Mitsubishi Electronics PUY-A12NHA2 Abnormalities detected while unit is operating, 63H worked

Page 37

<Abnormalities detected while unit is operating>

Error Code

Abnormal point and detection method

Case

Judgment and action

 

High pressure (High-pressure switch

1 Short cycle of indoor unit

1~6Check indoor unit and repair the defect.

 

63H worked)

2 Clogged filter of indoor unit

 

 

Abnormal if high-pressure switch 63H

3 Decreased airflow caused by

 

 

worked ( w ) during compressor operation.

dirt of indoor fan

 

 

w 4.15 MPa [602PSIG]

4 Dirt of indoor heat exchanger

 

 

63H: High-pressure switch

5 Locked indoor fan motor

 

 

6 Malfunction of indoor fan motor

7 Check if stop valve is fully open.

 

 

7 Defective operation of stop

 

 

valve (Not full open)

 

 

 

8 Clogged or broken pipe

8 Check piping and repair the defect.

 

 

9 Locked outdoor fan motor

9~2 Check outdoor unit and repair the defect.

 

 

0 Malfunction of outdoor fan

 

 

 

motor

 

 

 

1 Short cycle of outdoor unit

 

U1

 

2 Dirt of outdoor heat exchanger

3 Check the inspected temperature of outside

 

3 Decreased airflow caused by

(1302)

 

 

defective inspection of outside

temperature thermistor on LED display.

 

 

 

 

temperature thermistor

(SW2 on A-Control Service Tool : Refer to 10-

 

 

(It detects lower temperature

10.)

 

 

than actual temperature.)

4~6Turn the power off and check F5 is

 

 

4 Disconnection or contact failure

 

 

of connector (63H) on outdoor

displayed when the power is on again.

 

 

controller board

When F5 is displayed, refer to “Judgment

 

 

5 Disconnection or contact failure

and action” for F5.

 

 

of 63H connection

 

 

 

6 Defective outdoor controller

 

 

 

board

7 Check linear expansion valve.

 

 

7 Defective action of linear

 

 

expansion valve

Refer to 10-6, 7.

 

 

8 Malfunction of fan driving

8 Replace outdoor controller board.

 

 

circuit

 

 

 

 

 

 

High discharging temperature

1 Overheated compressor opera-

1 Check intake superheat.

 

(1) Abnormal if discharge temperature ther-

tion caused by shortage of

Check leakage of refrigerant.

 

mistor (TH4) exceeds 125:[257˚F] or

refrigerant

Charge additional refrigerant.

 

110: [230˚F] continuously for 5 min-

2 Defective operation of stop

2 Check if stop valve is fully open.

 

utes.

valve

 

 

Abnormal if condenser/evaporator tem-

3 Defective thermistor

34 Turn the power off and check if U3 is dis-

 

perature thermistor (TH5) exceeds 40:

4 Defective outdoor controller

played when the power is on again.

 

[104˚F] during defrosting and discharge

board

When U3 is displayed, refer to “Judgement

 

temperature thermistor (TH4) exceeds

 

and action” for U3.

 

110: [230˚F].

5 Defective action of linear

5 Check linear expansion valve.

 

(2) Abnormal if discharge superheat

expansion valve

Refer to 10-6, 7.

 

 

 

 

(Cooling: TH4 – TH5 / Heating: TH4 –

 

 

 

TH6) increases.

 

 

 

All the conditions in A or B are detected

 

 

 

simultaneously for 10 minutes continu-

 

 

 

ously after 6 minutes past from com-

 

 

 

pressor start-up (including the thermo-

 

 

U2

stat indication or recovery from defrost-

 

 

ing).

 

 

(1102)

<Condition A>

 

 

 

• Heating mode

 

 

 

• When discharge superheat is less

 

 

 

than 70 deg [126˚F].

 

 

 

• When the TH6 temp is more than the

 

 

 

value obtained by TH7 – 5 deg [9˚F].

 

 

 

• When the condensing temp of TH5 is

 

 

 

less than 35: [95˚F].

