Mitsubishi Electronics PUHY-YMC installation manual Multiple line/header

Page 14

ENGLISH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Constant

 

 

 

 

Variable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity unit

 

 

capacity unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Distributer (gas) (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Oil balance pipe (optional) I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Constant

 

Variable

 

 

 

 

 

 

 

 

(for distribution within the unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas line B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity unit

capacity unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas line A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Distributer (liguid) (optional)

Multiple line/header

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas line (main) C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line (main) C

 

 

 

 

 

 

 

 

 

Note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:indicates piping connection points

 

 

 

A

 

 

G

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection examples

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Distributer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(connecting to six indoor units)

 

 

 

 

 

 

 

 

 

 

(liquid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To down stream units

 

 

 

 

 

 

 

 

 

 

Distributer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

(gas)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Branch header

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The model total for downstream units

 

 

 

 

 

 

 

 

 

 

First branch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shown in the table below is the model

 

 

 

 

 

 

 

 

 

 

(branch joint)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

d

 

 

 

 

e

 

 

 

 

 

f

 

 

Cap

total when viewed from Point A in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

drawing above.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

In door

 

In door In door

 

 

 

With the exception of PUHY-600YMC,

 

 

 

 

 

 

 

 

 

 

 

 

Branch joint In door

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In door

 

 

In door

 

 

 

 

unit

 

unit

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

b

 

c

 

 

 

 

 

 

h

 

 

 

 

the first branch is always CMY-Y302-F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

unit

 

 

 

unit

 

 

4

 

 

5

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

2

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1: Because it is built into the variable capacity unit, B is used to carry liquid only. Set the constant capacity unit and

 

 

 

 

 

 

 

 

 

 

 

variable capacity unit in accordance with the G dimension given in the figure above (G = 0.01 m).

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping components

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tolerance

 

 

 

 

 

length

 

Indoor

 

Total piping length

 

 

 

 

 

 

 

A+B+C+D+E+F+a+b+c+d+e+f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220 m or less

 

 

 

 

 

 

 

Farthest piping length after first branch (r)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D+E+c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 m or less

 

 

 

 

 

 

 

side

 

Farthest piping length

(L)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A (B)+C+D+E+c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 m or less (Max. equivalent length 125 m)

Permissible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The included oil balance pipe must be used. If any other piping is used, the length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

Oil balance pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the oil balance pipe must be no more than 3 m (max. equivalent length 4 m),

 

 

side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and height from the bottom of the unit must be no more than 0.1 m.

 

 

 

Distributer (liquid)/Variable capacity unit, Constant capacity unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A, B (Liquid line)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 m or less (Max. equivalent length 5 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Distributer (gas)/Constant capacity unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A (Gas line)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 m or less (Max. equivalent length 5 m)

Permissible high/

 

Indoor/Outdoor

Outdoor upper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 m or less

 

 

 

 

 

 

Outdoor lower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 m or less

 

 

 

 

 

Low difference

 

Indoor/Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 m or less

 

 

 

 

 

 

 

 

 

Variable capacity unit/Constant capacity unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be installed on same frame, and there must be no high/low difference.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selecting the refrigerant branch kit

 

Select the branch kit, sold separately, from the table below. (Each kit contains a refrigerant and gas piping set.)

Use the table to the right to make the selection based

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line branching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header branching

 

on the model total of indoor units downstream from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total of units downstream

Total of units downstream

Total of units downstream

Total of units downstream

 

 

 

4 branching

 

 

7 branching

 

10 branching

 

branch section or on the number of indoor units to be

 

 

 

 

 

 

 

 

 

 

less than 180

 

 

 

 

 

 

 

 

181 to 370

 

 

 

 

 

 

 

 

371 to 710

 

 

more than 711

 

 

 

 

 

header

 

 

 

 

header

 

header

 

connected on the header branch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CMY-Y102S-C

 

CMY-Y102L-C

 

 

 

 

CMY-Y202-C

 

CMY-Y302-C

 

 

CMY-Y104

CMY-Y107

CMY-Y1010

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select each section of refrigerant piping

 

(1) Refrigerant piping diameter in section from out-

 

(2) Refrigerant piping diameter in section from

 

 

 

 

 

 

 

 

door unit to first branch (outdoor unit piping diam-

 

 

 

 

branch to indoor unit (indoor unit piping diam-

(1)

Section from outdoor unit to first

 

 

 

eter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

eter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

branch (C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

Piping diameter (mm)

 

 

 

 

 

Model number

 

 

 

 

 

Piping diameter (mm)

 

(2) Sections from branch to indoor

Each section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line

 

 

 

 

 

Gas line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line

 

 

 

ø 6.35

 

 

 

 

unit (a, b, c, d, e, f)

of piping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22 ·28 ·36 ·45

 

 

 

 

 

 

 

 

 

 

PUHY-600YSMC

 

 

 

 

ø 19.05

 

 

 

 

 

 

 

ø 38.1

 

 

 

 

 

 

 

 

 

Gas line

 

 

 

ø 12.7

 

 

(3) Section from branch to branch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUHY-650YSMC

 

 

 

 

ø 19.05

 

 

 

 

 

 

 

ø 44.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line

 

 

 

ø 9.52

 

 

 

 

(D, E, F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

56 to 90

 

 

 

 

 

 

 

 

 

 

 

 

PUHY-700YSMC

 

 

 

 

ø 19.05

 

 

 

 

 

 

 

ø 44.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas line

 

 

 

ø 15.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select the size from the table to the right.

