Bradford-White Corp 500-1825 warranty III. Water Dripping Firebox

Page 18

Internet Version for Reference Only

BRADFORD WHITE

Page 18

II.HEATER IS POUNDING, KNOCKING OR EMIT- TING STEAM FROM RELIEF VALVES.

Possible Cause

What To Do

 

 

A. Low or no water flow.

A. This condition is usually

 

caused by lack of adequate

 

water flow through heater.

 

Check the following:

 

1. Is the heater wired into the

 

pump circuit so that the heater

 

cannot fire unless the pump is

 

running?

 

2. Check to see that all valves

 

in system are open to be

 

sure that water can circulate

 

through the heater and the

 

system.

 

3. If the system has automatic

 

water valves (2-way or 3-way)

 

that can cut off the water flow

 

through the heater check to

 

see that they are equipped with

 

end-switches which shut the

 

heater down when the water

 

flow through the heater is

 

reduced by 70% from full flow.

 

4. Examine pump for clogged

 

impeller.

 

 

B. Low or no system pressure.

B. Clean strainer in pressure

 

reducing valve. Look for closed

 

valve water line or a leak in the

 

system.

 

 

C. Clogged “Y” strainer.

C. Remove strainer element and

 

clean screen.

 

 

D. Debris from system piping

D. Remove header covers.

is blocking tubes.

Examine all tubes and

 

waterways. Use new gaskets

 

when reassembling. Clean

 

out tubes.

 

 

E. Scale has formed in tubes.

E. This is always caused by the

 

inflow of raw water into the

 

system. Clean tubes with tube

 

cleaning kit. Determine

 

hardness. Check water flow,

 

replace pump for modified

 

flow if necessary.

 

 

III. WATER DRIPPING

IN FIREBOX.

Possible Cause

What To Do

 

 

Tube in heat exchanger has

A tube failure is almost always

overheated and ruptured.

caused by (a) scale formation

 

in the tube or (b) inadequate

 

water flow through the heater.

 

 

IV. PRESSURE RELIEF VALVES LEAKING INTER- MITTENTLY OR STEADILY.

Possible Cause

What To Do

 

 

A.Static pressure in system

A. Calculate height of water in

exceeds setting of relief valve.

system above heater. Install

 

new valve with psi setting 25%

 

above required static system

 

working pressure. Do not

 

exceed 160 psi.

 

 

B. Expansion tank is water-

B. Drain expansion tank, then

logged (if installed).

reopen it to the system. Look

 

for leaks in expansion tank

 

or fittings. Calculate required

 

volume of expansion tank in

 

relation to system to determine

 

if tank is adequate.

 

 

V.SOOT IN FLUEWAYS OR IN TUBES, OR NOX- IOUS FUMES INDICATIVE OF BAD COMBUSTION.

Possible Cause

What To Do

 

 

A. Combustion air supply to

A. Check air supply opening.

heater room is inadequate.

Look for debris in screen or

 

louvre which covers combus-

 

tion air opening, or for material

 

blocking the opening.

 

 

B. Stack or vent is blocked or

B. Look for blocked stack and

restrictive.

excessive number of elbows in

 

stack or excessive length of

 

horizontal runs.

 

 

C.Severe down draft is causing

C.Check for (1) proper vent cap

spillage of flue products into

on stack; (2) adequate height

room.

of stack above roof;

 

(3) equipment exhausting air

 

from inside of building; and

 

(4) proper installation of draft

 

diverter.

 

 

D.Gas pressure to burners is

D.Check gas pressure with

excessive.

nanometer, and adjust with

 

heater firing at full rate.

 

 

E. Heater not fitted for the fuel

E. See nameplate for correct fuel.

supplied.

 

 

 

F. Heater installed at high

F. Installations at altitudes in

altitude without proper

excess of 2000 ft. above sea

derating.

level are subject to jurisdiction

 

of the local inspection

 

authorities.

 

 

Image 18
Contents Copper Brute Table of Contents Heater Identification General InformationIntroduction Flow RequirementsInstallation of Indoor Heaters InstallationHeater Placement Water ChemistryClearance Indoor Outdoor From Inches Venting Heater Each Opening Model Square InchesInstallation of Outdoor Heaters Gas Supply and PipingElectrical Wiring Water Piping of SystemPump Performance and Installation Water ExpansionTank Installation Water PressureTwo-Temperature System WithDrain Pump 140F Water 180F Return From Bldg With Horizontal Tank To DrainOperation Controls GeneralInitial Start-Up Hi-Limit Checkout To set the temperature and high- limit controlsTo Start Up System Start Up HeaterTo Shut Down System MaintenanceTo Turn Off Heater Indoor ModelsTroubleshooting and Analysis Service Problems Heater will not FireIII. Water Dripping Firebox This page intentionally left blank Bradford White

500-1825 specifications

Bradford-White Corporation is renowned for manufacturing high-quality water heating solutions, and the model 500-1825 is a prime example of the company's commitment to innovation and durability. This water heater is particularly well-suited for residential and commercial applications, providing users with efficient and reliable hot water.

One of the key features of the Bradford-White 500-1825 is its robust construction. Built with high-quality materials, it boasts a glass-lined tank that ensures maximum protection against corrosion. This feature extends the lifespan of the unit significantly, providing users with a long-lasting solution for their hot water needs. The tank's insulation is designed to minimize heat loss, thereby enhancing the unit's energy efficiency and lowering operating costs.

The 500-1825 model employs advanced heating technologies that facilitate rapid heating and recovery rates. It is equipped with a powerful burner system that ensures a quick restoration of hot water even during peak usage times. This feature is particularly beneficial for larger households and commercial environments where hot water demand can be substantial.

Another standout characteristic of the Bradford-White 500-1825 is its user-friendly controls. The model typically includes a smart thermostat that allows users to precisely set and maintain their desired water temperature. This functionality not only enhances comfort but also contributes to energy savings, as the system operates according to the specific needs of the user.

Safety features are paramount in the design of the 500-1825. The unit often includes multiple safety mechanisms, such as a combination temperature and pressure relief valve. This ensures that the water heater operates within safe parameters, providing peace of mind for homeowners and businesses alike.

Additionally, Bradford-White's commitment to innovation is evident in their focus on sustainability. The 500-1825 is designed to meet or exceed stringent energy efficiency standards. This means that users can enjoy the benefits of significant energy savings while reducing their environmental footprint.

In conclusion, the Bradford-White 500-1825 water heater exemplifies the company's dedication to quality, efficiency, and safety. With its durable construction, advanced heating technologies, user-friendly controls, and emphasis on sustainability, it stands out as a reliable choice for those in need of effective hot water solutions. Whether for residential use or commercial applications, the 500-1825 continues to be a trusted option among consumers.