Mitsubishi Electronics PUY-A36NHA2-BS, PUZ-A42NHA2-BS Refrigerant recovering pump down

Page 27

1. Refrigerant recovering (pump down)

Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit.

1Turn on the power supply (circuit breaker).

wWhen power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If“CEN- TRALLY CONTROLLED” is displayed, the refrigerant collecting (pump down) cannot be completed normally.

2After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and outdoor units) start operating and refrigerant recovering operation begins. LED1 and LED2 on the control board of the outdoor unit are lit.

wSet the SWP switch (push-button type) to ON in order to perform refrigerant recovering operation only when the unit is stopped. However, refrigerant recovering operation cannot be performed until compressor stops even if the unit is stopped. Wait 3 minutes until compressor stops and set the SWP switch to ON again.

3Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit and LED2 is lit), be sure to quickly close the gas stop valve.

wIn case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then repeat step 2 3 minutes later.

wIf the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain stopped until the power supply is turned off.

4Turn off the power supply (circuit breaker.)

2. Start and finish of test run

Operation from the indoor unit

Execute the test run using the installation manual for the indoor unit.

Operation from the outdoor unit

By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation mode (cooling/heating) can be set up.

1Set the operation mode (cooling/heating) using SW4-2.

 

<SW4>

2Turn on SW4-1 to start test run with the operation mode set by SW4-2.

 

C D

3Turn off SW4-1 to finish the test run.

 

ON

 

 

 

 

 

 

There may be a faint knocking sound around the machine room after power is supplied, but this is

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

no problem with product because the linear expansion valve is just moving to adjust opening pulse.

 

1

2

 

 

A B

There may be a knocking sound around the machine room for several seconds after compressor

 

starts operating. But this is not a problem with product because the check valve itself generates

A Stop

C operation

the sound because pressure difference is small in the refrigerant circuit.

B Cooling

D Heating

(PUZ only)

Note:

The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1, change the operation mode and restart the test run by SW4-1.)