 

PUHY-750YSMC

 

 

 

 

ø 19.05

 

 

 

 

 

 

 

ø 44.45

 

 

 

 

 

112 ·140 ·160

 

 

 

Liquid line

 

 

ø 9.52

 

 

 

(3) Refrigerant piping diameter in section from branch

 

 

 

 

 

Gas line

 

 

 

ø 19.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

224

 

 

 

 

 

 

 

Liquid line

 

 

 

ø 12.7

 

 

 

 

 

 

 

 

 

 

to branch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas line

 

 

 

ø 25.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid line

 

 

ø 12.7

 

 

 

 

 

 

 

 

 

Downstream unit model total

Liquid line (mm)

 

 

Gas line (mm)

 

 

 

 

 

280

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas line

 

 

 

ø 28.6

 

 

 

 

 

 

 

 

 

 

 

 

90 or less

 

 

 

 

 

 

 

 

 

ø 9.52

 

 

 

 

 

 

 

ø 15.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

91 to 180

 

 

 

 

 

 

 

 

 

ø 12.7

 

 

 

 

 

 

 

ø 19.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

181 to 370

 

 

 

 

ø 12.7

 

 

 

 

 

 

 

ø 25.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

371 to 540

 

 

 

 

ø 15.88

 

 

 

 

 

 

 

ø 31.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

541 to 710

 

 

 

 

ø 15.88

 

 

 

 

 

 

 

ø 38.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

711 or more

 

 

 

 

ø 19.05

 

 

 

 

 

 

 

ø 44.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional refrigerant charge

 

 

<Additional charge>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The outdoor unit is charged with refrigerant at the time of

 

Liquid pipe size

 

 

Liquid pipe size

 

 

 

Liquid pipe size

 

 

Liquid pipe size

 

 

 

Liquid pipe size

 

 

 

shipping according to the chart above. As this charge

 

 

 

 

 

 

 

 

 

 

 

 

 

total length of

 

 

 

 

 

 

 

total length of

 

 

 

 

 

 

 

total length of

 

 

total length of

 

 

 

total length of

 

 

 

 

does not include the amount needed for extended piping,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø 19.05 0.29

 

 

 

 

 

+

ø 15.88

0.25

 

 

 

 

+

 

ø 12.7 0.12

+

 

ø 9.52

0.06

 

 

+

ø 6.35 0.024

 

+ α

additional charging for each refrigerant line will be required

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on site. In order that future servicing may be properly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

provided, always keep a record of the size and length of

 

(m)

 

0.29 (kg/m)

 

(m) 0.25 (kg/m)

 

 

(m) 0.12 (kg/m)

 

(m)

0.06 (kg/m)

 

 

(m) 0.024 (kg/m)

 

each refrigerant line and the amount of additional charge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Example> Indoor 1 : 125

A : ø 12.7

3 m

 

a

:ø 9.52

 

 

 

 

10 m

 

 

 

 

 

 

 

 

 

 

 

 

 

by writing it in the space provided on the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculation of additional refrigerant charge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 : 125

 

B : ø 15.88

1 m

 

b

:ø 9.52

 

 

 

 

 

5 m

 

 

 

At the conditions

• Calculate the amount of additional charge based on the length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 : 125

 

C : ø 19.05

30 m

 

 

c

:ø 9.52

 

 

 

 

 

5 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 : 125

 

D : ø 15.88

10 m

 

d

:ø 9.52

 

 

 

 

10 m

 

 

 

below:

 

 

 

 

 

 

of the piping extension and the size of the refrigerant line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 : 100

 

E : ø 12.7

5 m

 

e

:ø 9.52

 

 

 

 

15 m

 

 

 

 

 

 

 

 

 

 

 

 

 

• Use the table to the right as guide to calculating the amount

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 : 40

 

 

F : ø 12.7

15 m

 

 

f

:ø 6.35

 

 

 

 

 

5 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of additional charging and charge the system according.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The total length of each liquid line is as follows

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the calculation results in a fraction of less than 0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø 19.05 : C = 30 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kg, round up to the next 0.1 kg. For example, if the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø 15.88 : B + D = 1 + 10 = 11 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value of

α

 

 

 

 

 

 

 

 

 

 

 

 

 

 

result of the calculation was 20.03 kg, round the re-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø 12.7 : A + E + F = 3 + 5 + 15 = 23 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sult up to 20.1 kg.

