Mitsubishi Electronics PUY-A42NHA2-BS Before repair Frequent calling from customers, Action Table

Page 51

• Before repair

Frequent calling from customers

Phone Calls From Customers

How to Respond

Note

Unit does 1 The operating display of remote

1 Check if power is supplied to air conditioner.

 

not operate controller does not come on.

Nothing appears on the display unless power is

 

at all.

supplied.

 

2Unit cannot be restarted for a 2 Wait around 3 minutes to restart unit.

 

while after it’s stopped.

The air conditioner is in a state of being protected

 

 

 

 

by the microcomputer’s directive. Once the

 

 

 

 

compressor is stopped, the unit cannot be

 

 

 

 

restarted for 3 minutes. This control is also applied

 

 

 

 

when the unit is turned on and off by remote

 

 

 

 

controller or thermostat.

 

 

 

 

 

 

 

 

3 Error code appears and blinks

3 Error code will be displayed if any protection

Refer to “SELF-DIAGNOSIS

 

on the display of remote

devices of the air conditioner are actuated.

ACTION TABLE”.

 

controller.

What is error code?

Check if servicing is

 

 

 

required for the error.

 

 

 

 

 

Remote

1 “PLEASE WAIT” is displayed

1 Wait around 2 minutes.

 

 

controller

on the screen.

An automatic startup test will be conducted for

 

 

 

 

2 minutes when power is supplied to the air

 

 

 

 

conditioner. “PLEASE WAIT” will be kept being

 

 

 

 

displayed while that time.

 

 

2“FILTER” is displayed on the 2 This indicates that it is time to clean the air filters. Display time of “FILTER”

screen.

Clean the air filters. Press the FILTER button on

depends on the model.

 

the remote controller twice to clear “FILTER” from Long life filter: 2500 hrs.

 

the display.

Regular filter: 100 hrs.

 

See the operation manual that came with the

 

 

product for how to clean the filters.

 

3“STANDBY” is displayed on the 3 This is displayed when the unit starts HEAT

screen.

operation, when the thermostat puts the

 

compressor in operation mode, or when the

 

outdoor unit ends DEFROST operation and

 

returns to HEAT operation.

 

The display will automatically disappear around

 

10 minutes later.

 

While “STANDBY” is displayed on the remote

 

controller, the airflow amount will be restricted

 

because the indoor unit’s heat exchanger is not

 

fully heated up. In addition to that, the up/down

 

vane will be automatically set to horizontal blow

 

in order to prevent cold air from directly blowing

 

out to human body. The up/down vane will return

 

to the setting specified by the remote controller

 

when “STANDBY” is released.

4“DEFROST” is displayed on 4 The outdoor unit gets frosted when the outside

the screen. (No air comes out of

temperature is low and the humidity is high.

the unit.)

“DEFROST” indicates the DEFROST operation

 

is being performed to melt this frost. The

 

DEFROST operation ends in around 10 minutes

 

(at most 15 minutes).

 

During the DEFROST operation, the indoor unit’s

 

heat exchanger becomes cold, so the blower is

 

stopped. The up/down vane will be automatically

 

set to horizontal blow in order to prevent cold air

 

from directly blowing out to human body. The

 

display will turn into “STANDBY” when DEFROST

 

operation ends.

