American Water Heater BCL manual MAKE-UP AIR Direct Communication with Outdoors, Contaminated AIR

Page 8

MAKE-UP AIR DIRECT COMMUNICATION WITH OUTDOORS:

A fresh supply of make-up air for combustion can be supplied to the water heater through make-up air ducts, which directly communicate with the outdoors. (Not Direct Vent.)

Two openings are required: one within 12 inches (30 cm) of the top of the enclosure and one within 12 inches (30 cm) of the bottom of the enclosure. Each opening must have a free area of not less than 1 square inch per 4,000 BTU/Hr of the total input of all appliances within the enclosure. The lower opening primarily provides combustion air. The upper opening provides vent dilution air and acts as a relief opening for flue gases should the vent become obstructed or a downdraft condition occur.

Additionally, when the water heater is installed in a confined space and communicating with the outdoor air, one permanent opening, beginning within 12 inches (30 cm) of the top of the enclosure, must be permitted where the equipment has clearances of at least 1 inch (2.5 cm) from the sides and back, and 6 inches (16 cm) from the front of the appliance. The opening must directly communicate with the outdoors and must communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and must have a minimum free area of a) 1 square inch per 3,000 BTU/Hr (7cm2 per kW) of the total input of all equipment located in the enclosure and b) not less than the sum of the areas of all vent connectors in the confined space.

CONTAMINATED AIR:

Corrosion of the flue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation.

Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as hot surface igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage.

Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions).

6

Servicing should only be performed by a Qualified Service Technician

Image 8
Contents Commercial GAS Water Heaters For Models BCLPage Table of Contents Service Warning Service ReminderIntroduction QualificationsTools Required Installation Considerations Gas and Electrical CharacteristicsMultiple Appliance Installations GAS Pressure RequirementsAIR Supply MAKE-UP AIR Direct Communication with Outdoors Contaminated AIRPower Supply AIR RequirementsClosed Water Systems Thermal ExpansionFeatures and Components Blower and Burner Assembly Burner ReplacementPage Spark Igniter, Flame Sensor, Sight Glass Spark Igniter / Flame Sensor / Control TimingSpark Igniter Flame SensorInstallation Venting Category and Materials VentingMinimum Clearances BCL VentingExterior Clearances Venting Tables Technical Venting Data Type B GAS VentOperation and Service Sequence of OperationSequence of Operation Flow Chart YESFor Your Safety Read Before Operating Lighting and Operating LabelTroubleshooting Complaint Cause Remedy User Qualified AgencyControls Overview Control BOX Assembly Pressure Switches All ModelsHigh Limit SWITCH/ Digital Thermostat Display Lights Digital Thermostat LED Indication Action StatusThen Continuity Check of High Limit ECOConditions Ohms Upper Temperature Probe Continuity CheckOhms Resistance Table Lower Temperature Probe Continuity Check Wiring Terminals Description Ignition ControlStart UP/ Flame RECOVERY/ Safety Lockout Start UP Heat ModeFlame FAILURE- Recycle Mode Failure to Light LockoutFault Conditions Troubleshooting Guide for Ignition ControlInternal Control Failure Flame Sensor Current CheckPIN Connections PIN Number Description UGB Blower Speed ControlSW2 SW4 Used for Wiring Diagram American Water Heaters

381T1546NOX, 395T1996NOX, BCL, 381T1206NOX, 395T2506NOX specifications

The American Water Heater Ultra Low NOx Series represents a significant advancement in water heating technology, aiming to meet stringent environmental regulations while delivering reliable hot water for residential applications. Models such as the 104,395T1806NOX, 395T2506NOX, 381T1206NOX, and BCL are designed to prioritize efficiency, performance, and compliance with the latest emission standards.

One of the defining features of the Ultra Low NOx Series is its innovative combustion technology. These water heaters utilize a state-of-the-art gas burner that dramatically reduces nitrogen oxide (NOx) emissions, ensuring compliance with local and federal regulations. This technology not only benefits the environment but also contributes to improved indoor air quality.

Efficiency is a hallmark of the Ultra Low NOx Series, with models designed to maximize energy savings while delivering consistent hot water. They feature a user-friendly, adjustable thermostat, providing homeowners with the ability to set their desired water temperature for optimal comfort. In addition, the insulation on these water heaters is designed to minimize heat loss, ensuring that energy consumption is kept to a minimum.

The Ultra Low NOx models are equipped with an easy-to-use digital control panel that allows homeowners to monitor and adjust settings with ease. This convenience is enhanced by advanced diagnostics, which provide real-time alerts regarding system performance and maintenance needs. This proactive approach helps extend the lifespan of the unit and enhances reliability.

Safety is another crucial characteristic of the Ultra Low NOx Series. Each model is equipped with safety features such as a flame rollout switch and a fully automatic gas shut-off, which ensure that the system operates safely under various conditions.

In terms of installation and maintenance, these models are designed with user-friendly features, making the process simpler for technicians. The compact design allows for flexible installation options, even in tighter spaces.

Overall, the American Water Heater Ultra Low NOx Series, including the 104,395T1806NOX, 395T2506NOX, 381T1206NOX, and BCL models, represents an excellent choice for homeowners seeking an efficient, reliable, and environmentally responsible water heating solution. With a focus on reducing emissions and enhancing performance, these models are built to meet the demands of today's conscientious consumers.