 

 

ø 9.52 : a + b + c + d + e = 10 + 5 + 5 + 10 + 15 = 45 m

 

 

 

 

 

 

 

 

 

Total capacity of

 

 

α

 

 

If the total amount of refrigerant including the amount

ø 6.35

 

 

: f = 5 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connecting indoor units

 

 

 

 

 

 

 

of refrigerant sealed in the outdoor unit when shipped

 

Therefore,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to Model 80

 

1.0 kg

 

 

 

from the factor plus additional refrigerant for exten-

 

<Calculation example>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models 81 to 160

 

1.5 kg

 

 

 

 

Additional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sion piping exceeds 73 kg, use 73 kg as the total

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models 161 to 330

 

2.0 kg

 

 

 

 

refrigerant charge = 30

 

0.29 +11

 

0.25 + 23 0.12 +

 

 

 

 

 

 

 

 

 

 

 

 

amount of refrigerant.

 

 

 

 

 

 

 

 

 

 

 

 

Models 331 to 480

 

2.5 kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

 

0.06 + 5

 

 

0.024 + 3.0 = 20.1 kg

 

 

 

 

 

 

 

 

 

 

 

 

Amount of refrigerant when shipped from factory +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models 481 or more

 

3.0 kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

added refrigerant = 73 kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Image 14
Contents PUHY-YMC Contents Before getting installed Safety precautionsBefore installation and electric work Before getting installed moved electrical work Before starting the test runCombination with indoor units Confirmation of parts attachedModel Name Connecting pipe Elbow Shape Outdoor unit configurationSelection of installation site Variable capacity unit Constant capacity unitWhen there is an obstruction above the unit Individual installationWhen inlet air enters from right and left sides of unit Space required around unitBe very careful to carry product Lifting method and weight of productCollective installation and continu- ous installation Example of collective installation Installation of unitInstallation Location of anchor bolt60/61 dB A-weighted Connecting direction for refrigerant pipingDown piping and down wiring precautions Noise levelPUHY-400/500YMC Snow and seasonal windCountermeasure to seasonal wind PUHN-200/250YMCNever perform a pump down. This will damage the compressor Refrigerant piping installationAreas of caution Refrigerant piping system + αMultiple line/header Precautions concerning piping connection and valve operation For variable capacity unitGas side Liquid side Oil balance side Figure shows valve fully open100 to 1000 to Tightening angle standard Pipe diameter mm 50 to 57.5 / 500 to75 to 750 to 60 toOil balance pipe connection method Distributor gas connection method Part could be damaged if not cooled sufficientlyRestrictions on the posture for attaching joints How to install branch pipeJoint Gram belowEvacuation Airtight test and evacuationAirtight test No heat insulation must be provided for electric wires Thermal insulation of refrigerant pipingPenetrations Inner wall concealed Floor fireproofingElectrical work Constant capacity unit Control box and connecting posi- tion of wiringVariable capacity unit Hole For details, see item 11.3. Wiring transmission cablesPlate Transmission booster optionalWiring examples Wiring transmission cablesConnecting a transmission booster Name, code and possible unit connectionsOne remote control unit for each indoor unit Wiring method, address settingRemote control RC terminal block TB6 Within Address Unit Remote control operation Same as aboveFor details, see wire connection example C Unit Range Setting method Wiring LineSame group to the remote control RC terminal block TB6 Main remote controllerExtended length and the length to the most remote unit Capability Number of connected indoor units that can be WiringBooster RP Wiring of main power supply and equipment capacity Checking before getting test run Operation procedureTest run Test run methodHow to cope with test run abnormality AbnormalityDisplay at LED lighting blinking Remarks Flag Relay output 6603 Transmission error Transmission route Busy ErrorPower on Flag 8 always lightsCoping with remote controller abnormality Following phenomena do not represent abnormality emergency NMK Nknk NkokNKPK#$%&*+ Nkqk#$%&*+#,%&- ./0123145&6789#$%&=?@. !# Sknk Skok #$% +,-.ÜTK= UknkUkok Ukpk Ukqk Vkok NMK= Nmknk =NMKOK= $%&*+,-./01#$%&*+QMã NMKPK=L NMKQK= Ãã ! k·ãLâÖJÅã#$%&#*#%+, -. !*# NMKRK= NMKSK= #$%& *+& 012345678 .#$%&*+,-./0 1$%#234 NNK= NNKNK=NNKOK= NNKPK= Rsrv#$% +,-./012 NRO #$% +,-./0/12`kQN =EqRF= !# $%&*+ NNKQK= VwtNOKNK= NOKOK=NOKPK= EptNF EibaF NOKQK= Nokrk `ççäáåÖ EÉ~íáåÖNMK Nknk Nkqk #$%&!*+ Sknk Skok TK= Ukok Ukpk Ukqk Vkok NMK= NMKOK= #$%&*+QMã NMKPK=L NMKQK= #$%&#*#%+, -. !*# NMKRK= NMKSK= #$%& *+& 012345678 .#$%&*+,-./0 1$%#234 NNK= NNKOK= NNKPK= #$% +,-./012 NRO #$#%&* +,-./0123456 =EqRF= !# $%&*+ NNKQK= NOK= NOKPK= EptNF EibaF NOKQK= Nokrk WT02922X02