Mitsubishi Electronics PUGH18AYB, PUGH42AYB Specifications, Pcgh Series Heat Pump Systems

Page 3

036-21544-001 Rev. B (1103)

2 SPECIFICATIONS

PCGH SERIES - HEAT PUMP SYSTEMS

SYSTEM

INDOOR

OUTDOOR

BTU/H

BTUH/H HEAT

SEER

EER*

HSPF

COP*

COOL*

(AUX)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCGH24GK

PCH24GK

PUGH24AYB

25000

24200

10.00

9.00

7.35

3.10

 

 

 

 

 

 

 

 

 

PCGH30GK

PCH30GK

PUGH30AYB

30200

31000

10.00

9.35

7.6

3.33

 

 

 

 

 

 

 

 

 

PCGH36GK

PCH36GK

PUGH36AYB

35800

36200

10.50

9.65

7.4

3.24

 

 

 

 

 

 

 

 

 

PCGH42GK

PCH42GK

PUGH42AYB

40500

45000

11.50

10.25

7.8

3.35

 

 

 

 

 

 

 

 

 

*Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.

PKGH SERIES - HEAT PUMP SYSTEMS

SYSTEM

INDOOR

OUTDOOR

BTU/H

BTUH/H HEAT

SEER

EER*

HSPF

COP*

COOL*

(AUX)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKGH18FK3

PKH18FK3

PUGH18AYB

17900

17400

11.50

10.00

7.5

3.38

PKGH24FK3

PKH24FK3

PUGH24AYB

23400

23000

10.50

9.20

7.45

3.10

PKGH30FK3

PKH30FK3

PUGH30AYB

29600

30000

11.00

9.85

7.8

3.44

PKGH36FK3

PKH36FK3

PUGH36AYB

34200

35000

10.70

9.85

7.4

3.22

*Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.

PLGH SERIES - HEAT PUMP SYSTEMS

SYSTEM

INDOOR

OUTDOOR

BTU/H

BTUH/H HEAT

SEER

EER*

HSPF

COP*

COOL*

(AUX)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLGH18AK

PLH18AK3

PUGH18AYB

19200

19200

10.75

10.00

7.6

3.64

 

 

 

 

 

 

 

 

 

PLGH24AK

PLH24AK3

PUGH24AYB

24400

24200

10.00

8.90

7.25

3.04

 

 

 

 

 

 

 

 

 

PLGH30AK

PLH30AK3

PUGH30AYB

27800

30200

10.00

8.85

7.4

3.18

 

 

 

 

 

 

 

 

 

PLGH36AK

PLH36AK3

PUGH36AYB

35200

36400

10.00

9.45

7.35

3.22

 

 

 

 

 

 

 

 

 

PLGH42AK

PLH42AK3

PUGH42AYB

40000

45000

11.00

9.85

7.5

3.22

 

 

 

 

 

 

 

 

 

*Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.

ELECTRICAL SPECIFICATIONS - HEAT PUMP UNITS

MODEL

 

PUGH18AYB

PUGH24AYB

PUGH30AYB

PUGH36AYB

PUGH42AYB

Compressor

Locked Rotor Amps1

48

68

82

86

109

 

 

 

 

 

 

Full Load Amps1

9.0

12.8

14.7

16.6

18.3

 

 

 

 

 

 

 

 

Outdoor Fan

Full Load Amps1

0.5

0.5

1.4

1.3

1.3

 

 

 

 

 

 

 

Unit Total

Full Load Amps1

9.5

13.3

16.1

17.9

19.6

 

 

 

 

 

 

 

Max Fuse Size (Amps)

 

20

25

30

35

40

 

 

 

 

 

 

 

Min. Circuit Ampacity

 

11.8

12.8

19.8

22.1

24.2

 

 

 

 

 

 

 

Mitsubishi Electronics 2003

3

Image 3
Contents Pugh Outdoor Unit Applies to Voltage Phase SuffixCapacity Correction Factors for Description and FeaturesPkgh Series Heat Pump Systems SpecificationsElectrical Specifications Heat Pump Units Pcgh Series Heat Pump SystemsStandard Operating Data PCH Indoor Units with Pugh Outdoor UnitsModels PCH24GK PCH30GK PCH36GK PCH42GK Models PKH18FK PKH24FK PKH30FK PKH36FK PKH Indoor Units with Pugh Outdoor UnitsModels PLH18GK PLH24GK PLH30GK PLH36GK PLH42GK PLH Indoor Units with Pugh Outdoor UnitsPCH24GK+PUGH24 Indoor Air = 810 CFM Performance Data Operating Pressures CoolingPCH30GK+PUGH30 Indoor Air = 1130 CFM PCH36GK+PUGH36 Indoor Air = 1130 CFM PCH42GK+PUGH42 Indoor Air = 1130 CFM PKH18FK+PUGH18 Indoor Air = 640 CFM PKH24FK+PUGH24 Indoor Air = 640 CFM PKH30FK+PUGH30 Indoor Air = 910 CFM PKH36FK+PUGH36 Indoor Air = 885 CFM PLH18AK+PUGH18 Indoor Air = 670 CFM PLH24AK+PUGH24 Indoor Air = 950 CFM PLH30AK+PUGH30 Indoor Air = 1020 CFM PLH36AK+PUGH36 Indoor Air = 1020 CFM PLH42AK+PUGH42 Indoor Air = 1100 CFM PKH24FK/PUGH24 Performance Data Operating Pressures HeatingPKH18FK/PUGH18 PKH30FK/PUGH30PLH36AK/PUGH36 PLH18AK/PUGH18PLH24AK/PUGH24 PLH30AK/PUGH30PCH42GK/PUGH42 PCH24GK/PUGH24PCH30GK/PUGH30 PCH36GK/PUGH36Typical Installation Dimensions and ClearancesOperating Pressures / Superheat System Charge Measurement MethodSuperheat Charging Method Operating Pressures / Superheat Temperature and PressureOperating Range Operating Temperature RangeModel Liquid OD Vapor OD CHARGE, OZ/FT Factory Charge ADD Charge ARI Rating Point ModelCHARGE, OZ Model Refrigerant Piping Length ONE WAY Capacity Correction Factors for Various Pipe LengthsCOOLING/HEATING Operation Microprocessor ControlLED Flashes Indication of Condition Electrical Refrigerant System Service PortsParts Breakdown Description PUGH018AYB PUGH024AYB PUGH030AYB Models 18, 24,Description PUGH036AYB PUGH042AYB Models 36Mitsubishi Electronics 036-21544-001 Specifications are subject to change without notice