Mitsubishi Electronics PKH24FL, PKH36FL, PKH30FL, PKH18FL service manual Cooling Operation

Page 21

COOLING OPERATION

COOL operation

Four-way valve/OFF

NO

Initial

w 8

COOLING

YES

 

Vane initial

 

setting

NO

 

Vane

 

55 deg downward angle

 

 

70 deg downward angle

 

NO

YES

 

Fan speed

 

 

 

 

LOW

 

NO

YES

 

Downward discharge

 

 

 

 

1 hour

 

 

YES

Vane setting notch

Vane horizontal

airflow

 

w9

Compressor YES thermostat ON

NO

Allowance cancel

NO

YES

3-minute

 

 

 

 

 

 

 

 

time delay

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

YES

6-minute

 

 

 

Allowance

YES

 

 

 

time delay

 

 

 

period

 

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

6 minute

 

 

 

NO

3-minute

 

 

 

 

 

 

 

 

 

time delay

 

 

 

 

compressor operation

 

 

 

 

 

 

 

 

YES

 

 

 

Allowance set

 

Coil frost protection

 

 

 

 

 

 

 

 

 

 

w 10

YES

 

 

 

 

 

 

 

Coil frost

 

 

 

 

 

 

 

protection

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

w 11

 

NO

 

 

 

 

 

 

 

Cooling area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

NO

10-minute

 

Indoor coil

NO

NO

 

 

 

 

compressor operation

 

1 min continue

 

 

 

YES

 

temperature is 50˚F

 

 

 

 

 

 

or higher

 

 

YES

 

 

 

Allowance cancel

 

YES

 

 

 

 

 

 

 

 

FAN speed

 

 

 

 

 

 

 

 

 

 

 

Coil frost

YES

Defrosting

NO

 

LOW

 

 

 

 

 

 

 

 

protection detection

 

 

 

 

 

 

prevention

 

temperature 30˚F

 

 

FAN speed

YES

 

 

NO

 

or lower

 

 

 

 

 

YES

 

 

LOW 5 min elapse

 

 

 

16-minute

 

 

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

 

 

compressor operation

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

6-minute

3-minute

 

 

 

YES

 

 

trouble

 

 

 

time delay

time delay

 

 

 

Indoor pipe

YES

 

 

 

 

 

 

 

 

 

 

 

temperature is 34˚F

 

 

 

 

 

 

 

 

or lower

 

 

 

 

 

 

 

 

NO

Coil frost

Coil frost

 

 

 

 

 

 

 

prevention

prevention release

 

 

 

 

Compressor ON

Compressor OFF

1

w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes during auto vane SWING, the auto vane will continue to swing.

w9 When operating TEST RUN, the thermostat will be continuously ON.

w10 After 3 minute compressor operation, if the indoor coil thermistor reads 5°F or below for 3 minutes, the compressor will stop for 6 minutes.

w11Heating area : Indoor coil temperature is more than 9 degrees above the room temperature. Cooling area : Indoor coil temperature is more than 9 degrees below the room temperature. FAN area : Indoor coil temperature is within 9 degrees either way of the room temperature.

21

Image 21
Contents Revised EDITION-A ContentsFeatures Part Names and Functions Models PKH18FL, PKH24FL, PKH30FL, PKH36FL SpecificationsModels PKH18FL, PKH24FL, PKH30FL, PKH36FL Performance Data DataHeating Capacity Performance Curve PKH18FLPKH24FL PKH36FL PKH18FL Cooling Mode Heating ModeCondensing Pressure and Suction Pressure Indoor DB temperature F 80 psi.G Pressure Suction PKH24FL Cooling ModePKH30FL Cooling Mode PKH36FL Cooling Mode SHF PKH18FL PKH24FL PKH30FL PKH36FL Standard Operation DataOperating Range Outlet AIR Speed and Coverage RangeWith wind baffle D.B F if no wind baffle PKH30FL Noise Criterion CurvesPKH36FL Band Center FREQUENCIES, HzOutlines PKH24FLUnit inch Inch PKH36FL PKH30FLRefrigerant System Diagram Wireless Remote ControllerPKH18FL PKH24FL PKH30FL PKH36FL Models PKH18FL, PKH24FL, PKH30FL, PKH36FL Wiring Diagram Wiring DiagramMain Operation Operation FLOW-CHARTCooling Operation YES DRY OperationYES FAN Speed no Heating OperationOutline of Microprocessor Control Microprocessor ControlHow to operate Cool operation time chartIndoor Unit Control Cool operationStart condition Compressor controlCoil frost protection Termination conditionsAuto Return Auto vane controlDetecting abnormalities in the outdoor unit DRY operation DRY operation time chart How to operateFan control in DRY operation Heat operation time chart How to operate Heat operationDisplay in Heat operation Overheat protection Booster heater controlOverheat prevention Defrosting operation Indoor coil temperature abnormality detectionInitial mode Mode changeTemperature range Auto vane control COOL/DRY operationAuto return Timer operation Timer functionTest run Before emergency operation Emergency operationOn remote controller board On indoor controller board Dip switch and jumper connector functionsIndoor FAN Control Model No Wireless remote controller pair number setting operationSelf-check TroubleshootingOther Troubles and Causes Between remote controller and indoor unit Wrong Wiring on SiteCheck points HOW to Check the PartsOperating Procedure PHOTOS&ILLUSTRATION Disassembly ProcedureIndoor unit PKH24FL PhotoRemoving the vane motor Removing the intake grillesRemoving the drain pan Operating Procedure Photos Removing the line flow fan and the fan motorRemoving the electrical heater Electrical Parts PKH18FL PKH24FL PKH30FL PKH36FL Parts ListT7W E13 Qty / set Wiring Parts No Parts Name SpecificationsT7W E14 R01 12G 621PKH24FL PKH30FL PKH36FL Structural PartsPage Distributed in Dec No.OC276 New publication, effective Nov Specifications are subject to change without notice