2-6 TIMER operation
COOL | ˚F |
| |
| STOP PM |
| FAN |
| SWING |
| START AM |
ON/OFF TEMP
| FAN | AUTO STOP |
MODE | VANE | AUTO START |
CHECK | LOUVER | h |
TEST RUN |
| min |
SET | RESET CLOCK |
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1Push POWER ON/OFF button.
2Check if or not the current time is correct.
3Push the or button and select the desired time.
4 Set the timer time using HR and MIN buttons.
2-7 Test run
6
3
2
COOL | TEST |
| RUN |
FAN |
|
ON/OFF | TEMP |
| FAN | AUTO STOP |
MODE | VANE | AUTO START |
CHECK | LOUVER | h |
TEST RUN |
| min |
SET | RESET CLOCK |
A
4
5
Test run
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M".
1Turn on the main power to the unit.
2Press the TEST RUN button twice continuously.
(Start this operation from the status of remote controller display turned off.)
ATEST RUN and current operation mode are displayed.
3Press the MODE ( ) button to activate COOL mode, then
check whether cool air is blown out from the unit.
FAN
4 Press the button and check whether strong air is blown out from the unit.
5Press the VANE button and check whether the auto vane operates properly.
6Press the ON/OFF button to stop the test run.
Note:
•Point the remote controller towards the indoor unit receiver while following steps 2 to 6.
•It is not possible to run the in FAN, DRY or AUTO mode.
36