American Water Heater BCL3 85T275 6NOX Draining and Flushing, Deliming Solvents, Example

Page 29

Draining and Flushing

Burn harzard.

Hot water discharge.

Keep hands clear of drain valve discharge.

It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures.

To Drain the Water Heater Storage Tank:

1.Turn off the electrical supply to the water heater.

2.Turn off the gas supply at the Main Gas Shutoff Valve if the water heater is going to be shut down for an extended period.

3.Ensure the cold water inlet valve is open.

4.Open a nearby hot water faucet and let the water run until the water is no longer hot.

5.Close the cold water inlet valve to the water heater.

6.Connect a hose to the water heater drain valve and terminate it to an adequate drain.

7.Open the water heater drain valve and allow all the water to drain from the storage tank.

8.Close the water heater drain valve when all water in the storage tank has drained.

9.Close the hot water faucet opened in Step 4.

10.If the water heater is going to be shut down for an extended period, the drain valve should be left open.

To Flush the Water Heater Storage Tank:

1.Turn off the electrical supply to the water heater.

2.Ensure the cold water inlet valve is open.

3.Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet.

4.Connect a hose to the drain valve and terminate it to an adequate drain.

5.Ensure the drain hose is secured before and during the entire flushing procedure. Flushing is performed with system water pressure applied to the water heater.

6.Open the water heater drain valve to flush the storage tank.

7.Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean.

8.Close the water heater drain valve when flushing is completed.

9.Remove the drain hose.

10.Fill the water heater - see Filling The Water Heater in this manual.

11.Turn on the electrical supply to place the water heater back in operation.

12.Turn on the gas supply to the water heater at the Main Gas Shutoff Valve.

13.Allow the water heater to complete several heating cycles to ensure it is operating properly.

Periodic Removal of Lime Deposits from Tank Type Commercial Water Heaters

The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils.

Lime accumulation may affect the life of equipment, the efficiency of the heater, and fuel consumption characteristics. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.

The time between cleaning will vary from weeks to years depending upon water conditions and usage.

The depth of lime buildup should be measured periodically. Heaters equipped with cleanouts will have about 2" of lime buildup when the level of lime has reached the bottom of the cleanout opening. A schedule for deliming should then be set up based on the amount of time it would take for a 1" buildup of lime. It is recommended that the water heater initially be inspected after 6 months.

Example 1:

Initial inspection after 6 months shows 1/2" of lime accumulation. Therefore, the heater should be delimed once a year.

Example 2:

Initial inspection after 6 months shows 2" of lime accumulation. Therefore, the heater should be delimed every 3 months.

Figure 26.

Deliming Solvents

UN•LIME is recommended for deliming. UN•LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products.

UN•LIME may be obtained from your dealer, distributor or water heater manufacturer. Order Part Number 9005416105, 1 gallon, packed 4 gallons per case or Part Number 9005417105, 5 gallon container.

29

Image 29
Contents Commercial gas water heaters Table Of Contents Approvals Safe Installation, Use and ServiceFire and Explosion Hazard General Safety InformationHydrogen Gas Flammable PrecautionsGrounding Instructions Introduction Qualified Installer or Service AgencyAbbreviations Used QualificationsEliminator self-cleaning system Features and ComponentsBlower/Burner Assembly High Limit Switch ControlsRough In Dimensions Installation considerationsRough-In-Dimensions Recovery Capacities, based on 82% efficiencyClearances Locating the Water HeaterInsulation Blanket NSF Leg KitHard Water Circulation PumpsBreathing Hazard Carbon Monoxide Gas High Altitude InstallationsInstallation Requirements Dishwashing Machines Temperature-Pressure Relief ValveClosed Water Systems Thermal ExpansionValve Discharge Pipe Requirements Combustible Material StorageContaminated Air Unconfined Space Air RequirementsConfined Space VentingFresh Air Openings for Confined Spaces Multiple Heater Manifold Outdoor Air Through One OpeningOutdoor Air Through Two Openings Outdoor Air Through Two Horizontal DuctsAir From Other Indoor Spaces Outdoor Air Through Two Vertical DuctsMultiple Gas Fired Tank-Type Heaters Type B GAS VentModel ABCL3 85T275 6NOX Valve Discharge Pipe Water heater installationWater Line Connections Tube Inlet Installation Installation Diagrams Top Inlet/Outlet UsageHeater Wiring Gas Piping Gas Line Leak TestingPurging Gas Meter Size Natural Gases OnlyInitial Start Up Start upPrior to Start Up Multiple Appliance Installations Water Temperature AdjustmentChecking Venting Checking the InputLighting & Operating Label Sequence of OperationYES Sequence of Operation Flow ChartTemperature-Pressure Relief Valve Test MaintenanceVenting System Intake Air ScreenDeliming Solvents Draining and FlushingTo Drain the Water Heater Storage Tank To Flush the Water Heater Storage TankDeliming Using Flo-Jug Method Tank Cleanout ProcedureElectrical Servicing System DiagnosticsIgnition Control System For Your Information High Water Temperature Shut OFF SystemStart Up Conditions Operational ConditionsComplaint Cause Remedy User TroubleshootingQualified Service Agency Water Piping DiagramsTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Model Dimension a Page Claim Procedure Service and Repair ExpensesALL Other Parts Conditions and Exceptions

BCL3 95T199 6NOX, BCL3 85T390 6NOX, BCL3 85T275 6NOX specifications

American Water Heater Company has been a leader in the production of high-quality water heaters for residential and commercial use. Among their acclaimed collection are three notable models: the BCL3 85T275 6NOX, BCL3 85T390 6NOX, and BCL3 95T199 6NOX. Each of these models is meticulously designed, providing efficient heating solutions while prioritizing safety and environmental responsibility.

The BCL3 85T275 6NOX is an advanced model that offers a remarkable 275,000 BTU output, making it suitable for a variety of applications, from single-family homes to larger commercial settings. This unit features a powerful water heating capacity and is equipped with a robust heat exchanger that maximizes thermal efficiency. One of its key technological innovations is the low nitrogen oxide (NOX) emissions system, which significantly reduces harmful emissions, thereby complying with stringent environmental standards.

Similarly, the BCL3 85T390 6NOX enhances performance with a higher BTU output of 390,000. This capacity allows it to effectively serve larger facilities with higher demand for hot water. The technology behind this model includes an automatic flue damper that optimizes energy use by adjusting the airflow, resulting in improved combustion efficiency. Additionally, its durable construction ensures long service life, catering to the needs of both residential users and commercial operations.

The BCL3 95T199 6NOX, with its 199,000 BTU capacity, combines efficiency with versatility. This unit is designed for a wide range of water heating needs, providing an excellent option for both medium-sized homes and smaller commercial setups. Its unique design incorporates advanced insulation materials that help retain heat longer, thereby enhancing overall efficiency. Like its counterparts, this model is equipped with advanced NOX reduction technology, which makes it an environmentally friendly choice.

All three models share a common theme of reliability and efficiency. Their advanced control systems enable precise temperature management, allowing users to set their desired hot water temperatures with ease. Furthermore, each unit is designed with safety features such as a high-temperature limit switch and electronic ignition, ensuring safe operation.

In conclusion, the American Water Heater BCL3 series — featuring the BCL3 85T275 6NOX, BCL3 85T390 6NOX, and BCL3 95T199 6NOX — showcases the company's commitment to innovation, quality, and environmental stewardship. These models not only meet the demanding needs of consumers but also contribute to a more sustainable future with their low emissions and efficient systems. Whether for residential or commercial use, they are designed to deliver reliable performance year after year.