Bradford-White Corp ULTRA HIGH EFFICIENCY GAS WATER HEATER Mechanical Exhausting of Room AIR

Page 13

MECHANICAL EXHAUSTING OF ROOM AIR

1.Where an exhaust fan is installed in the same room with this water heater and combustion air is drawn from inside the room, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE WATER HEATER’S VENTING SYSTEM, CAUSING POOR COMBUSTION THAT MAY BE HAZARDOUS TO LIFE. SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE WATER HEATER AND RISK OF FIRE OR EXPLOSION, WHICH CAN ALSO CREATE A RISK OF ASPHYXIATION. Refer to local codes and /or National Fuel Gas Code for proper air opening sizing.

UNCONFINED SPACE

1.In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion and ventilation.

2.If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion and ventilation must be obtained from outdoors. This may be accomplished by piping air directly to the water heater from outside or providing opening or ducts in the wall. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.

CONFINED SPACE

1.When drawing combustion air from inside a conventionally constructed building to a confined space, such a space must be provided with two permanent openings.

The top opening is to be located within 12 inches (30.5 cm) of the enclosure top and the bottom opening within 12 inches (30.5 cm) of the enclosure bottom.

Each opening must have a free area of at least 1 inch² (6.5 cm²) per 1000 Btu/h (.3 kw) of the total input of all appliances in the enclosure, but not less than 100 inches² (645.2 cm²).

2.If the confined space is within a building of tight construction, air for combustion and ventilation must be obtained from outdoors. This may be accomplished by piping air directly to the water heater from outside or providing opening or ducts in the wall. When directly communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, must be provided.

Each opening must have a free area of not less than 1 inch² (6.5 cm²) per 4000 Btu/h (1.2 kw) of the total input of all appliances in the enclosure.

If horizontal ducts are used, each opening must have a free area of not less than 1 inch² (6.5 cm²) per 2000 Btu/h (.6 kw) of the total input of all appliances in the enclosure.

3.If the water heater is installed as a direct vent (outside air piped directly to the water heater), then additional opening, other than the opening for the air intake, are not required. However, adequate ventilation air must be provided in all cases to prevent increased room temperature.

CHEMICAL VAPOR CORROSION

Corrosion of the flue ways and vent system will occur if air for combustion contains certain chemical vapors. Such corrosion may result in poor combustion and create a risk of asphyxiation, as well as reducing the life of the water heater. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes and process chemicals are corrosive. Products of this sort should not be stored near the water heater or outside by the air intake (if applicable).

TYPICAL INSTALLATION ILLUSTRATION

CAUTION

If the building cold water supply has a back-flow preventer, check valve, or water meter with check valve, provisions for thermal expansion of water in the hot water system must be provided.

13

Image 13
Contents What to do if YOU Smell GAS With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensions Inches Section II SpecificationsSection III General Information FeaturesTemperature and Pressure Relief Valve Condensate Elbow With Trap Section IV Installation Instructions Unpacking Minimum Clearance To Combustible Material Remove Crate LocationAIR Requirements Mechanical Exhausting of Room AIR Typical Installation IllustrationUnconfined Space Confined SpaceTypical Front Inlet Connection Typical Two Water Heater Connection Instructions for Connections Section V Water ConnectionsScalding Approximate TIME/TEMPERATURE Relationships in Scalds Approximate Time/Temperature Scald ChartSection VI Venting Approved Venting Materials Page Venting Direct Vent InstallationCanadian US Installations2 Installations1 Clearance above Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Inch 5.1 cm Inch 7.6 cm Inch 10.2 cm Power Vent InstallationTypical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Concentric Vent Terminal Installation Procedure Vertical InstallationRain Cap to Small Vent Pipe Assembly Concentric Vent Side Wall Attachment Horizontal InstallationVent Pipe Preparation Vent Diameter Dimension MIN MAXInitial Preparation Section VII GAS ConnectionsGAS Pressure Regulation GAS Meter Size Natural Gases onlySection Viii Electrical Connections Wiring Diagram and SchematicGeneral Instructions Section IX Operating InstructionsTo Fill the Water Heater Sequence of OperationLighting and SHUT-DOWN Instructions For Your Safety Read Before LightingTemperature Adjustment Water Heater Display and Control Buttons Step To Increase Setpoint TemperatureTo Decrease Setpoint Temperature Changes to C Step General Section X MaintenanceBurner Flame Check Sight Glass Location Maintenance ScheduleDraining Water Heater Flushing Water HeaterFilling Water Heater Sediment and Lime Scale RemovalDrain Valve and Tank Access Panel Anode Inspection and ReplacementRelief Valve Combustion System Inspection Vent and AIR Intake SystemSection XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature  Setpoint value Error Code Shown Water Heater Display SELECT No current error codes Max Setpoint Flashes Exiting Service Mode To Display Flame Sense Current of the Pilot Flame Sensor Display of Water TemperatureTo Display and Change Temperature Setpoint To Display and Change Temperature Format ˚F/˚C Changes to C F/C Flashes Symbol Stops Flashing Resetting Error Codes in Soft Lockout Condition How to reset the control from Lockout ConditionsTo view previous error codes Error Code HistoryError Code Index Stored Error Code For Code Index #9 Exiting SELECTService SETMode Page Procedure for Checking Thermostat Sensors EF Series Water Heater Section XII Parts ListCombustion Surround AssemblyIgnition Control Assembly Combustion Assembly pictured previousPage
Related manuals
Manual 72 pages 6.06 Kb