2. Combination with indoor units
The indoor units connectable to this unit are shown below.
Outdoor unit model | Total capacity of | Quantity of connectable |
|
|
|
connected indoor unit |
| Model name of connectable indoor unit |
| ||
name | models | indoor unit |
|
|
|
|
|
|
|
| |
|
|
|
|
| |
300 to 780 |
| PLFY- P32 · 40 · 50 · 63 · 80 · 100 · 125 | VKM | ||
| PLFY- P20 · 25 · 32 · 40 · 50 · 63 · 80 · 100 · 125 | VLMD | |||
|
|
| |||
325 to 845 |
| PEFY- P20 · 25 · 32 · 40 · 50 · 63 · 80 · 100 · 125 | VM | ||
| PDFY- P20 · 25 | · 32 · 40 · 50 · 63 · 71 · 80 · 100 · 125 VM | |||
|
|
| |||
|
| 3 to 32 | PCFY- P40 · 63 | · 100 · 125 | VGM |
|
| ||||
350 to 910 |
| PKFY- P20 · 25 |
| VAM | |
|
|
| PKFY- P32 · 40 | · 50 | VGM |
375 to 975 |
| PFFY- P25 · 32 · 40 · 50 · 63 | VLEM | ||
| PFFY- P25 · 32 · 40 · 50 · 63 | VLRM | |||
|
|
| |||
|
|
|
|
|
|
Note:
1.The total capacity of connected indoor unit models represents the total sum of the figures expressed in the indoor model name.
2.Combinations in which the total capacity of the connected indoor units exceeds the capacity of the outdoor unit will reduce the capacity of each indoor unit below the rated capacity during simultaneous operation. Therefore, if circumstances allows, combine indoor units within the capacity of the outdoor unit
3.A transmission booster (RP) is required when the number of connected indoor unit models in a cooling system exceeds the number of models specified in the chart below.
*The maximum number of units that can be controlled is determined by the indoor unit model, the type of remote controller and their capabilities.
| Remote controller type | Remote controller | |
(*1) |
|
|
|
Capability of the | Number of connected indoor units that can be | Prior to Ver. E | After Ver. F |
connected indoor units | connected without a RP. |
|
|
| 200 or lower | 16 (32) | 20 (40) |
| 200 or higher | 16 (32) | 16 (32) |
The number of indoor units and the total number of remote controllers is displayed within the parenthesis ( ).
*1 If even one unit that is higher than 200 exists in the cooling system, the maximum capacity will be “200 or higher”.
3. Confirmation of parts attached
This outdoor unit is attached with the parts below. Please check the quantity for each item.
| Name | 1 Conduit mounting plate | 2 Conduit mounting plate | 3 Conduit mounting plate | 4 Tapping screw M4 ⋅ 12 | |
|
| ø 40 | ø 33 | ø 27 |
| |
| Shape |
|
|
|
| |
name | 1 | 1 | 1 | 4 | ||
Model | ||||||
|
|
|
| |||
|
|
|
|
| ||
| Name | 5 Oil balance pipe | 6 Connecting pipe | 7 Packing | 8 Seal | |
| Shape |
|
|
|
| |
|
|
|
| insideø 23 outsideø 35 |
| |
name | 1 | 1 | 1 | 2 | ||
Model | ||||||
|
|
|
| |||
|
|
|
|
| ||
|
|
|
| *6 Connecting pipe is fixed with the unit. |
ENGLISH
5