VHX SERIES STEAMER - ELECTRICAL OPERATION
ELECTRICAL OPERATION
COMPONENT FUNCTION
CABINET BASE BOILER CONTROLS
Power Switch . . . . . . . . . . . . . . . .
Reset Switch (Manual) . . . . . . . . .
Boiler Fill Valve . . . . . . . . . . . . . . .
Cold Water Condenser
Valve . . . . . . . . . . . . . . . . . . . . . . .
Cold Water Condenser
Cycling Thermostat . . . . . . . . . . .
Cycling Pressure Switch . . . . . . .
High Limit Pressure Switch . . . . .
Main Water Level Control . . . . . .
Auxiliary Water Level Control . . .
Relay Board . . . . . . . . . . . . . . . . . .
Controls 120VAC to the boiler control circuit.
Resets the low water level safety circuit on initial startup or the occurrence of a low water condition. Also, resets the high pressure level safety circuit on initial startup or the occurrence of a high pressure condition which allows heating to start.
Allows water flow to the boiler when energized thru
Allows cold water to spray thru a nozzle inside the condenser drain box to condense steam and cool the hot water before discharging into the drain.
Regulates cold water spray inside the condenser drain box during a cooking cycle or boiler blowdown/drain.
Regulates boiler pressure between
Prevents boiler from reaching pressures above 15 PSI by removing power from heating circuit. The high limit automatically resets at approximately 12 psi (green ready light on).
A dual function control that allows water to fill and maintain the proper level in the boiler, providing differential level control; and removes power from heating circuit if water level drops too low, providing low level
A back up to the low level
Provides a centralized location for wire harness connections and power transfer thru board relays
NOTE: The relay’s below are mounted on the relay board and are individually replaceable.
K1 Relay | Energized when water level reaches the Aux LLCO probe (water level |
| condition satisfied). |
K2 Relay | Energized when high limit pressure switch is closed (high limit pressure |
| condition satisfied). When K1 & K2 are energized, ready light (green) will be |
| on. |
K3 Relay | Energized when K1(2) N.O. contacts close and reset switch is activated. |
| When K3 is energized, K3(2) N.O. contacts close and low water light turns |
| off. |
K4 Relay | Energized when K2(2) N.O. contacts are closed and reset switch is |
| activated. When K4 is energized, K4(2) N.O. contacts close and high |
| pressure light turns off. When K3 and K4 are energized, power is supplied to |
| auxiliary contactors A & C. |
F25154 (February 2004) |
| Page 24 of 48 |
|