SECTION 1: SPECIFICATION INFORMATION
JFT-S L-R & R-L LEGEND & EXHAUST FAN DIMENSIONS
Legend
1 -
2 - Electrical Connection - See Table for Amp Draw 3 - 3/4" NPT Incoming Water Connection
4 -
5 - 3/4" NPT Wash Section Condensate Return
6 - 3/4" NPT Power Rinse Section Condensate Return
7 - 3/4" NPT Booster Heater Condensate Return
8 - Condensate Connection - See Detail
Note:
The condensate removal system built into the dishmachine consists of a fan that will remove 1200 CFM. A single condensate connection must be provided by the installing contractor. This is an indirect connection that must be capable of removing 1200 CFM from the area.
| Condensate Exhaust Duct | |
18" [457mm] I.D. Square | Minimum 18" Square (Cross Section 324 Sq. In.) | |
Deep | Provided by HVAC Contractor | |
Exhaust Requirements | ||
| ||
3" [72mm] | - 1200 CFM | |
| ||
| Condensate duct to extended into duct pan. | |
| Condensate duct pan mounted on top of | |
| dishmachine electrical section. | |
|