Bradford-White Corp EFR160T120 warranty Section XI Diagnostic and Troubleshooting Guide

Page 52

SECTION XI: DIAGNOSTIC AND TROUBLESHOOTING GUIDE

DIRECT SPARK HONEYWELL INTEGRATED CONTROL SYSTEM

SEQUENCE OF OPERATION

1.When the tank temperature drops below the temperature setpoint on the display, the control sends power to the combustion blower for a 30 second pre-purge period.

2.At the end of the pre-purge period, the control sends high voltage through the spark cable to the spark rod to spark to the burner. The gas valve also opens. If the burner lights, a microamp current is generated through the flame sense rod allowing the control to detect burner flame. The sparking then ceases and the flame is monitored by the flame sense circuit until the tank temperature reaches the thermostat setpoint and turns off the gas valve.

3.If the burner fails to light, the gas valve closes, sparking to the burner stops, and the combustion blower continues to operate for 60 seconds to purge the heat exchanger of unburned gas. The ignition trial is repeated. The control will make 3 attempts to ignite the burner. If the burner fails to light after the third attempt, the control enters “Soft Lockout”, which is an idle period for 60 minutes. There will be an error code 62 or 63 shown on the water heater display indicating that the control cycled through the maximum number of ignition retries for ignition. The control will make another 3 ignition attempts after the 1 hour waiting period.

4.If the exhaust vent terminal should become blocked or the condensate drain becomes plugged, the exhaust vent pressure switch will open and the gas valve closes. The combustion blower will continue to operate. An error code 29 is shown on the water heater display. Removing the blockage will resume normal operation.

5.The burner flame is monitored by the flame sense circuit and if the flame should extinguish, the gas valve closes and the combustion blower will operate to purge the heat exchanger before making an attempt to relight the burner. There may be 3 attempts to relight the burner before going into the Soft Lockout period explained previously.

6.The burner will continue to operate during the heating cycle until the tank temperature reaches the setpoint. The gas valve opens and the combustion blower continues to operate for 30 seconds to purge the heat exchanger of flue gases.

7.If for some reason, the tank temperature should exceed 200°F (93°C), then the control closes the gas valve and goes into a “Hard Lockout” state and will not operate until reset by a qualified service person. The display will read error code “65”, which indicates the tank high limit temperature has been exceeded. No attempt should be made to reset the control until a service person has corrected the cause of the high limit condition. Refer to the diagnostic service section at the end of this Installation and Operating Instruction Manual.

52

Image 52
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensions InchesFeatures Section III General InformationTemperature and Pressure Relief Valve Condensate Elbow With Trap Section IV Installation Instructions Unpacking Minimum Clearance To Combustible Material Remove Crate LocationAIR Requirements Typical Installation Illustration Mechanical Exhausting of Room AIRUnconfined Space Confined SpaceTypical Front Inlet Connection Typical Two Water Heater Connection Instructions for Connections Section V Water ConnectionsScalding Approximate Time/Temperature Scald Chart Approximate TIME/TEMPERATURE Relationships in ScaldsSection VI Venting Approved Venting Materials Page Direct Vent Installation VentingCanadian US Installations2 Installations1 Clearance above Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Inch 5.1 cm Inch 7.6 cm Inch 10.2 cmTypical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Vertical Installation Concentric Vent Terminal Installation ProcedureRain Cap to Small Vent Pipe Assembly Horizontal Installation Concentric Vent Side Wall AttachmentVent Diameter Dimension MIN MAX Vent Pipe PreparationSection VII GAS Connections Initial PreparationGAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsSection IX Operating Instructions General InstructionsTo Fill the Water Heater Sequence of OperationFor Your Safety Read Before Lighting Lighting and SHUT-DOWN InstructionsTemperature Adjustment Water Heater Display and Control Buttons To Increase Setpoint Temperature StepTo Decrease Setpoint Temperature Changes to C Step General Section X MaintenanceBurner Flame Check Maintenance Schedule Sight Glass Location Flushing Water Heater Draining Water Heater Filling Water Heater Sediment and Lime Scale RemovalDrain Valve and Tank Access Panel Anode Inspection and ReplacementRelief Valve Vent and AIR Intake System Combustion System InspectionSection XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature  Setpoint value Error Code Shown Water Heater Display SELECT No current error codes Max Setpoint Flashes Exiting Service Mode Display of Water Temperature To Display Flame Sense Current of the Pilot Flame SensorTo Display and Change Temperature Setpoint To Display and Change Temperature Format ˚F/˚C Changes to C F/C Flashes Symbol Stops Flashing How to reset the control from Lockout Conditions Resetting Error Codes in Soft Lockout ConditionError Code History To view previous error codesError Code Index Stored Error Code For Code Index #9 Exiting SELECTService SETMode Page Procedure for Checking Thermostat Sensors Section XII Parts List EF Series Water HeaterAssembly Combustion SurroundCombustion Assembly pictured previous Ignition Control AssemblyPage