Mitsubishi Electronics PKH18FL Wrong Wiring on Site, Between remote controller and indoor unit

Page 43

3. WRONG WIRING ON SITE

3-1 Between remote controller and indoor unit

If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.

3-2 Phenomenon due to wrong wiring between indoor and outdoor units

Wrong wiring

 

Mode

Thermostat

Phenomenon

 

 

 

 

 

 

 

 

OFF

Operation stops.

Indoor

Outdoor

COOL

 

 

ON

4-Way valve turns ON. 9 minutes later, check code “P8” appears

1

1

 

 

on remote controller display.

2

2

 

 

 

OFF

Cooling operation. Several minutes later, check code “P8” appears

3

3

 

 

on remote controller display.

HEAT

 

 

 

ON

Normal operation until first thermostat OFF.

 

 

 

 

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops, 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Outdoor unit stops.

Indoor

Outdoor

COOL

 

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

1

1

 

 

remote controller display.

2

2

 

 

 

 

 

 

OFF

Operation stops.

3

3

 

HEAT

 

 

 

 

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

Disconnection between 1 and 1 or 2

 

OFF

Operation stops.

COOL

 

 

and 2.

 

ON

Operation stops. 9 minutes later, check code “P8” appears on

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

OFF

Operation stops. 4-way valve turns OFF.

 

 

HEAT

 

 

 

 

ON

27 minutes later, check code “P8” appears on remote controller

 

 

 

 

 

 

display.

 

 

 

 

 

 

 

 

 

Disconnection between 3 and 3.

COOL

Normal operation.

 

 

 

 

 

 

 

 

 

 

 

OFF

Operation stops. 4-way valve turns OFF.

 

 

HEAT

 

 

 

 

ON

Operation stops. 27 minutes later, check code “P8” appears on

 

 

 

 

 

 

remote controller display.

 

 

 

 

 

 

 

 

 

43

Image 43
Contents Revised EDITION-A ContentsFeatures Part Names and Functions Models PKH18FL, PKH24FL, PKH30FL, PKH36FL SpecificationsModels PKH18FL, PKH24FL, PKH30FL, PKH36FL Performance Data DataHeating Capacity PKH18FL Performance CurvePKH24FL PKH36FL Heating Mode PKH18FL Cooling ModeCondensing Pressure and Suction Pressure Indoor DB temperature F 80 psi.G Pressure Suction PKH24FL Cooling ModePKH30FL Cooling Mode PKH36FL Cooling Mode SHF PKH18FL PKH24FL PKH30FL PKH36FL Standard Operation DataOutlet AIR Speed and Coverage Range Operating RangeWith wind baffle D.B F if no wind baffle Band Center FREQUENCIES, Hz Noise Criterion CurvesPKH30FL PKH36FLPKH24FL OutlinesUnit inch Inch PKH36FL PKH30FLWireless Remote Controller Refrigerant System DiagramPKH18FL PKH24FL PKH30FL PKH36FL Models PKH18FL, PKH24FL, PKH30FL, PKH36FL Wiring Diagram Wiring DiagramMain Operation Operation FLOW-CHARTCooling Operation YES DRY OperationYES FAN Speed no Heating OperationOutline of Microprocessor Control Microprocessor ControlCool operation Cool operation time chartHow to operate Indoor Unit ControlTermination conditions Compressor controlStart condition Coil frost protectionAuto Return Auto vane controlDetecting abnormalities in the outdoor unit DRY operation DRY operation time chart How to operateFan control in DRY operation Heat operation Heat operation time chart How to operateDisplay in Heat operation Booster heater control Overheat protectionOverheat prevention Defrosting operation Indoor coil temperature abnormality detectionMode change Initial modeTemperature range COOL/DRY operation Auto vane controlAuto return Timer function Timer operationTest run Before emergency operation Emergency operationOn remote controller board On indoor controller board Dip switch and jumper connector functionsIndoor FAN Control Model No Wireless remote controller pair number setting operationSelf-check TroubleshootingOther Troubles and Causes Between remote controller and indoor unit Wrong Wiring on SiteCheck points HOW to Check the PartsPhoto Disassembly ProcedureOperating Procedure PHOTOS&ILLUSTRATION Indoor unit PKH24FLRemoving the intake grilles Removing the vane motorRemoving the drain pan Removing the line flow fan and the fan motor Operating Procedure PhotosRemoving the electrical heater Electrical Parts PKH18FL PKH24FL PKH30FL PKH36FL Parts ListR01 12G 621 Qty / set Wiring Parts No Parts Name SpecificationsT7W E13 T7W E14PKH24FL PKH30FL PKH36FL Structural PartsPage Distributed in Dec No.OC276 New publication, effective Nov Specifications are subject to change without notice