 

 

<Condition B>

During comp operation (Cooling and Heating)

When discharge superheat is less than 80 deg [144˚F] in cooling

When discharge super heat is less than 90 deg [162˚F] in heating

When condensing temp of TH6 is more than –40:[–40˚F] (In cooling only)

37

Image 37
Contents Parts Catalog OCB429 ContentsIndoor Unit Reference ManualAlways Observe for Safety Safety PrecautionAdditional refrigerant charge When charging directly from cylinderR22 PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BS FeaturesPUZ-A42NHA2 PUZ-A42NHA2-BS PUY-A42NHA2 PUY-A42NHA2-BS PUZ-A18NHA2 PUZ-A24NHA2 PUZ-A30NHA2 PUZ-A36NHA2 PUZ-A42NHA2 SpecificationsPUY-A18NHA2-BS PUY-A24NHA2-BS Data Compressor Technical DataPUZ-A18NHA2-BS Noise Criterion CurvesHeat pump Standard Operation DataPKA-A12GA PKA-A18GA PKA-A24FA PKA-A30FA PKA-A36FA PLA-A42BA Cooling onlyUnit mminch Outdoor UnitExample of Notes 662-5/8 Air outlet Service SpaceNET Adapter Wiring DiagramNET Adapter PUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BSWUse copper supply wires TABU/V/W System Simultaneous twin system Wiring SpecificationsOFF Separate Indoor UNIT/OUTDOOR Unit Power SuppliesIndoor Outdoor Connecting Cable Refrigerant address NET address Control Remote Controller NET Wiring MethodRefrigerant address setting NET address settingRegulations in address settings NET wiringPUZ-A18NHA2 PUZ-A18NHA2-BS Refrigerant System DiagramPUZ-A42NHA2 PUZ-A42NHA2-BS Way valve solenoid coil Heating on Cooling OFFPUY-A42NHA2 PUY-A42NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BSStart and finish of test run Refrigerant recovering pump downTroubleshooting TroubleshootingCheck Point Under Test RUN Before test runSymptoms in test run mode Cause Remote Controller Display Operating proceduresContents of inferior phenomena Test run for wireless remote controller When a Problem Occurs During Operation HOW to Proceed SELF-DIAGNOSISSelf-Diagnosis During Maintenance or Service ON/OFF Remote Controller DiagnosisMalfunction-diagnosis method at maintenance service Malfunction-diagnosis method by wireless remote controllerProcedure Case of trouble during operationU9,UH 63L connector open Error Code Abnormal point and detection method CaseSELF-DIAGNOSIS Action Table CndcCase Judgment and action 63H connector open Error CodeConnector open Indoor/outdoor unit connectorHigh discharging temperature Case Judgment and action High pressure High-pressure switchAbnormalities detected while unit is operating 63H workedTemperature of heatsink Temperature thermistor TH4Power module Case Judgment and action Open/short circuit of dischargeWhen compressor locked Synchronous signal to main circuitCurrent sensor error Case Judgment and action Outdoor fan motorErrorE0/signal receiving errorE4 Remote controller transmissionRemote controller control board Case Judgment and action Low pressure 63L workedErrorE3/signal receiving errorE5 Case Judgment and action Remote controller transmissionError Signal receiving error Non defined error codeCase Judgment and action Pipe temperature NET communication errorHardware error of transmission Case Judgment and action Address duplicate definitionTo the next Fresh Master From the previousMaster LossnayVCTF, VCTFK, CVV CVS, VVR, VVF, VCT Troubleshooting by Inferior PhenomenaPhenomena Factor Countermeasure Melans YES Please WaitPower supply To the outdoor unit Check the breaker Outdoor power circuit boardOutdoor connecting wire Miswiring, breakingDefective indoor Replace the indoor Power board Indoor/outdoor connecting wire BlinkingNot lighting Breaking or poor Fix the breaking or poorCheck if there is breaking Action Table Before repair Frequent calling from customersSometimes This is the sound which is heard when the flow Phone Calls From Customers How to RespondRefrigerant in the air conditioner is switched This is not a malfunctionWith Airflow Direction… With Blower…There might be a case that Page HOW to Check the Parts Power supply check Remove the connector CNF1 Wiring contact checkFuse check ENDThermistor feature chart Low temperature thermistors HOW to Check the