Greenheck Fan 470658 MSX manual Start-Up Water Wizard optional

Page 20

Start-Up - Water Wizard™ (optional)

L1

L2

L3

Function Key

 

Up Key

Enter Key

 

Down Key

Water Wizard™ User Interface

Key Function Description

1. Open the Solenoid

Confirm that the manual water supply valve is closed. Press and hold the Function Button

for one second. L3 will begin blinking (short on, long off), indicating that Flow Test Mode is active and the supply solenoid is open.

2. Set the Water Pressure

With the solenoid open, set the supply water pressure to the correct setting (see table below).

Use the manual supply valve to adjust the supply pressure. A pressure gauge is provided between the manual supply valve and the media.

warning

Opening the manual supply valve will allow water to pass to the media. Be sure the sump is safely draining before opening the manual supply valve.

NOTE

The manual supply valve ships closed and must be adjusted for proper performance.

Recommended Water Pressure Chart

Housing

Media Width

Water Pressure

Size

(inches)

(in. wc)

MSX-H12

30

20

MSX-H22

4334

36

60

61

 

 

 

 

MSX-H32

66

72

96*

42

 

 

 

 

MSX-H35

120*

61

 

 

 

MSX-H38

180*

37

MSX-H42

216*

51

 

 

 

*Multiple media sections. Values represent total media width.

NOTE

The recommended water pressure is based on media width. Refer to the table provided for proper water pressure settings.

3. Break-in Media

Leave the supply solenoid open to saturate and breakin media for 20 minutes with the blower off.

4. Close Solenoid

With the pressure set, press the Function Key for one second to deactivate Flow Test Mode

and allow the supply solenoid to close.

5. Check Media

Start the cooling cycle and check the media after one hour of operation. If the media is continuously dry or if too much water is draining from the sump tank, refer to Troubleshooting, Water Wizard™.

NOTE

Steps 6 through 8 are provided to adjust the minimum cooling temperature. The minimum cooling is preset to the factory recommended 75°F (24°C). Only adjust if needed.

NOTE

The inlet air sensor function overrides and shuts down the evaporative cooler if the outside temperature falls below the minimum cooling temperature.

6. Enter Program Mode

Press and hold

the Enter Key

for three seconds. The display will read “Pro” when Program Mode is active.

Program Display

7.Adjust the Minimum Cooling Temperature

While in the Program Menu, use the Up and Down Keys to navigate the Menu Options

until “toF” is

Minimum Cooling

displayed. Press the

Temperature Display

 

Enter Key to access the selected Menu Option setting.

Use the Up and Down Keys to adjust the Minimum Cooling Temperature as needed. Press the Enter Key to save the Minimum Cooling Temperature setting and return to the Program Menu.

NOTE

The enter key must be pressed to save the new minimum cooling temperature.

8. Exit Program Mode

After 15 seconds of idle time the controller will exit Program Mode.

20

Model MSX Make-Up Air

®

Image 20
Contents Installation, Operation and Maintenance Manual General Safety InformationInspection and Maintenance during Storage ReceivingUnpacking HandlingInstallation of Indoor Unit Table of ContentsClearance to Combustibles / Service Clearances Installation Arrangement DB / HZ / UB Installation of Roof Mounted Unit Arrangement DBC Install Curb/Equipment SupportsInstall Combination Extension Install Exhaust FanInstall Supply Unit Installation of Evaporative Cooling Module optional Locate Equipment SupportsSecure Cooling Module to Unit Set Evaporative Cooling ModuleInstallation of Electrical Wiring Installation of Electric Heater optional Sizing of Supply ConductorsInstallation Evaporative Cooler Piping optional Install the Water Supply LineInstall the Drain Line Check/Adjust Water LevelInstall the Drain Line Installation of Water WizardTM optional Install Normally Closed Supply Line/ SolenoidInstall Normally Open Drain Line/ Solenoid Wire the SolenoidsInstallation of Direct Expansion DX Coil Piping optional Installation of Chilled Water Coil Piping optional Verify Coil Hand DesignationCheck the Coil for Leaks Connect the Supply and Return LinesInstallation of Building Pressure Control optional Mount Pressure TapRun Pressure Tap Lines Set the Building PressureStart-Up Blower Air Volume Measurement & Check Set-Up Optional ComponentsAirflow Interlock Set the Unit’s Operating TemperatureStart-Up Electric Heater optional Start-Up Evaporative Cooling Recirculating optional Start-Up Water Wizard optional Adjust the Freeze Temperature Building Pressure Control Variable Volume OperationCheck Operation VAV Units optional Building Pressure Control a Operation Electrical Exhaust Fan Contact S1 Closed optionalSupply Fan Contact S2 Closed Electric Heat Contact S4 Closed optionalOperation - Water Wizard optional Troubleshooting Blower Does Not OperateMotor Overamps Insufficient Airflow Too Much AirflowExcessive Noise or Vibration Electric Heater Does Not Operate optional Supply fan must be on for heater to operateEvaporative Cooler does not Operate Recirculating pump Water Blows through Evaporative CoolerWater Wizard Improper Water Supply Adjust the Manual Supply ValveAdjust the On Time Factor Maintenance Routine Belt DrivesSnow Accumulation MotorsEvaporative Coolers BearingsFilters Cooling Coils Chilled Water CoilsMaintenance Fall Winterizing Chilled Water CoilsBlowing-Out Coils Flushing CoilsTypical Control Center Layout Dirty Filter SwitchReference Start-Up Evaporative Cooler optional refer Start-Up ChecklistStart-Up Checklist Maintenance Log Warranty

470658 MSX specifications

The Greenheck Fan 470658 MSX is a premium performance ventilation solution designed to meet the needs of various commercial and industrial applications. Known for its robustness and efficient air movement capabilities, the MSX series is highly regarded in the industry for its innovative technologies and user-friendly features.

One of the standout features of the Greenheck Fan 470658 MSX is its advanced motor technology. It is equipped with an energy-efficient direct drive motor, which minimizes energy consumption while delivering high airflow rates. The motor's design allows for quieter operation, making it ideal for environments where noise reduction is crucial.

The aerodynamic design of the fan blades is another hallmark of the Greenheck MSX. The blades are engineered to enhance performance by maximizing airflow while reducing turbulence. This design optimization results in increased efficiency and lower operational costs over time. Furthermore, the fan is capable of handling a wide range of air volumes, making it versatile for various installation requirements.

Durability is a key characteristic of the Greenheck Fan 470658 MSX. Constructed from high-quality materials, it can withstand harsh environmental conditions, including exposure to moisture and corrosive elements. The fan housing is designed to be robust, ensuring long-lasting performance and minimal maintenance needs.

In addition to its physical attributes, the MSX series comes equipped with smart technology features. The fan can be integrated with building management systems for real-time monitoring and control, helping facility managers optimize energy usage and maintain indoor air quality. The inclusion of variable speed controls further enhances adaptability, allowing users to adjust fan speed according to specific ventilation needs.

Safety features are also a priority with the Greenheck Fan 470658 MSX. The unit is designed with built-in protections against overheating and overcurrent, ensuring reliable operation under demanding conditions. Additionally, the fan meets rigorous safety standards and certifications, instilling confidence in its performance.

With its combination of efficiency, durability, and innovative features, the Greenheck Fan 470658 MSX is a top choice for those seeking reliable ventilation solutions. Its ability to deliver consistent airflow while minimizing energy consumption sets it apart in the competitive market of industrial fans, making it a valuable investment for businesses looking to enhance their air management systems.