Mitsubishi Electronics PKH30FL, PKH36FL, PKH24FL, PKH18FL service manual Other Troubles and Causes

Page 42

2. OTHER TROUBLES AND CAUSES

Auto vanes do not work.

 

 

 

 

Auto vane motor does not work.

 

 

 

 

 

 

 

 

 

 

 

Connector is poorly connected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto vane motor is poorly assembled.

 

 

 

 

 

 

 

 

 

Indoor controller board is damaged.

 

 

 

 

Auto vane motor is damaged. Auto vane motor relay is damaged.

Unit stops after 5 to

Protection function is working.

Refer to check code on remote controller display.

20 seconds operation

 

 

Power ON/OFF button is not available.

Indoor/outdoor connecting wire is connected incorrectly.

Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Defroster is broken.

Remote controller is damaged. Transmission wire is poorly connected

Transmission wire is damaged. Connector is poorly connected.

Check

Diagnosis of malfunction

 

Cause

 

 

Check points

code

 

 

 

 

 

 

 

 

 

1

Abnormality of room temper-

1)

Bad contact of thermistor

1)

Check the thermistor.

 

ature thermistor (RT1)

2)

Damaged thermistor

2) Measure the resistance of the thermistor.

 

 

 

 

 

Normal resistance should be as follows.

 

 

 

 

 

32°F····15kΩ

86°F·····4.3kΩ

 

 

 

 

 

50°F······9.6kΩ 104°F·····3.0kΩ

 

 

 

 

 

68°F······6.3kΩ

 

2

Abnormality of indoor coil

 

 

 

 

 

 

 

If the resistance is normal, replace the indoor

 

thermistor (RT2)

 

 

 

controller board.

 

 

 

 

 

 

 

 

 

 

4

Abnormality of drain sensor

1) Bad contact of transmission

1)

Check the connector.

 

 

 

wire

2)

Measure the resistance of the thermistor

 

 

2)

Damaged thermistor

 

(between - of CN50).

 

 

 

 

 

As for the normal resistance, refer to the case

 

 

 

 

 

of 1.

 

 

 

 

 

If the resistance is normal, replace the indoor con-

 

 

 

 

troller board.

 

 

 

 

 

 

5

Malfunction of drain pump

1)

Malfunction of drain pump

1) Check the drain pump.

 

 

2)

Damaged drain sensor

2) Check the drain sensor.

 

 

 

 

 

Check the drain sensor heater. Normal resis-

 

 

 

 

 

tance should be 82Ω . (between 1 - 3of

 

 

 

 

 

CN50).

 

 

 

 

 

If the resistance is normal, replace the indoor con-

 

 

 

 

troller board.

 

 

 

 

 

 

 

6

Coil frost protection is work-

1)

Short cycle of air cycle

1)

Clear obstructions from the air cycle.

 

ing.

2)

Dirty air filter

2)

Clean the air filter

 

 

3)

Damaged fan

3)

Check the fan.

 

 

 

4) Abnormal refrigerant

4)

Check the refrigerant temperature.

 

 

 

 

 

8

Abnormality in outdoor unit

1) Wrong wiring of indoor/outdoor

1)

Check the indoor/outdoor connecting wire.

 

 

 

connecting wire

2)

Change the connection of electric wiring.

 

 

2)

Reversed phase

3)

Check the protection device.

 

 

3)

Protection device is working

4)

Measure the resistance of the outdoor coil ther-

 

 

4) Damaged outdoor coil thermis-

 

mistor. If the resistance is normal, replace the

 

 

 

tor

 

outdoor controller board.

 

 

 

 

 

 

 

The number of check code shows times of Buzzer sound.

42

Image 42
Contents Contents Revised EDITION-AFeatures Part Names and Functions Specifications Models PKH18FL, PKH24FL, PKH30FL, PKH36FLData Models PKH18FL, PKH24FL, PKH30FL, PKH36FL Performance DataHeating Capacity Performance Curve PKH18FLPKH24FL PKH36FL PKH18FL Cooling Mode Heating ModeCondensing Pressure and Suction Pressure PKH24FL Cooling Mode Indoor DB temperature F 80 psi.G Pressure SuctionPKH30FL Cooling Mode PKH36FL Cooling Mode Standard Operation Data SHF PKH18FL PKH24FL PKH30FL PKH36FLOperating Range Outlet AIR Speed and Coverage RangeWith wind baffle D.B F if no wind baffle PKH36FL Noise Criterion CurvesPKH30FL Band Center FREQUENCIES, HzOutlines PKH24FLUnit inch PKH36FL PKH30FL InchRefrigerant System Diagram Wireless Remote ControllerPKH18FL PKH24FL PKH30FL PKH36FL Wiring Diagram Models PKH18FL, PKH24FL, PKH30FL, PKH36FL Wiring DiagramOperation FLOW-CHART Main OperationCooling Operation DRY Operation YESHeating Operation YES FAN Speed noMicroprocessor Control Outline of Microprocessor ControlIndoor Unit Control Cool operation time chartHow to operate Cool operationCoil frost protection Compressor controlStart condition Termination conditionsAuto vane control Auto ReturnDetecting abnormalities in the outdoor unit DRY operation time chart How to operate DRY operationFan control in DRY operation Heat operation time chart How to operate Heat operationDisplay in Heat operation Overheat protection Booster heater controlOverheat prevention Indoor coil temperature abnormality detection Defrosting operationInitial mode Mode changeTemperature range Auto vane control COOL/DRY operationAuto return Timer operation Timer functionTest run Emergency operation Before emergency operationDip switch and jumper connector functions On remote controller board On indoor controller board Indoor FAN Control Wireless remote controller pair number setting operation Model NoTroubleshooting Self-checkOther Troubles and Causes Wrong Wiring on Site Between remote controller and indoor unitHOW to Check the Parts Check pointsIndoor unit PKH24FL Disassembly ProcedureOperating Procedure PHOTOS&ILLUSTRATION PhotoRemoving the vane motor Removing the intake grillesRemoving the drain pan Operating Procedure Photos Removing the line flow fan and the fan motorRemoving the electrical heater Parts List Electrical Parts PKH18FL PKH24FL PKH30FL PKH36FLT7W E14 Qty / set Wiring Parts No Parts Name SpecificationsT7W E13 R01 12G 621Structural Parts PKH24FL PKH30FL PKH36FLPage Distributed in Dec No.OC276 New publication, effective Nov Specifications are subject to change without notice