Mitsubishi Electronics PUY-A36NHA2 NET address setting, Refrigerant address setting, NET wiring

Page 24

M-NET wiring

(1)

Use 2-core x 1.25mm2 [AWG16] shield wire for electric wires.

M-NET

 

 

 

 

 

(Excluding the case connecting to system controller.)

terminal

 

Ground

 

block

 

(2)

Connect the wire to the M-NET terminal block. Connect one core of the

 

wire

 

 

 

 

 

 

transmission wire (non-polar) to A terminal and the other to B. Peel the

 

 

 

 

A B

S

 

shield wire, twist the shield part to a string and connect it to S terminal.

 

Transmission

Shield

(3)

In the system which several outdoor units are being connected, the terminal

wire

part

 

 

(A, B, S) on M-NET terminal block should be individually wired to the other

outdoor unit’s terminal, i.e. A to A, B to B and S to S. In this case, choose one of those outdoor units and drive a screw to fix an ground wire on the plate as shown on the right figure.

8-4-1. M-NET address setting

In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI series, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.

Address number can be set by using rotary switches (SW11 for ones digit and SW12 for tens digit), which is located on the M-NET board of outdoor unit.

(Initial setting: all addresses are set to “0”.)

8-4-2. Refrigerant address setting

<Setting example> M-NET Address No.

 

SW11

Switching

ones

digit

setting

SW12

 

tens

 

digit

1

2

34

01

5

9

7

6

8

 

2

34

01

5

9

7

6

8

 

2

2

34

01

5

9

7

6

8

 

2

34

01

5

9

7

6

8

 

~

50

2

34

01

5

9

7

6

8

 

2

34

01

5

9

7

6

8

 

In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group set- ting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all switches are OFF. (All refrigerant addresses are “00”.)]

Refrigerant address

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

1

2

3

4

5

6

 

 

 

0

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

7

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

1

2

3

4

5

6

 

 

 

8

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

10

 

 

 

 

 

 

11

 

 

 

 

 

 

12

 

 

 

 

 

 

13

 

 

 

 

 

 

14

 

 

 

 

 

 

15

 

 

8-4-3. Regulations in address settings

In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above sec- tion. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.

Group A

Group B

Group C

System controller

Power supply unit for transmission wire

Refrigerant address 00

M-NET address 01

A-control remote controller

Refrigerant address 00

M-NET address 02

A-control remote controller

Refrigerant address 01

M-NET address 03

TB5

Refrigerant address 00

M-NET address 04

A-control remote controller

wRefrigerant addresses can be overlapped if they are in the different group.

System controller

Power supply unit for transmission wire

Group A

Refrigerant address 00

M-NET address 01

A-control remote controller

Refrigerant address 01

M-NET address 02

Refrigerant address 00

M-NET address 04

TB5

A-control remote controller

Group B

Refrigerant address 01

M-NET address 03

Refrigerant address 02

M-NET address 05

wIn group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As “03” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the group for the outdoor unit whose refrigerant address is “00”.

