Bradford-White Corp Hydronic Boiler, Water Volume Heater Maintenance, To Restart the Brute Deluxe

Page 29

Brute Deluxe (500-2000)

Page 29

 

appliances or 9.2% for LP appliances (to be checked only at full fire). When using an O2 analyzer, the correct O2 is 6.8% for both Natural Gas and LP appliances.

Caution

Should any odor of gas be detected, or if the gas burner does not appear to be functioning in a normal manner, close main shutoff valve, do not shut off switch, and contact your heating contractor, gas company, or factory representative.

6.7 Shutting Down the Brute Deluxe

1.Switch off the main electrical disconnect switch.

2.Close all manual gas valves.

3.If freezing is anticipated, drain the Brute Deluxe and be sure to also protect building piping from freezing.

This step to be performed by a qualified service person.

6.8 To Restart the Brute Deluxe

If drained, follow Section 6.2 in this manual for proper filling and purging.

1.Switch off the main electrical disconnect switch.

2.Close all manual gas valves.

3.WAIT FIVE (5) MINUTES.

4.Set the aquastat or thermostat to its lowest setting.

5.Open all manual gas valves.

6.Reset all safety switches (pressure switch, manual reset high limit, etc.).

7.Set the temperature controller to the desired temperature setting and switch on electrical power.

8.Burner will go through a prepurge period and ignitor warm-up period, followed by ignition.

SECTION 7.

Maintenance

7.1 System Maintenance

1.Lubricate the system water-circulating pump, if required, per the instructions on the pump.

2.If a strainer is employed in a pressure reducing valve or the piping, clean it every six months.

3.Inspect the venting system for obstruction or leakage at least once a year. Periodically clean the screens in the vent terminal and combustion air terminal (when used).

4.Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.

5.If the appliance is not going to be used for extended periods in locations where freezing normally occurs, it should be isolated from the system and completely drained of all water. All systems connected to it should also be drained or

protected from freezing.

6.Low water cutoffs, if installed, should be checked every 6 months. Float type low water cutoff should be flushed periodically.

7.Inspect flue passages, and clean with brushes/ vacuums, if necessary. Sooting in flue passages indicates improper combustion. Determine the cause and correct.

8.Inspect the vent system and air intake system, and if the vent system is Category III, ensure that all joints are sealed properly. If joints need to be resealed, completely remove existing sealing material, and clean with alcohol. Apply new sealing material, and re-assemble.

7.2 Appliance Maintenance and

Component Description

Only genuine replacement parts should be used.

Caution

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dan- gerous operation. Verify proper operation after servicing.

See Figure 5 for location of gas train components. The gas and electric controls on the appliance are

engineered for long life and dependable operation, but the safety of the equipment depends on their proper functioning. It is strongly recommended that a qualified service technician inspect the basic items listed below every year.

a.Ignition controls

b.Ignitors

c.Water temperature control

d.Automatic gas valve

e.Pressure switches

f.Blowers

7.2.1 Burners

Close main manual gas valve before proceeding. Checking the burners for debris - Remove the ignitor inspection panels(s) and ignitor(s) and inspect the burners through the ignitor hole(s) using a flashlight to illuminate. If there is any indication of debris on the burners that are visible, all the burners will need to be inspected more thoroughly. Remove the screws from around the front of the air box (large panel from which the ignitor inspection panel(s) were removed), and remove the large panel. Remove the gas manifold assemblies and the burner panels. Inspect the burners. Clean burners, if necessary, by blowing compressed air from the outside of the burners into the center of the burner. A dirty burner may be an indication of improper combustion or dirty combustion air. Determine the cause, and correct. Replace the burners in the reverse order

