Vulcan-Hart VHX24E service manual Cold Water Condenser Thermostat Adjustment

Page 21

VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS

3.To check boiler fill valve:

A.Verify 120VAC to solenoid valve coil.

B.If voltage is correct but valve is not opening (little or no water flow), turn power switch off and disconnect power to machine.

1)Remove lead wires from coil and check for continuity.

2)If no continuity is measured, install a replacement solenoid valve and check for proper operation.

3)If continuity is measured, the coil is good.

C.If voltage is not correct, check main water level control board as outlined under

WATER LEVEL CONTROLS TEST.

4.To check cold water condenser valve:

NOTE: Valve should energize only during cooking cycles and at boiler blowdown/drain.

A.Verify 120VAC to solenoid valve coil.

B.If voltage is correct but valve is not opening (little or no water flow), turn power switch off and disconnect power to machine.

1)Remove lead wires from coil and check for continuity.

2)If no continuity is measured, install a replacement solenoid valve and check for proper operation.

3)If continuity is measured, the coil is good. Continue with procedure for additional valve checks.

C.If voltage is not correct, check cold water condenser thermostat as outlined under

COLD WATER CONDENSER THERMOSTAT ADJUSTMENT.

5.To check valve ports for clogs or valve component malfunction, continue with procedure for disassembly and inspection of internal components.

6.Turn water supply off, disconnect water line from valve body then remove solenoid valve.

7.Remove coil assembly from valve stem

8.Secure the valve body to keep it from turning.

9.Scribe a line on stem nut to valve body for proper re-tightening then remove stem locking nut and remove the stem from valve body.

10.All parts are now accessible for inspection and cleaning.

NOTE: If internal solenoid parts appear to be damaged or worn, then replace the solenoid valve. Do not reuse damaged or worn parts. No internal solenoid parts are available as a service replacement.

A.Check rubber seal on bottom of plunger.

B.Check plunger spring.

C.Check O-ring in valve body.

D.Check ports in valve body.

11.Reverse procedure to install and check for proper operation.

COLD WATER CONDENSER THERMOSTAT ADJUSTMENT

During a cooking cycle or boiler blowdown/drain, the cold water condenser thermostat (N.O.) should close and energize the cold water condenser solenoid valve. The water from spray nozzle mixes with the drain water in the condenser drain box to reduce drain water temperature and condense steam vapors.

If excessive steam vapors are seen exiting the drain, adjust the cold water condenser thermostat as outlined below.

1.Turn power switch off and allow boiler to blowdown/drain.

2.Access cold water condenser thermostat as outlined under PRESSURE SWITCH CONTROL BOX COMPONENTS in REMOVAL AND REPLACEMENT OF PARTS.

3.Turn thermostat shaft fully counterclockwise to energize the cold water condenser solenoid valve.

A.Allow cold water to flow until condenser drain box has completely cooled.

B.Slowly turn thermostat shaft clockwise until thermostat opens and de-energizes the solenoid valve. Turn shaft an additional 1/4 turn to prevent the thermostat from closing near room ambient temperatures.

4.Check for proper operation.

Page 21 of 48

 

F25154 (February 2004)

 

Image 21
Contents VHX24E Shown VHX Boiler Base Series High Efficiency Electric SteamerTable of Contents VHX Series Steamers INSTALLATION, Operation Cleaning Introduction GeneralModel Number of Pans PAN Depth PER Compartment Inches Water Conditioning SpecificationsBoiler Code Descriptions Boiler PressureElectrical ToolsStandard SpecialPressure Switch Control BOX Components Removal and Replacement of PartsMain Control BOX Components Left Side View Shown Water Level Gauge AssemblyHeating Elements Heating Elements Heating Element Mounting PlateRight Side View Shown Boiler AssemblyDescaler Cathodic Protector Removal Cooking Compartment DoorsGasket HandleLatch Assembly Boiler Service Procedures and AdjustmentsWater Level Probe Housing Blowdown Water Level Controls TestMain Water Level Control Auxiliary Low level Cut-Off Control Cycling Pressure Switch Adjustment Boiler Fill and Cold Water Condenser Solenoid Valves High Limit Pressure Switch AdjustmentCold Water Condenser Thermostat Adjustment Intake Shut-Off Valve Adjustment Steam Flow Heating Element TestCooking Compartment Door Latch Adjustment Door Sealing AdjustmentElectrical Operation Reset Switch ManualComponent Function Cold Water CondenserCompartment Pressure Switch Blowdown/DrainSteam Solenoid Valve Boiler Base Controls Component LocationsBoiler Base Controls Cooking Compartment Controls Low Level Cut-Off & Differential Control Water Level ControlsAuxiliary Low Level Cut-Off Relay Board Layout, Legend & Diagnostic Test PointsSchematic Initial Fill and Preheat Sequence of OperationBoiler Blowdown/drain Water Refill After Initial FillVHX Series Steamer Electrical Operation Schematics Cooking Compartment Controls Wiring Diagrams VHX Series Steamer Electrical Operation Heating Element Circuits Cooking Compartment Controls Troubleshooting Symptom Possible CausesBoiler Base Controls Symptom Possible Causes Symptom Possible Causes Cooking Compartment Controls VHX Series Steamer VHX Series Steamer Condensed Spare Parts List VHX24E, VHX24E5, MHB24EPart Number Description