24

Image 24
Contents Contents Parts Catalog OCB429Reference Manual Indoor UnitSafety Precaution Always Observe for SafetyWhen charging directly from cylinder Additional refrigerant chargeR22 Features PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BSPUZ-A42NHA2 PUZ-A42NHA2-BS PUY-A42NHA2 PUY-A42NHA2-BS Specifications PUZ-A18NHA2 PUZ-A24NHA2 PUZ-A30NHA2 PUZ-A36NHA2 PUZ-A42NHA2PUY-A18NHA2-BS PUY-A24NHA2-BS Compressor Technical Data DataNoise Criterion Curves PUZ-A18NHA2-BSStandard Operation Data Heat pumpCooling only PKA-A12GA PKA-A18GA PKA-A24FA PKA-A30FA PKA-A36FA PLA-A42BAOutdoor Unit Unit mminchExample of Notes Service Space 662-5/8 Air outletWiring Diagram NET AdapterPUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BS NET AdapterWUse copper supply wires TABU/V/W Wiring Specifications System Simultaneous twin systemSeparate Indoor UNIT/OUTDOOR Unit Power Supplies OFFIndoor Outdoor Connecting Cable NET Wiring Method Refrigerant address NET address Control Remote ControllerNET address setting Refrigerant address settingRegulations in address settings NET wiringRefrigerant System Diagram PUZ-A18NHA2 PUZ-A18NHA2-BSPUZ-A42NHA2 PUZ-A42NHA2-BS Way valve solenoid coil Heating on Cooling OFFPUY-A12/18NHA2 PUY-A12/18NHA2-BS PUY-A42NHA2 PUY-A42NHA2-BSRefrigerant recovering pump down Start and finish of test runTroubleshooting TroubleshootingCheck Point Under Test RUN Before test runOperating procedures Symptoms in test run mode Cause Remote Controller DisplayContents of inferior phenomena Test run for wireless remote controller HOW to Proceed SELF-DIAGNOSIS When a Problem Occurs During OperationSelf-Diagnosis During Maintenance or Service Remote Controller Diagnosis ON/OFFMalfunction-diagnosis method by wireless remote controller Malfunction-diagnosis method at maintenance serviceProcedure Case of trouble during operationU9,UH Error Code Abnormal point and detection method Case 63L connector openSELF-DIAGNOSIS Action Table CndcError Code Case Judgment and action 63H connector openConnector open Indoor/outdoor unit connectorCase Judgment and action High pressure High-pressure switch High discharging temperatureAbnormalities detected while unit is operating 63H workedTemperature thermistor TH4 Temperature of heatsinkPower module Case Judgment and action Open/short circuit of dischargeSynchronous signal to main circuit When compressor lockedCurrent sensor error Case Judgment and action Outdoor fan motorRemote controller transmission ErrorE0/signal receiving errorE4Remote controller control board Case Judgment and action Low pressure 63L workedCase Judgment and action Remote controller transmission ErrorE3/signal receiving errorE5Error Signal receiving error Non defined error codeNET communication error Case Judgment and action Pipe temperatureHardware error of transmission Case Judgment and action Address duplicate definitionTo the next From the previous Fresh MasterMaster LossnayTroubleshooting by Inferior Phenomena VCTF, VCTFK, CVV CVS, VVR, VVF, VCTPhenomena Factor Countermeasure Melans Please Wait YESOutdoor power circuit board Power supply To the outdoor unit Check the breakerOutdoor connecting wire Miswiring, breakingIndoor/outdoor connecting wire Blinking Defective indoor Replace the indoor Power boardNot lighting Breaking or poor Fix the breaking or poorCheck if there is breaking Before repair Frequent calling from customers Action TablePhone Calls From Customers How to Respond Sometimes This is the sound which is heard when the flowRefrigerant in the air conditioner is switched This is not a malfunctionWith Blower… With Airflow Direction…There might be a case that Page HOW to Check the Parts Wiring contact check Power supply check Remove the connector CNF1Fuse check ENDHOW to Check the Components Thermistor feature chart Low temperature thermistorsMedium temperature thermistor High temperature thermistorOutput pulse signal and the valve operation Operation summary of the linear expansion valveLinear expansion valve operation Linear expansion valve A24, 30, 36 How to detach the coil How to attach the coilBe sure to attach the stopper Emergency operation procedure Emergency OperationReleasing emergency operation SW4Operation data during emergency operation Test Point Diagram LI, NI CNAC1, CNAC2CN5 LO, noPUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BS RS1 LD1-LD2 DIP-PFCDIP-IPM CN3 CN4 CN5Cnaf CN3TABP2/SC-P2 ActmUpper side Lower sideL1, L2 Function of SWITCHES, Connectors and Jumpers Function of switchesFunction Action by the switch operation Effective timing OFF2Function of connector SW9Special function 50%75% Display function of inspection for outdoor unit Blinking Abnormality of outdoor fan Motor rotational speed 1Check the outdoor fan motor 1Check if stop valves are openOperation indicator Digital indicator LED1 working detailsExample When 42500 times 425 100 times Secs 5secs ~9999 When it is 100 hours or more, hundreds digit, tensExample When 2450 hours 245 10 hours Lighting Cancellation of postponementSW2 setting Display detail Explanation for display Unit Outdoor unit setting information Single phase 2 3 phaseUnit Cooling onlyDegF Fan step on error occurring ~10 Step Example When 130 pulse Discharge superheat on error occurring ~327 0~182degC SHd Secs Sub cool on error occurring. SC ~234 0~130degCExample When 415 minutes Minute Secs U9 Error status during the ErrorRise of discharge temperature LEDEasy Maintenance Function Maintenance Mode Operation MethodSwitching to maintenance mode Fixed Hz operationData measurement To check the data for each item, repeat steps 5 toGuide for Operation Condition Function Setting Unit Function Setting by the Remote ControllerData of the sensor Ta=C On main remote Controller Average data Initial Ta=A+B/2 Sensor on allMode No.11 Setting No SettingsPLA-BA PCA-GA Selecting functions using the wired remote controller For modes 15 and higherSpecified indoor unit Press E FAN operationOperating Procedure Flow of function selection procedure Operating instructionsFunction Selection of Remote Controller Mode SelectionFunction selection flowchart Mode Vane FANButton for 3 seconds to switch to Maintenance monitor Check button for 3 seconds to return to maintenance modeTurn on the Monitoring the operation data PressRequest Code List Outdoor unit-Control state Code Description 100 For indoor fan pulsation controlDetail Contents in Request Code 101Error content U9 Request code 102Fan control state Request code Actuator output state Request codeOutdoor unit --Capacity setting display Request code Outdoor unit Setting information Request code103 Contact demand capacity Request code104 Indoor unit Model setting information Request code Indoor unit Capacity setting information Request code105 Data display See the table on the rightDisassembly Procedure PUZ-A18NHA2 PUZ-A18NHA2-BS Operating Procedure Photos106 PhotoRemoving the thermistor Outdoor 2-phase pipe TH6 107Removing the electrical parts box Thermistor Outdoor pipe TH3Operating Procedure Photos 108109 Removing the 4-way valveRemoving linear expansion valve Separator Recover refrigerant 110Removing the compressor MC Removing the accumulatorOperating Procedure Photos & Illustration Removing the service panel and top panel111 Removing the fan motor MF1112 Removing the thermistor Outdoor pipe TH3Thermistor Discharge TH4 113 Removing the 4-way valve coilRemoving the linear expansion valve coil Removing the bypass valve coil114 Removing the bypass valveRemoving the reactor ACLA24 115 Removing the reactor DCL A30Remove 2 receiver leg fixing screws 4 116 Removing the fan motor MF1, MF2Remove the service panel. See figure Outdoor pipe 117Remove the top panel. See figure Controller 118 Are not oxidizedLinear expansion Coil Valve coilLow pressure switch 63L 119Removing the reactor DCL and capacitor CE DCLRemove 2 back cover panel fixing screws 5 10

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.