American Water Heater American Water Heaters Residential Gas Water Heater, VG6250T76NV Series 100

Page 13

Figure 7. The water heater should have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance. The opening should directly communicate with the outdoors or should communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and should have a minimum free area of the following:

1.1 square inch per 3000 Btu/hr (700 mm2 per kW) of the total input rating of all appliances located in the enclosure, and

2.Not less than the sum of the areas of all vent connectors in space.

OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS

FIGURE 8.

Confined space should be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of top and one commencing within 12 inches (300 mm) of bottom of enclosure. Horizontal ducts should communicate directly with outdoors. See Figure 8.

Each duct opening should have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.

When ducts are used, they should be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts should be not less than 3 inches.

OUTDOOR AIR THROUGH TWO VERTICAL DUCTS

The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only.

Do not refer to these illustrations for the purpose of vent installation. See Installation of Vent System on pages 18-27 for complete venting installation instructions.

FIGURE 9.

The confined space should be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the

enclosure. The vertical ducts should communicate directly with the outdoors. See Figure 9.

Each duct opening should have a minimum free area of 1 square inch

per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of

all appliances installed in the enclosure.

When ducts are used, they should be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts should be not less than 3 inches.

AIR FROM OTHER INDOOR SPACES

FIGURE 9A.

The confined space should be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. See Figure 9A.

Each opening should communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space.

Each opening should have a minimum free area of 1 square inch per

1,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all

appliances installed in the enclosure. Each opening should not be

less than 100 square inches (645 cm2).

13

Image 13
Contents Printed Whenever maintenance adjustment or service is required319339-002 Approvals Safe INSTALLATION, USE and ServiceImportant Definitions General Safety Information General Safety Information Introduction Table of ContentsApproved Carbon Monoxide Detectors Installation of Carbon Monoxide DetectorsSignage ExemptionsReplacement Parts and Deliming Products Typical InstallationElbow Access Door Condensate Hose and Drain PAN Less Severe Burns 2nd & 3rd Degree Mixing Valves Facts to Consider About the Location Locating the NEW Water HeaterAir REQUIREMENTs Insulation BlanketsConfined Space Unconfined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Vertical Ducts Outdoor AIR Through TWO Horizontal DuctsAIR from Other Indoor Spaces Chemical Vapor Corrosion Installing the NEW Water HeaterWater Piping Space Heating and Potable Water SystemThermal Expansion Temperature-Pressure Relief ValveValve and Pipe Insulation Gas Piping High Altitude InstallationFilling the Water Heater Sediment TrapsVenting Vent Pipe AssemblyVent Pipe Termination Termination Clearances Sidewall Power VentCondensate Planning the Vent SystemBreathing Hazard Carbon Monoxide Gas Installation of Vent System Blower Assembly InstallationVent Terminal INSTALLATION, Sidewall Power Vent Wiring Schematic Figure Sequence of INSTALLATIONS, FigureVent Termination Figure Installation of Vertical Vent System Installation of Vent SYSTEM, SidewallVertical VAA Installations Recommended Vent Attenuation Assembly InstallationInch vent Vertical VAA Installations Recommended BRUSH* Size for Primer Cement Applications Vent Pipe PreparationStep E Step BStep F Step GPage GAS Control Valve Front View Temperature RegulationFor Your Information Periodic MaintenanceStart UP Conditions Operational ConditionsBurner Operation and Inspection Burner CleaningHousekeeping Anode ROD InspectionDraining and Flushing Temperature-Pressure Relief Valve TestTo Drain the Water Heater Storage Tank To Flush the Water Heater Storage TankLeakage Checkpoints ServiceRepair Parts List LED Status Problem Solution Troubleshooting GuidelinesLED Status Problem Solution Troubleshooting Guidelines Page Fill in Warranty and Keep for Future Reference Limited Warranty
Related manuals
Manual 40 pages 29.25 Kb