Hobart HSF3 manual Electrical Data, Plumbing Connections, Drain Connections

Page 5

ELECTRICAL DATA

 

 

 

 

Rated Amps

 

Fuse Size or

 

Total

 

Kilowatts Per Phase

3 Phase

 

1 Phase

Circuit Size

90°C Copper

Volts / Hz / Ph

 

Circuit Breaker Size *

KW

 

Amps Per Line Wire

Amps

(Amps)

Wire Size

 

 

(Amps)

 

L1 - L2 L2 - L3 L1 - L3 L1

L2

L3

 

 

 

 

 

 

 

 

 

 

 

7.5

208 / 60 / 1

 

 

 

 

 

 

36

50

50

8

7.5

240 / 60 / 1

 

 

 

 

 

 

31

45

45

8

7.5

208 / 60 / 3

2.5

2.5

2.5

21

21

21

 

30

30

10

7.5

240 / 60 / 3

2.5

2.5

2.5

18

18

18

 

25

25

14

7.5

480 / 60 / 3

2.5

2.5

2.5

9

9

9

 

15

15

16

10

208 / 60 / 1

 

 

 

 

 

 

48

60

60

8

10

240 / 60 / 1

 

 

 

 

 

 

42

60

60

8

10

208 / 60 / 3

3.3

3.3

3.3

28

28

28

 

35

35

10

 

 

 

 

 

 

 

 

 

 

 

 

10

240 / 60 / 3

3.3

3.3

3.3

24

24

24

 

35

35

10

 

 

 

 

 

 

 

 

 

 

 

 

10

480 / 60 / 3

3.3

3.3

3.3

12

12

12

 

15

15

16

 

 

 

 

 

 

 

 

 

 

 

 

15

208 / 60 / 1

 

 

 

 

 

 

72

90

90

6

15

240 / 60 / 1

 

 

 

 

 

 

63

90

90

6

15

208 / 60 / 3

5

5

5

42

42

42

 

60

60

8

15

240 / 60 / 3

5

5

5

36

36

36

 

50

50

8

15

480 / 60 / 3

5

5

5

18

18

18

 

25

25

14

 

 

 

 

 

 

 

 

 

 

* Dual Element Time-Delay Fuse or

 

 

 

 

 

 

 

 

 

 

 

Inverse Time Circuit Breaker

 

Circuit Size (Minimum) & Fuse/Circuit Breaker Size (Maximum) compiled in accordance with the National Electrical Code ANSI/NFPA 70 (latest edition).

PLUMBING CONNECTIONS

WARNING: PLUMBING CONNECTIONS MUST COMPLY WITH APPLICABLE SANITARY, SAFETY AND PLUMBING CODES.

1.Connect the water supply line to the two 3/8" copper tube inlets as identified at the rear of the steamer.

2.Install the line strainer provided in the steam generator fill line.

Provide a manual shutoff valve convenient to the steamer for descaling.

DRAIN VENT

BY CUSTOMER

DRAIN CONNECTIONS

The drain connection (Fig. 2) must be:

1" IPS (iron pipe size) down, preferably with one elbow only.

Maximum length of 6 feet (1.8 m).

Piped to an open gap type drain.

CAUTION: In order to avoid any back pressure in the steamer, do not connect solidly to any drain connection.

20(500) MIN .

2 (500)

PL-50880

1 1/4 NPT TO OPEN

GAP DRAIN

BY CUSTOMER

Fig. 2

– 5 –

Image 5
Contents UCT Table of Contents Location Leveling Feet Standard or 4 10 CM Adjustable Legs OptionalUnpacking Anchoring Steamer Without Legs LevelingStacking KIT Electrical ConnectionsDrain Connections Electrical DataPlumbing Connections Vent Hood Water QualityTesting Procedure Preheat ControlsOFF Shutdown CookExtended Shutdown Cooking HintsFrozen Food Items CleaningAcceptable Pan Sizes Draining Steam GeneratorWeekly, or more often if necessary Cooking in Solid Pans Cooking GuidelinesCooking in Perforated Pans Cooking in Perforated Pans Contd Removal of Lime Scale Deposits Deliming and Cleaning SteamerCold Water Condenser Service