American Water Heater Commercial Ultra Low NOx Gas water Heater warranty Relief Valve, GAS Piping

Page 7

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown in Figure 3.

Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.

COMBINATION WATER (POTABLE) HEATING

AND SPACE HEATING

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to installation diagram on page 6 of this manual for suggested piping arrangements.

5.These water heaters cannot be used in space heating applications only.

CAUTION

A closed system will exist if a check valve (without bypass), pressure reducing valve (without bypass), or a water meter (without bypass) is installed in the cold water line between the water heater and street main (or well).

Excessive pressure may develop in such closed systems, causing premature tank failure or intermittent relief valve operation. This is not a warranty failure. An expansion tank or a similar device may be required in the inlet supply line between the appliance and the meter or valve to compensate for the thermal expansion of the water.

SYSTEM CONNECTIONS

The system installation must conform to these instructions and to the local code authority having jurisdiction. Good practice requires that all heavy piping be supported.

RELIEF VALVE

This water heater is equipped with a combination temperature-pressure relief valve that complies with the standard for relief valves for hot water supply systems Z21.22-CSA 4.4. FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED OR PLUGGED.

ASME ratings cover pressure relief capacities. ANSI ratings cover release rate with temperature actuation.

In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved combination temperature (ANSI) and pressure (ASME) relief valve(s). This valve shall comply with the standard for relief valves for hot water supply systems Z21.22-CSA 4.4.

WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.

Your local code authority may have other specific relief valve requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.

See SERVICE INFORMATION section for procedure and precautions.

The type, size and location of the relief valves must be in accordance with local codes. The location of the relief valve is shown in Figure 1. The heater has a factory installed high temperature limit switch.

GAS PIPING

Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.

Size the main gas line in accordance with Table 4. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the current edition of the National Fuel Gas Code. For Canadian installations consult Canadian Installation Code CAN/CSA-B149.1.

WARNING

The minimum gas supply pressure for input adjustment is 6.0" kPa W.C. for natural gas (11.0" kPa W.C. for propane).

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 14" kPa WATER COLUMN SUPPLY PRESSURE. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE CONTROL WHICH COULD RESULT IN FIRE OF EXPLOSION. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the control must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system not the heater. Vent blockage may occur during ice storms.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 5). THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE. For Canadian installations consult Canadian Installation Code CAN/ CSA-B149.1.

To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

7

Image 7
Contents Notify Owner to Keep for Future Reference Place These Instructions Adjacent to HeaterTOP View DimensionsRecovery Ratings Input Rate GAS and Electrical CharacteristicsTable of Contents Installation Instructions Unconfined Space ClearancesHard Water AIR RequirementsVent Connection VentingSystem Connections Combination Water Potable Heating Space HeatingRelief Valve GAS PipingWiring Diagram and Schematic Heater WiringGAS Meter Size Natural Gases only PurgingGAS Pressure Regulator To Operate the HeaterWhat to do if YOU Smell GAS For Your Safety Read Before OperatingChecking Venting Temperature RegulationChecking GAS Input Service InformationHigh Temperature Limit Switch ECO Main Burner and IgniterPreventive Maintenance FLO-JUG Method of Deliming Tank Cleanout ProcedureCondensation ChecklistAnode Water Heating Cycle TroubleshootingService and Repair GAS and Electric Power are ON,OFF/ON Switch is onLeaking T&P Valve Not Enough or no HOT WaterCondensation Water LeaksTrouble Shooting Troubleshooting GuidelinesD E F Black resistor wire between pins 3 & 4 with an ohm meterUnplug the ignitor assembly plug from the control. Check Page Page Conditions and Exceptions Service and Repair ExpensesClaim Procedure ALL Other Parts

BBCN375T754NV, Commercial Ultra Low NOx Gas water Heater specifications

The American Water Heater BBCN375T754NV is a standout in the realm of commercial water heating solutions, specifically designed to meet the demands of businesses requiring high efficiency and reliability. This ultra-low NOx gas water heater is engineered to reduce nitrogen oxide emissions, adhering to strict environmental regulations, which makes it an ideal choice for those conscious of their ecological footprint.

One of the main features of the BBCN375T754NV is its impressive capacity of 75 gallons, making it suitable for various commercial applications, including restaurants, hotels, and manufacturing facilities. This model is built to provide a consistent and rapid supply of hot water, ensuring that users have access to the hot water they need without interruption.

The heater is equipped with a powerful gas burner system, providing an input of 375,000 BTUs per hour, which guarantees robust performance even during peak demand times. This high input rate allows for quick recovery and reduces waiting times for hot water delivery, an essential factor in maintaining operational efficiency.

In terms of technology, the BBCN375T754NV incorporates advanced combustion management systems that optimize gas consumption and efficiency. This ensures that the heater operates at maximum capacity while minimizing energy waste. Additionally, the unit features a robust insulation system designed to reduce heat loss, further contributing to its energy-efficient performance.

Another important characteristic of this water heater is its durable construction. Made from high-quality materials, including a glass-lined tank for corrosion resistance, the BBCN375T754NV is built to withstand the rigors of a commercial environment. The unit comes with a built-in anode rod to enhance longevity and minimize maintenance needs.

Furthermore, the heater includes an easy-to-navigate digital display that simplifies temperature adjustments and monitoring. This feature enables operators to easily manage the system settings, ensuring optimal performance and safety.

To sum up, the American Water Heater BBCN375T754NV is designed for those who need an efficient, reliable, and environmentally friendly solution to their commercial hot water requirements. With its high capacity, advanced technologies, and durable design, it stands as a robust option for businesses looking to enhance their water heating systems while adhering to environmental standards.