Image 29
Contents Brute Deluxe Table of Contents Model Identification General InformationIntroduction Dimensions WarrantyLocating the Appliance Clearances45¾ 33¾ 16¾ 42522¾ 505 57¾22¾ 58¼ 16¾ 46¼28¾ 70¼ 34¼ 10¼ 80¾Combustion Air Venting and Combustion AirCombustion Air From Room Intake Combustion AirVent Categories VentingCategory I Vent Common Venting SystemsSide Wall Vent Terminal Locating Vent & Combustion Air TerminalsSide Wall Combustion Air Terminal Vertical Vent TerminalCombustion Air and Vent Through Side Wall Vertical Combustion Air Terminal Common Vent Test BoilersVent Terminals for Outdoor Units Gas Supply and PipingNatural Propane Natural4A.1 Heating System Piping Hot Supply Connections Boiler Water Connections Boiler4A.2 Cold Water Make-Up Boiler Water Connections Water Heater4A.3 Water Flow Requirements Boiler 4A.4 Freeze Protection Boiler4B.2 Hot Water Supply Piping Water Heater Electrical Connections4B.3 Water Flow Requirements Water Heater 4B.5 Freeze Protection Water HeaterHydronic Piping Multiple Boilers, Primary Secondary System Hydronic Piping One Boiler, Multi-Temperature System Water Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Flow Requirements BMT2V Water Heater Piping Multiple Heaters, Multiple TanksField Wiring Main PowerBrute Deluxe 1000 Wiring Diagram Brute Deluxe 500-750 Connection Diagram Brute Deluxe 1000 Connection Diagram Brute Deluxe 1250-2000 Connection Diagram Operating Instructions External Staging Control WiringSequence of Operation Filling the SystemOperating the Burner and Set Up Operating Temperature ControlSet Up for 0 to 2500 Feet Altitude External Boiler OperationsHigh Altitude Adjustment and Set Up System Maintenance MaintenanceAppliance Maintenance Component Description Shutting Down the Brute DeluxeTemperature Control Manual Reset High Limit ControlFlow Switch FilterResolving Lockouts Trouble ShootingDelayed Ignition Possible Causes Short Cycling Water Heater Parts List see next Replacement PartsShort Cycling Boiler High Gas ConsumptionInternal Components See Figure Sheet Metal Components See FigureGas Train Components See Figure Heat Exchanger Components See Figure Electrical Components See Figure Sheet Metal Components Internal Components Brute Deluxe Water Heater Brute Deluxe Hydronic BoilerElectrical Components

BMT2H, BMT2V, Hydronic Boiler, Water Volume Heater specifications

Bradford-White Corporation, a leader in the water heating and hydronic heating industries, offers an impressive range of products designed to meet diverse residential and commercial needs. Among their notable innovations are the BMT2V and BMT2H series hydronic boilers and water volume heaters, which combine state-of-the-art technology with user-friendly features.

The BMT2V and BMT2H models are designed to deliver high-efficiency heating solutions for various applications. One of the key features of these boilers is their superior thermal efficiency, which reduces fuel consumption while ensuring optimal output. With a range of BTU inputs suitable for different heating needs, these boilers can provide efficient heating for residential, commercial, and industrial applications.

Both the BMT2V and BMT2H units are built with advanced combustion technology, allowing for cleaner and more efficient burning of fuel. This not only contributes to lower emissions but also ensures that the boilers operate quietly and reliably. The integrated draft inducer further enhances the efficiency of the combustion process by optimizing airflow, leading to improved overall performance.

Another standout characteristic of these models is their robust construction. Made with high-quality materials, the BMT2V and BMT2H boilers are designed to endure harsh operational conditions while providing long-lasting performance. The tanks are lined with corrosion-resistant coatings, which significantly extend the lifespan of the unit and reduce maintenance requirements.

Both models are also equipped with smart control systems that enable precise temperature regulation and easy monitoring of system performance. These controls allow users to adjust settings remotely or via integrated digital interfaces, further enhancing user convenience. Additionally, the integration of safety features, such as pressure relief valves and automated shut-off systems, ensures safe operation.

The BMT2 series also emphasizes ease of installation and maintenance. Compact designs and flexible venting options allow for versatile installation in various environments. Serviceability is streamlined through easily accessible components, ensuring that technicians can perform maintenance tasks efficiently.

In summary, Bradford-White's BMT2V and BMT2H hydronic boilers and water volume heaters embody efficiency, durability, and advanced technology. With their focus on sustainability and high performance, these models are ideal choices for anyone looking to invest in reliable heating solutions.