27

Image 27
Contents Parts Catalog OCB429 ContentsIndoor Unit Reference ManualAlways Observe for Safety Safety PrecautionAdditional refrigerant charge When charging directly from cylinderR22 Features PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BSPUZ-A42NHA2 PUZ-A42NHA2-BS PUY-A42NHA2 PUY-A42NHA2-BS PUZ-A18NHA2 PUZ-A24NHA2 PUZ-A30NHA2 PUZ-A36NHA2 PUZ-A42NHA2 SpecificationsPUY-A18NHA2-BS PUY-A24NHA2-BS Data Compressor Technical DataPUZ-A18NHA2-BS Noise Criterion CurvesHeat pump Standard Operation DataPKA-A12GA PKA-A18GA PKA-A24FA PKA-A30FA PKA-A36FA PLA-A42BA Cooling onlyUnit mminch Outdoor UnitExample of Notes 662-5/8 Air outlet Service SpaceNET Adapter Wiring DiagramNET Adapter PUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BSWUse copper supply wires TABU/V/W System Simultaneous twin system Wiring SpecificationsOFF Separate Indoor UNIT/OUTDOOR Unit Power SuppliesIndoor Outdoor Connecting Cable Refrigerant address NET address Control Remote Controller NET Wiring MethodNET wiring NET address settingRefrigerant address setting Regulations in address settingsWay valve solenoid coil Heating on Cooling OFF Refrigerant System DiagramPUZ-A18NHA2 PUZ-A18NHA2-BS PUZ-A42NHA2 PUZ-A42NHA2-BSPUY-A42NHA2 PUY-A42NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BSStart and finish of test run Refrigerant recovering pump downBefore test run TroubleshootingTroubleshooting Check Point Under Test RUNOperating procedures Symptoms in test run mode Cause Remote Controller DisplayContents of inferior phenomena Test run for wireless remote controller HOW to Proceed SELF-DIAGNOSIS When a Problem Occurs During OperationSelf-Diagnosis During Maintenance or Service ON/OFF Remote Controller DiagnosisCase of trouble during operation Malfunction-diagnosis method by wireless remote controllerMalfunction-diagnosis method at maintenance service ProcedureU9,UH Cndc Error Code Abnormal point and detection method Case63L connector open SELF-DIAGNOSIS Action TableIndoor/outdoor unit connector Error CodeCase Judgment and action 63H connector open Connector open63H worked Case Judgment and action High pressure High-pressure switchHigh discharging temperature Abnormalities detected while unit is operatingCase Judgment and action Open/short circuit of discharge Temperature thermistor TH4Temperature of heatsink Power moduleCase Judgment and action Outdoor fan motor Synchronous signal to main circuitWhen compressor locked Current sensor errorCase Judgment and action Low pressure 63L worked Remote controller transmissionErrorE0/signal receiving errorE4 Remote controller control boardNon defined error code Case Judgment and action Remote controller transmissionErrorE3/signal receiving errorE5 Error Signal receiving errorCase Judgment and action Address duplicate definition NET communication errorCase Judgment and action Pipe temperature Hardware error of transmissionTo the next Lossnay From the previousFresh Master MasterTroubleshooting by Inferior Phenomena VCTF, VCTFK, CVV CVS, VVR, VVF, VCTPhenomena Factor Countermeasure Melans YES Please WaitMiswiring, breaking Outdoor power circuit boardPower supply To the outdoor unit Check the breaker Outdoor connecting wireBreaking or poor Fix the breaking or poor Indoor/outdoor connecting wire BlinkingDefective indoor Replace the indoor Power board Not lightingCheck if there is breaking Action Table Before repair Frequent calling from customersThis is not a malfunction Phone Calls From Customers How to RespondSometimes This is the sound which is heard when the flow Refrigerant in the air conditioner is switchedWith Blower… With Airflow Direction…There might be a case that Page HOW to Check the Parts END Wiring contact checkPower supply check Remove the connector CNF1 Fuse checkHigh temperature thermistor HOW to Check the ComponentsThermistor feature chart Low temperature thermistors Medium temperature thermistorOutput pulse signal and the valve operation Operation summary of the linear expansion valveLinear expansion valve operation Linear expansion valve A24, 30, 36 How to attach the coil How to detach the coilBe sure to attach the stopper SW4 Emergency operation procedureEmergency Operation Releasing emergency operationOperation data during emergency operation Test Point Diagram LO, no LI, NICNAC1, CNAC2 CN5PUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BS RS1 CN3 CN4 CN5 LD1-LD2DIP-PFC DIP-IPMActm CnafCN3 TABP2/SC-P2Upper side Lower sideL1, L2 OFF Function of SWITCHES, Connectors and JumpersFunction of switches Function Action by the switch operation Effective timingSW9 2Function of connectorSpecial function 50%75% Display function of inspection for outdoor unit 1Check the outdoor fan motor 1Check if stop valves are open Blinking Abnormality of outdoor fan Motor rotational speedDigital indicator LED1 working details Operation indicatorLighting Cancellation of postponement Example When 42500 times 425 100 times Secs 5secs~9999 When it is 100 hours or more, hundreds digit, tens Example When 2450 hours 245 10 hoursSW2 setting Display detail Explanation for display Unit Cooling only Outdoor unit setting informationSingle phase 2 3 phase UnitDegF Fan step on error occurring ~10 Step Example When 130 pulse U9 Error status during the Error Discharge superheat on error occurring ~327 0~182degC SHdSecs Sub cool on error occurring. SC ~234 0~130degC Example When 415 minutes Minute SecsLED Rise of discharge temperatureFixed Hz operation Easy Maintenance FunctionMaintenance Mode Operation Method Switching to maintenance modeTo check the data for each item, repeat steps 5 to Data measurementGuide for Operation Condition Average data Initial Ta=A+B/2 Sensor on all Function SettingUnit Function Setting by the Remote Controller Data of the sensor Ta=C On main remote ControllerMode No.11 Setting No SettingsPLA-BA PCA-GA Press E FAN operation Selecting functions using the wired remote controllerFor modes 15 and higher Specified indoor unitOperating Procedure Operating instructions Flow of function selection procedureMode Selection Function Selection of Remote ControllerFunction selection flowchart FAN Mode VanePress Button for 3 seconds to switch to Maintenance monitorCheck button for 3 seconds to return to maintenance mode Turn on the Monitoring the operation dataRequest Code List Outdoor unit-Control state Code Description For indoor fan pulsation control 100101 Detail Contents in Request CodeActuator output state Request code Error content U9 Request code102 Fan control state Request codeContact demand capacity Request code Outdoor unit --Capacity setting display Request codeOutdoor unit Setting information Request code 103104 Data display See the table on the right Indoor unit Model setting information Request codeIndoor unit Capacity setting information Request code 105Photo Disassembly ProcedurePUZ-A18NHA2 PUZ-A18NHA2-BS Operating Procedure Photos 106Thermistor Outdoor pipe TH3 Removing the thermistor Outdoor 2-phase pipe TH6107 Removing the electrical parts box108 Operating Procedure Photos109 Removing the 4-way valveRemoving linear expansion valve Removing the accumulator Separator Recover refrigerant110 Removing the compressor MCRemoving the fan motor MF1 Operating Procedure Photos & IllustrationRemoving the service panel and top panel 111112 Removing the thermistor Outdoor pipe TH3Thermistor Discharge TH4 Removing the bypass valve coil 113Removing the 4-way valve coil Removing the linear expansion valve coil114 Removing the bypass valveRemoving the reactor ACLA24 115 Removing the reactor DCL A30Remove 2 receiver leg fixing screws 4 Removing the fan motor MF1, MF2 116Remove the service panel. See figure Outdoor pipe 117Remove the top panel. See figure Controller Coil Valve coil 118Are not oxidized Linear expansionDCL Low pressure switch 63L119 Removing the reactor DCL and capacitor CERemove 2 back cover panel fixing screws 5 10

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.