Greenheck Fan 470658 MSX manual Start-Up Blower

Page 16
Voltage, Hertz, Phase

Start-Up - Blower

2. Check the Blower Rotation

Refer to the Start-Up Checklist in the Reference section before proceeding further!

Pre Start-Up Check

Rotate the fan wheel by hand and make sure no parts are rubbing. Check the V-belt drive for proper alignment and tension (a guide for proper belt tension and alignment is provided in the Belt Maintenance section). Check fasteners, set screws and locking collars on the

Open the blower access door and run the blower momentarily to determine the rotation. Arrows are placed on the blower scroll to indicate the proper direction or reference the example shown to the right.

 

 

 

n

 

 

 

io

 

 

 

t

 

 

a

R

o

t

 

 

 

 

 

 

Blower

Housing

Blower Rotation

fan, bearings, drive, motor base, and accessories for tightness.

warning

Disconnect and lock-out all power and gas before performing any maintenance or service to the unit. Failure to due so could result in serious injury or death and damage to equipment.

SPECIAL EQUIPMENT REQUIRED

Required and recommended tools. Equivalent products may be used.

Voltage &

Manufacturer:

Fluke

Model:

177

Amperage

Phone:

1-800-44-FLUKE

Meter

www.fluke.com

 

 

 

 

 

 

 

Manufacturer:

Fluke

Thermometer

Model:

50

Phone:

1-800-44-FLUKE

 

 

www.fluke.com

 

Micro Amp

Manufacturer:

Fluke

Model:

116

Meter

Phone:

1-800-44-FLUKE

 

www.fluke.com

 

U-Tube

Manufacturer:

Dwyer

Model:

Slack Tube

Manometer

Phone:

1-219-897-8000

 

www.dwyer-inst.com

 

Manufacturer:

Monarch

Tachometer

Model:

Pocket Tach 100

Phone:

1-800-999-3390

 

 

www.monarchinstrument.com

Warning

Check the housing, blower, and ductwork for any foreign objects before running the blower.

1. Check the Voltage

Before starting the unit, compare the supplied voltage, hertz, and phase with the unit and motor’s nameplate information.

VOLTS

 

 

HZ

 

 

PH

 

SUP HP

 

 

EXH HP

 

 

 

 

 

 

MCA

 

 

 

MOP

 

 

 

 

 

 

 

 

 

Electrical Nameplate

Note

To reverse the rotation on three phase units, disconnect and lock-out the power, then interchange any two power leads.

Note

To reverse the rotation on single phase units, disconnect and lock-out the power, then rewire the motor per the manufacturer’s instructions.

Important

If the blower is rotating in the wrong direction, the unit will move some air, but will not perform as designed. Be sure to perform a visual inspection to guarantee the correct blower rotation.

3. Check for Vibration

Check for unusual noise, vibration or overheating of the bearings. Reference the Troubleshooting section for corrective actions.

Important

Excessive vibration may be experienced during the initial start-up. Left unchecked, it can cause a multitude of problems including structural and/or component failure.

Important

Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To minimize this undesirable effect, the use of heavy canvas duct connectors is recommended.

4. Motor Check

Measure the motor’s voltage, amps and RPM. Compare to the specifications. Motor amps can be reduced by lowering the motor RPM or increasing system static pressure.

Important

Additional starters and overloads may be provided in the make-up air control center for optional exhaust blowers. Any additional overloads must be checked for proper voltage, amps and RPMs.

