INSTALLATION, OPERATION AND CARE OF
STOCKPOT RANGE
GENERAL
Stockpot ranges are designed for commercial use only and feature fast, efficient gas heat. Each burner is controlled by an adjustable gas valve.
Model | Number of Burners | BTU/hr Input Rating |
|
|
|
VSP100, WSPR1 | 2 | 110,000 |
|
|
|
VSP200, WSPR2 | 4 | 220,000 |
|
|
|
VSP200F, WSPR2F | 4 | 220,000 |
|
|
|
INSTALLATION
UNPACKING
Immediately after unpacking, check for possible shipping damage. If the stockpot is found to be damaged, save the packaging material and contact the carrier within 15 days of delivery.
Before installing, verify that the type of gas (natural or propane) and the clearance dimensions (see below) agree with the specifications on the rating plate which is located at the back of the stockpot.
LOCATION
The installation location must be kept free and clear of combustibles. Do not obstruct the flow of combustion and ventilation air. DO NOT install the stockpot adjacent to open burners or fryers.
Sufficient air should be allowed to enter the room to compensate for the amount of air removed by any ventilating system and for combustion of the gas burners. Do not obstruct the air flow into and around the appliance. Do not obstruct the flow of flue gases through and above the stockpot top grate. Position the stockpot in its final location. Check that there are sufficient clearances to service the stockpot and to make the required gas supply connection(s). Provide 24" clearance at the front for cleaning, maintenance, service and proper operation.
Minimum Clearance | Combustible Construction | |
Rear | 24” | 4” |
Sides | 18” | 0” |
- 3 -