ComponentsMedium temperature thermistor High temperature thermistorOperation summary of the linear expansion valve Output pulse signal and the valve operationLinear expansion valve operation Linear expansion valve A24, 30, 36 How to attach the coil How to detach the coilBe sure to attach the stopper Emergency Operation Emergency operation procedureReleasing emergency operation SW4Operation data during emergency operation Test Point Diagram CNAC1, CNAC2 LI, NICN5 LO, noPUZ-A24NHA2 PUZ-A24NHA2-BS PUY-A24NHA2 PUY-A24NHA2-BS RS1 DIP-PFC LD1-LD2DIP-IPM CN3 CN4 CN5CN3 CnafTABP2/SC-P2 ActmLower side Upper sideL1, L2 Function of switches Function of SWITCHES, Connectors and JumpersFunction Action by the switch operation Effective timing OFFSW9 2Function of connector50% Special function75% Display function of inspection for outdoor unit 1Check the outdoor fan motor 1Check if stop valves are open Blinking Abnormality of outdoor fan Motor rotational speedDigital indicator LED1 working details Operation indicator~9999 When it is 100 hours or more, hundreds digit, tens Example When 42500 times 425 100 times Secs 5secsExample When 2450 hours 245 10 hours Lighting Cancellation of postponementSW2 setting Display detail Explanation for display Unit Single phase 2 3 phase Outdoor unit setting informationUnit Cooling onlyDegF Fan step on error occurring ~10 Step Example When 130 pulse Secs Sub cool on error occurring. SC ~234 0~130degC Discharge superheat on error occurring ~327 0~182degC SHdExample When 415 minutes Minute Secs U9 Error status during the ErrorLED Rise of discharge temperatureMaintenance Mode Operation Method Easy Maintenance FunctionSwitching to maintenance mode Fixed Hz operationTo check the data for each item, repeat steps 5 to Data measurementGuide for Operation Condition Unit Function Setting by the Remote Controller Function SettingData of the sensor Ta=C On main remote Controller Average data Initial Ta=A+B/2 Sensor on allSetting No Settings Mode No.11PLA-BA PCA-GA For modes 15 and higher Selecting functions using the wired remote controllerSpecified indoor unit Press E FAN operationOperating Procedure Operating instructions Flow of function selection procedureMode Selection Function Selection of Remote ControllerFunction selection flowchart FAN Mode VaneCheck button for 3 seconds to return to maintenance mode Button for 3 seconds to switch to Maintenance monitorTurn on the Monitoring the operation data PressRequest Code List Outdoor unit-Control state Code Description For indoor fan pulsation control 100101 Detail Contents in Request Code102 Error content U9 Request codeFan control state Request code Actuator output state Request codeOutdoor unit Setting information Request code Outdoor unit --Capacity setting display Request code103 Contact demand capacity Request code104 Indoor unit Capacity setting information Request code Indoor unit Model setting information Request code105 Data display See the table on the rightPUZ-A18NHA2 PUZ-A18NHA2-BS Operating Procedure Photos Disassembly Procedure106 Photo107 Removing the thermistor Outdoor 2-phase pipe TH6Removing the electrical parts box Thermistor Outdoor pipe TH3108 Operating Procedure PhotosRemoving the 4-way valve 109Removing linear expansion valve 110 Separator Recover refrigerantRemoving the compressor MC Removing the accumulatorRemoving the service panel and top panel Operating Procedure Photos & Illustration111 Removing the fan motor MF1Removing the thermistor Outdoor pipe TH3 112Thermistor Discharge TH4 Removing the 4-way valve coil 113Removing the linear expansion valve coil Removing the bypass valve coilRemoving the bypass valve 114Removing the reactor ACLA24 Removing the reactor DCL A30 115Remove 2 receiver leg fixing screws 4 Removing the fan motor MF1, MF2 116117 Remove the service panel. See figure Outdoor pipeRemove the top panel. See figure Controller Are not oxidized 118Linear expansion Coil Valve coil119 Low pressure switch 63LRemoving the reactor DCL and capacitor CE DCLRemove 2 back cover panel fixing screws 5 10

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.