10.5.Distributor (gas) connection method

Taking out piping from the front direction

(1)Remove the copper cap and rubber packing attached to the pip- ing and flange of the distributor (gas) (optional).

(2)Assemble outside the unit with the elbow (8) in the specified shape and braze. (see Fig. 1.)

For the 600 type, braze the connecting pipe (7) also.

Brazing

8Elbow

Taking out piping in the downward direction

(1)Remove the copper cap and rubber packing attached to the pip- ing and flange of the distributor (gas) (optional).

(2)Assemble outside the unit with the elbow (8), connecting pipe (7 for 600 type), or connecting pipe (6 for types other than 600) in the specified shape and braze. (see Fig. 4.)

Brazing

 

 

Brazing

8Elbow

 

 

 

 

For 600

: 7Connecting pipe

 

For other than 600

: 6Connecting pipe

8Elbow

7Connecting pipe

Fig. 4

Fig. 1

(3)Braze the connecting pipe (4) and piping assembled in step (2) to the distributor (gas) so that the connecting pipe is attached as shown in Fig. 2. For assembly procedure, see Fig. 3. When braz- ing piping, cool the brazed portion of the distributor side piping with a dampened waste cloth to prevent heating by brazing.

Flange

4Connecting pipe

Distributor (gas)

Elbow assembly

Fastening plate

Fig. 2

4Connecting pipe

Flange

Fastening plate

Distributor (gas)

Fig. 3

(4)Connect the ø 12.7 oil balance pipe to the ball valve of the vari- able capacity unit (oil balance) and constant capacity unit.

(5)Connect the ø 15.88 piping branched by the distributor (liquid) to the ball valve of the variable capacity unit (liquid side).

(6)Insert the distributor (gas) into the variable capacity unit and con- nect to the flange of the ball valve (gas side). (Use a socket wrench and socket wrench extension.) When doing so, be sure to mount the included packing between the ball valve (gas side) and flange of the distributor.

(7)Fasten the plate of the distributor (gas) to the frame of the unit with screws.

(8)Connect and braze the ø 44.45 (ø 38.1 for 600 type) gas piping (main pipe) and ø 28.58 gas pipe that connects the constant ca- pacity unit with the distributor (gas).

(3)Braze the connecting pipe (5) and connecting piping assembled in step (2) to the distributor (gas) outside the unit. For assembly procedure, see Fig. 5. When brazing piping, cool the brazed por- tion of the distributor side piping with a dampened waste cloth to prevent heating by brazing.

ENGLISH

5Connecting pile

Flange

Fastening plate

Distributor (gas)

Fig. 5

The rest of the procedure is the same as for “Running piping from front direction”.

Caution:

When brazing, cool with a waste cloth dampened with water so that the flange and ends of the distributor side piping don’t get heated.

- Part could be damaged if not cooled sufficiently.

19

Image 19
Contents PUHY-YMC Contents Before installation and electric work Safety precautionsBefore getting installed Before starting the test run Before getting installed moved electrical workConfirmation of parts attached Combination with indoor unitsVariable capacity unit Constant capacity unit Outdoor unit configurationSelection of installation site Model Name Connecting pipe Elbow ShapeSpace required around unit Individual installationWhen inlet air enters from right and left sides of unit When there is an obstruction above the unitCollective installation and continu- ous installation Lifting method and weight of productBe very careful to carry product Location of anchor bolt Installation of unitInstallation Example of collective installationNoise level Connecting direction for refrigerant pipingDown piping and down wiring precautions 60/61 dB A-weightedPUHN-200/250YMC Snow and seasonal windCountermeasure to seasonal wind PUHY-400/500YMCAreas of caution Refrigerant piping installationNever perform a pump down. This will damage the compressor + α Refrigerant piping systemMultiple line/header For variable capacity unit Precautions concerning piping connection and valve operationFigure shows valve fully open Gas side Liquid side Oil balance side60 to 50 to 57.5 / 500 to75 to 750 to 100 to 1000 to Tightening angle standard Pipe diameter mmOil balance pipe connection method Part could be damaged if not cooled sufficiently Distributor gas connection methodGram below How to install branch pipeJoint Restrictions on the posture for attaching jointsAirtight test Airtight test and evacuationEvacuation Thermal insulation of refrigerant piping No heat insulation must be provided for electric wiresInner wall concealed Floor fireproofing PenetrationsElectrical work Variable capacity unit Control box and connecting posi- tion of wiringConstant capacity unit Transmission booster optional For details, see item 11.3. Wiring transmission cablesPlate HoleName, code and possible unit connections Wiring transmission cablesConnecting a transmission booster Wiring examplesWithin Address Unit Remote control operation Same as above Wiring method, address settingRemote control RC terminal block TB6 One remote control unit for each indoor unitFor details, see wire connection example C Main remote controller Wiring LineSame group to the remote control RC terminal block TB6 Unit Range Setting methodExtended length and the length to the most remote unit Booster RP WiringCapability Number of connected indoor units that can be Wiring of main power supply and equipment capacity Test run method Operation procedureTest run Checking before getting test runAbnormality How to cope with test run abnormalityFlag 8 always lights 6603 Transmission error Transmission route Busy ErrorPower on Display at LED lighting blinking Remarks Flag Relay outputCoping with remote controller abnormality Following phenomena do not represent abnormality emergency NMK Nkok NknkNkqk NKPK#$%&*+#$%&*+#,%&- ./0123145&6789#$%&=?@. !# Sknk #$% +,-.Ü SkokUknk TK=Ukok Ukpk Ukqk Vkok Nmknk = NMK=$%&*+,-./01 NMKOK=#$%&*+QMã NMKPK=L Ãã ! k·ãLâÖJÅã NMKQK=#$%&#*#%+, -. !*# NMKRK= NMKSK= #$%& *+& 012345678 .#$%&*+,-./0 1$%#234 NNKNK= NNK=NNKOK= Rsrv NNKPK=#$% +,-./012 NRO #$% +,-./0/12`kQN =EqRF= !# $%&*+ Vwt NNKQK=NOKOK= NOKNK=NOKPK= EptNF EibaF NOKQK= `ççäáåÖ EÉ~íáåÖ NokrkNMK Nknk Nkqk #$%&!*+ Sknk Skok TK= Ukok Ukpk Ukqk Vkok NMK= NMKOK= #$%&*+QMã NMKPK=L NMKQK= #$%&#*#%+, -. !*# NMKRK= NMKSK= #$%& *+& 012345678 .#$%&*+,-./0 1$%#234 NNK= NNKOK= NNKPK= #$% +,-./012 NRO #$#%&* +,-./0123456 =EqRF= !# $%&*+ NNKQK= NOK= NOKPK= EptNF EibaF NOKQK= Nokrk WT02922X02