51

Image 51
Contents Parts Catalog OCB429 ContentsIndoor Unit Reference ManualAlways Observe for Safety Safety PrecautionAdditional refrigerant charge When charging directly from cylinderR22 Features PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BSPUZ-A42NHA2 PUZ-A42NHA2-BS PUY-A42NHA2 PUY-A42NHA2-BS PUZ-A18NHA2 PUZ-A24NHA2 PUZ-A30NHA2 PUZ-A36NHA2 PUZ-A42NHA2 SpecificationsPUY-A18NHA2-BS PUY-A24NHA2-BS Data Compressor Technical DataPUZ-A18NHA2-BS Noise Criterion CurvesHeat pump Standard Operation DataPKA-A12GA PKA-A18GA PKA-A24FA PKA-A30FA PKA-A36FA PLA-A42BA Cooling onlyUnit mminch Outdoor UnitExample of Notes 662-5/8 Air outlet Service SpaceNET Adapter Wiring DiagramNET Adapter PUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BSWUse copper supply wires TABU/V/W System Simultaneous twin system Wiring SpecificationsOFF Separate Indoor UNIT/OUTDOOR Unit Power SuppliesIndoor Outdoor Connecting Cable Refrigerant address NET address Control Remote Controller NET Wiring MethodNET wiring NET address settingRefrigerant address setting Regulations in address settingsWay valve solenoid coil Heating on Cooling OFF Refrigerant System DiagramPUZ-A18NHA2 PUZ-A18NHA2-BS PUZ-A42NHA2 PUZ-A42NHA2-BSPUY-A42NHA2 PUY-A42NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BSStart and finish of test run Refrigerant recovering pump downBefore test run TroubleshootingTroubleshooting Check Point Under Test RUNOperating procedures Symptoms in test run mode Cause Remote Controller DisplayContents of inferior phenomena Test run for wireless remote controller HOW to Proceed SELF-DIAGNOSIS When a Problem Occurs During OperationSelf-Diagnosis During Maintenance or Service ON/OFF Remote Controller DiagnosisCase of trouble during operation Malfunction-diagnosis method by wireless remote controllerMalfunction-diagnosis method at maintenance service ProcedureU9,UH Cndc Error Code Abnormal point and detection method Case63L connector open SELF-DIAGNOSIS Action TableIndoor/outdoor unit connector Error CodeCase Judgment and action 63H connector open Connector open63H worked Case Judgment and action High pressure High-pressure switchHigh discharging temperature Abnormalities detected while unit is operatingCase Judgment and action Open/short circuit of discharge Temperature thermistor TH4Temperature of heatsink Power moduleCase Judgment and action Outdoor fan motor Synchronous signal to main circuitWhen compressor locked Current sensor errorCase Judgment and action Low pressure 63L worked Remote controller transmissionErrorE0/signal receiving errorE4 Remote controller control boardNon defined error code Case Judgment and action Remote controller transmissionErrorE3/signal receiving errorE5 Error Signal receiving errorCase Judgment and action Address duplicate definition NET communication errorCase Judgment and action Pipe temperature Hardware error of transmissionTo the next Lossnay From the previousFresh Master MasterTroubleshooting by Inferior Phenomena VCTF, VCTFK, CVV CVS, VVR, VVF, VCTPhenomena Factor Countermeasure Melans YES Please WaitMiswiring, breaking Outdoor power circuit boardPower supply To the outdoor unit Check the breaker Outdoor connecting wireBreaking or poor Fix the breaking or poor Indoor/outdoor connecting wire BlinkingDefective indoor Replace the indoor Power board Not lightingCheck if there is breaking Action Table Before repair Frequent calling from customersThis is not a malfunction Phone Calls From Customers How to RespondSometimes This is the sound which is heard when the flow Refrigerant in the air conditioner is switchedWith Blower… With Airflow Direction…There might be a case that Page HOW to Check the Parts END Wiring contact checkPower supply check Remove the connector CNF1 Fuse checkHigh temperature thermistor HOW to Check the ComponentsThermistor feature chart Low temperature thermistors Medium temperature thermistorOutput pulse signal and the valve operation Operation summary of the linear expansion valveLinear expansion valve operation Linear expansion valve A24, 30, 36 How to attach the coil How to detach the coilBe sure to attach the stopper SW4 Emergency operation procedureEmergency Operation Releasing emergency operationOperation data during emergency operation Test Point Diagram LO, no LI, NICNAC1, CNAC2 CN5PUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BS RS1 CN3 CN4 CN5 LD1-LD2DIP-PFC DIP-IPMActm CnafCN3 TABP2/SC-P2Upper side Lower sideL1, L2 OFF Function of SWITCHES, Connectors and JumpersFunction of switches Function Action by the switch operation Effective timingSW9 2Function of connectorSpecial function 50%75% Display function of inspection for outdoor unit 1Check the outdoor fan motor 1Check if stop valves are open Blinking Abnormality of outdoor fan Motor rotational speedDigital indicator LED1 working details Operation indicatorLighting Cancellation of postponement Example When 42500 times 425 100 times Secs 5secs~9999 When it is 100 hours or more, hundreds digit, tens Example When 2450 hours 245 10 hoursSW2 setting Display detail Explanation for display Unit Cooling only Outdoor unit setting informationSingle phase 2 3 phase UnitDegF Fan step on error occurring ~10 Step Example When 130 pulse U9 Error status during the Error Discharge superheat on error occurring ~327 0~182degC SHdSecs Sub cool on error occurring. SC ~234 0~130degC Example When 415 minutes Minute SecsLED Rise of discharge temperatureFixed Hz operation Easy Maintenance FunctionMaintenance Mode Operation Method Switching to maintenance modeTo check the data for each item, repeat steps 5 to Data measurementGuide for Operation Condition Average data Initial Ta=A+B/2 Sensor on all Function SettingUnit Function Setting by the Remote Controller Data of the sensor Ta=C On main remote ControllerMode No.11 Setting No SettingsPLA-BA PCA-GA Press E FAN operation Selecting functions using the wired remote controllerFor modes 15 and higher Specified indoor unitOperating Procedure Operating instructions Flow of function selection procedureMode Selection Function Selection of Remote ControllerFunction selection flowchart FAN Mode VanePress Button for 3 seconds to switch to Maintenance monitorCheck button for 3 seconds to return to maintenance mode Turn on the Monitoring the operation dataRequest Code List Outdoor unit-Control state Code Description For indoor fan pulsation control 100101 Detail Contents in Request CodeActuator output state Request code Error content U9 Request code102 Fan control state Request codeContact demand capacity Request code Outdoor unit --Capacity setting display Request codeOutdoor unit Setting information Request code 103104 Data display See the table on the right Indoor unit Model setting information Request codeIndoor unit Capacity setting information Request code 105Photo Disassembly ProcedurePUZ-A18NHA2 PUZ-A18NHA2-BS Operating Procedure Photos 106Thermistor Outdoor pipe TH3 Removing the thermistor Outdoor 2-phase pipe TH6107 Removing the electrical parts box108 Operating Procedure Photos109 Removing the 4-way valveRemoving linear expansion valve Removing the accumulator Separator Recover refrigerant110 Removing the compressor MCRemoving the fan motor MF1 Operating Procedure Photos & IllustrationRemoving the service panel and top panel 111112 Removing the thermistor Outdoor pipe TH3Thermistor Discharge TH4 Removing the bypass valve coil 113Removing the 4-way valve coil Removing the linear expansion valve coil114 Removing the bypass valveRemoving the reactor ACLA24 115 Removing the reactor DCL A30Remove 2 receiver leg fixing screws 4 Removing the fan motor MF1, MF2 116Remove the service panel. See figure Outdoor pipe 117Remove the top panel. See figure Controller Coil Valve coil 118Are not oxidized Linear expansionDCL Low pressure switch 63L119 Removing the reactor DCL and capacitor CERemove 2 back cover panel fixing screws 5 10

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.