switch FilterTrouble Shooting Delayed Ignition Possible CausesResolving Lockouts Replacement Parts Short Cycling Water Heater Parts List see nextShort Cycling Boiler High Gas ConsumptionSheet Metal Components See Figure Internal Components See FigureGas Train Components See Figure Heat Exchanger Components See Figure Electrical Components See Figure Sheet Metal Components Internal Components Brute Deluxe Hydronic Boiler Brute Deluxe Water HeaterElectrical Components

BMT2H, BMT2V, Hydronic Boiler, Water Volume Heater specifications

Bradford-White Corporation, a leader in the water heating and hydronic heating industries, offers an impressive range of products designed to meet diverse residential and commercial needs. Among their notable innovations are the BMT2V and BMT2H series hydronic boilers and water volume heaters, which combine state-of-the-art technology with user-friendly features.

The BMT2V and BMT2H models are designed to deliver high-efficiency heating solutions for various applications. One of the key features of these boilers is their superior thermal efficiency, which reduces fuel consumption while ensuring optimal output. With a range of BTU inputs suitable for different heating needs, these boilers can provide efficient heating for residential, commercial, and industrial applications.

Both the BMT2V and BMT2H units are built with advanced combustion technology, allowing for cleaner and more efficient burning of fuel. This not only contributes to lower emissions but also ensures that the boilers operate quietly and reliably. The integrated draft inducer further enhances the efficiency of the combustion process by optimizing airflow, leading to improved overall performance.

Another standout characteristic of these models is their robust construction. Made with high-quality materials, the BMT2V and BMT2H boilers are designed to endure harsh operational conditions while providing long-lasting performance. The tanks are lined with corrosion-resistant coatings, which significantly extend the lifespan of the unit and reduce maintenance requirements.

Both models are also equipped with smart control systems that enable precise temperature regulation and easy monitoring of system performance. These controls allow users to adjust settings remotely or via integrated digital interfaces, further enhancing user convenience. Additionally, the integration of safety features, such as pressure relief valves and automated shut-off systems, ensures safe operation.

The BMT2 series also emphasizes ease of installation and maintenance. Compact designs and flexible venting options allow for versatile installation in various environments. Serviceability is streamlined through easily accessible components, ensuring that technicians can perform maintenance tasks efficiently.

In summary, Bradford-White's BMT2V and BMT2H hydronic boilers and water volume heaters embody efficiency, durability, and advanced technology. With their focus on sustainability and high performance, these models are ideal choices for anyone looking to invest in reliable heating solutions.