American Water Heater 395T2506NOX Installation Considerations, Gas and Electrical Characteristics

Page 6

INSTALLATION CONSIDERATIONS

Gas AND ELECTRICAL CHARACTERISTICS

MODELS

GAS TYPE

GAS SUPPLY PRESSURE

VOLTS/HZ

AMPERES

MINIMUM

MAXIMUM

 

 

 

 

All Models

Natural

3.5" WC (0.87 kPa)

14.0" WC (3.48 kPa)

120/60

< 5

All models require a minimum gas supply pressure of 3.5” W.C. The minimum supply pressure is measured while gas is flowing (dynamic pressure). The supply pressure (dynamic) should never fall below 3.5” W.C. The supply pressure should be measured with all gas fired appliances connected to the common main firing at full capacity. If the supply pressure drops more than 1.5” W.C. as gas begins to flow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized.

The gas valve on all models has a maximum gas supply pressure limit of 14" W.C. The maximum supply pressure is measured while gas is not flowing (static pressure).

GAS PRESSURE – REQUIREMENTS

Main line gas pressure to the water heater for natural gas should be between a maximum of 14" w.c. (3.48 kPa) static pressure and a minimum of 3.5" w.c. (0.87 kPa) dynamic pressure for Natural Gas.

A supply gas pressure regulator ( service regulator ) must be installed on the gas supply line if the static pressure exceeds 14” w.c. and it should be installed no closer than 3 feet (1 meter), but no farther than 8 feet (2.4 meters) of equivalent length from the water heater’s inlet gas connection.

1.Check gas line pressure with a manometer.

2.Cycle the burner on and off several times to check its operation.

3.Check the operation of the limit and operating controls.

4.Check the vent system seams and joints and ensure that there is no discharge of flue products into the room.

5.Check the input rate.

Supply gas pressure shall be measured while the water heater is not firing (static pressure) and while the water heater is firing at full capacity (dynamic pressure). If the supply gas pressure to the water heater is not between the required minimum and maximum values given in table above, adjust the supply gas regulator as necessary. Adjust the supply gas regulator(s) per the regulator manufacturer’s instructions to achieve the required “static” and “dynamic” supply gas pressure.

MULTIPLE APPLIANCE INSTALLATIONS:

In multiple water heater installations or in installations where the installed water heater(s) share a common gas supply main with other gas fired appliances; the supply gas pressures shall be measured at each water heater with all gas fired appliances connected to a common main firing at full capacity.

In multiple water heater installations the supply gas line regulators shall be adjusted to provide gas pressure to each water heater within the minimum and maximum supply pressure requirements listed in table above with all gas fired appliances connected to a common gas main firing at full capacity.

Note: A pressure drop of more than 1.5” W. C. (0.37 kPa) when the main burner ignites is an indication of an inadequate supply of gas and can lead to ignition failure, rough starts and/or rough operation. If a drop of more than 1.5” W. C. (0.37 kPa) in supply gas pressure occurs when the main burner ignites, ensure the supply gas lines and regulator(s) are properly sized and installed.

4

Servicing should only be performed by a Qualified Service Technician

Image 6
Contents Commercial GAS Water Heaters For Models BCLPage Table of Contents Introduction Service WarningService Reminder QualificationsTools Required Multiple Appliance Installations Installation ConsiderationsGas and Electrical Characteristics GAS Pressure RequirementsAIR Supply MAKE-UP AIR Direct Communication with Outdoors Contaminated AIRClosed Water Systems Power SupplyAIR Requirements Thermal ExpansionFeatures and Components Blower and Burner Assembly Burner ReplacementPage Spark Igniter Spark Igniter, Flame Sensor, Sight GlassSpark Igniter / Flame Sensor / Control Timing Flame SensorMinimum Clearances Installation Venting Category and MaterialsVenting BCL VentingExterior Clearances Venting Tables Technical Venting Data Type B GAS VentOperation and Service Sequence of OperationSequence of Operation Flow Chart YESFor Your Safety Read Before Operating Lighting and Operating LabelTroubleshooting Complaint Cause Remedy User Qualified AgencyControls Overview Control BOX Assembly Pressure Switches All ModelsHigh Limit SWITCH/ Digital Thermostat Display Lights Digital Thermostat LED Indication Action StatusContinuity Check of High Limit ECO ConditionsThen Upper Temperature Probe Continuity Check Ohms Resistance TableOhms Lower Temperature Probe Continuity Check Wiring Terminals Description Ignition ControlFlame FAILURE- Recycle Mode Start UP/ Flame RECOVERY/ Safety LockoutStart UP Heat Mode Failure to Light LockoutInternal Control Failure Fault ConditionsTroubleshooting Guide for Ignition Control Flame Sensor Current CheckUGB Blower Speed Control SW2 SW4 Used forPIN Connections PIN Number Description Wiring Diagram American Water Heaters

381T1546NOX, 395T1996NOX, BCL, 381T1206NOX, 395T2506NOX specifications

The American Water Heater Ultra Low NOx Series represents a significant advancement in water heating technology, aiming to meet stringent environmental regulations while delivering reliable hot water for residential applications. Models such as the 104,395T1806NOX, 395T2506NOX, 381T1206NOX, and BCL are designed to prioritize efficiency, performance, and compliance with the latest emission standards.

One of the defining features of the Ultra Low NOx Series is its innovative combustion technology. These water heaters utilize a state-of-the-art gas burner that dramatically reduces nitrogen oxide (NOx) emissions, ensuring compliance with local and federal regulations. This technology not only benefits the environment but also contributes to improved indoor air quality.

Efficiency is a hallmark of the Ultra Low NOx Series, with models designed to maximize energy savings while delivering consistent hot water. They feature a user-friendly, adjustable thermostat, providing homeowners with the ability to set their desired water temperature for optimal comfort. In addition, the insulation on these water heaters is designed to minimize heat loss, ensuring that energy consumption is kept to a minimum.

The Ultra Low NOx models are equipped with an easy-to-use digital control panel that allows homeowners to monitor and adjust settings with ease. This convenience is enhanced by advanced diagnostics, which provide real-time alerts regarding system performance and maintenance needs. This proactive approach helps extend the lifespan of the unit and enhances reliability.

Safety is another crucial characteristic of the Ultra Low NOx Series. Each model is equipped with safety features such as a flame rollout switch and a fully automatic gas shut-off, which ensure that the system operates safely under various conditions.

In terms of installation and maintenance, these models are designed with user-friendly features, making the process simpler for technicians. The compact design allows for flexible installation options, even in tighter spaces.

Overall, the American Water Heater Ultra Low NOx Series, including the 104,395T1806NOX, 395T2506NOX, 381T1206NOX, and BCL models, represents an excellent choice for homeowners seeking an efficient, reliable, and environmentally responsible water heating solution. With a focus on reducing emissions and enhancing performance, these models are built to meet the demands of today's conscientious consumers.