16

Model MSX Make-Up Air

®

Image 16
Contents Installation, Operation and Maintenance Manual General Safety InformationInspection and Maintenance during Storage ReceivingUnpacking HandlingClearance to Combustibles / Service Clearances Table of ContentsInstallation of Indoor Unit Installation Arrangement DB / HZ / UB Installation of Roof Mounted Unit Arrangement DBC Install Curb/Equipment SupportsInstall Combination Extension Install Exhaust FanInstall Supply Unit Installation of Evaporative Cooling Module optional Locate Equipment SupportsSecure Cooling Module to Unit Set Evaporative Cooling ModuleInstallation of Electrical Wiring Installation of Electric Heater optional Sizing of Supply ConductorsInstallation Evaporative Cooler Piping optional Install the Water Supply LineInstall the Drain Line Check/Adjust Water LevelInstall the Drain Line Installation of Water WizardTM optional Install Normally Closed Supply Line/ SolenoidInstall Normally Open Drain Line/ Solenoid Wire the SolenoidsInstallation of Direct Expansion DX Coil Piping optional Installation of Chilled Water Coil Piping optional Verify Coil Hand DesignationCheck the Coil for Leaks Connect the Supply and Return LinesInstallation of Building Pressure Control optional Mount Pressure TapRun Pressure Tap Lines Set the Building PressureStart-Up Blower Air Volume Measurement & Check Set-Up Optional ComponentsStart-Up Electric Heater optional Set the Unit’s Operating TemperatureAirflow Interlock Start-Up Evaporative Cooling Recirculating optional Start-Up Water Wizard optional Adjust the Freeze Temperature Check Operation VAV Units optional Variable Volume OperationBuilding Pressure Control Building Pressure Control a Operation Electrical Exhaust Fan Contact S1 Closed optionalSupply Fan Contact S2 Closed Electric Heat Contact S4 Closed optionalOperation - Water Wizard optional Troubleshooting Blower Does Not OperateMotor Overamps Insufficient Airflow Too Much AirflowExcessive Noise or Vibration Electric Heater Does Not Operate optional Supply fan must be on for heater to operateEvaporative Cooler does not Operate Recirculating pump Water Blows through Evaporative CoolerAdjust the On Time Factor Adjust the Manual Supply ValveWater Wizard Improper Water Supply Maintenance Routine Belt DrivesSnow Accumulation MotorsFilters BearingsEvaporative Coolers Cooling Coils Chilled Water CoilsMaintenance Fall Winterizing Chilled Water CoilsBlowing-Out Coils Flushing CoilsReference Dirty Filter SwitchTypical Control Center Layout Start-Up Checklist Start-Up ChecklistStart-Up Evaporative Cooler optional refer Maintenance Log Warranty

470658 MSX specifications

The Greenheck Fan 470658 MSX is a premium performance ventilation solution designed to meet the needs of various commercial and industrial applications. Known for its robustness and efficient air movement capabilities, the MSX series is highly regarded in the industry for its innovative technologies and user-friendly features.

One of the standout features of the Greenheck Fan 470658 MSX is its advanced motor technology. It is equipped with an energy-efficient direct drive motor, which minimizes energy consumption while delivering high airflow rates. The motor's design allows for quieter operation, making it ideal for environments where noise reduction is crucial.

The aerodynamic design of the fan blades is another hallmark of the Greenheck MSX. The blades are engineered to enhance performance by maximizing airflow while reducing turbulence. This design optimization results in increased efficiency and lower operational costs over time. Furthermore, the fan is capable of handling a wide range of air volumes, making it versatile for various installation requirements.

Durability is a key characteristic of the Greenheck Fan 470658 MSX. Constructed from high-quality materials, it can withstand harsh environmental conditions, including exposure to moisture and corrosive elements. The fan housing is designed to be robust, ensuring long-lasting performance and minimal maintenance needs.

In addition to its physical attributes, the MSX series comes equipped with smart technology features. The fan can be integrated with building management systems for real-time monitoring and control, helping facility managers optimize energy usage and maintain indoor air quality. The inclusion of variable speed controls further enhances adaptability, allowing users to adjust fan speed according to specific ventilation needs.

Safety features are also a priority with the Greenheck Fan 470658 MSX. The unit is designed with built-in protections against overheating and overcurrent, ensuring reliable operation under demanding conditions. Additionally, the fan meets rigorous safety standards and certifications, instilling confidence in its performance.

With its combination of efficiency, durability, and innovative features, the Greenheck Fan 470658 MSX is a top choice for those seeking reliable ventilation solutions. Its ability to deliver consistent airflow while minimizing energy consumption sets it apart in the competitive market of industrial fans, making it a valuable investment for businesses looking to enhance their air management systems.