hussman RGSSFP manual Installing Condensate Drain, Refrigerant Type, Refrigeration Lines

Page 4

INSTALLING CONDENSATE DRAIN

Poorly or improperly installed condensate drains can se- riously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:

1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.

2.When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumb- ing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe section. Never use two water seals in series in any one line. Double P-traps in series will cause a lock and prevent draining.

3.Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to main- tain the 1/8" pitch and to prevent warping.

4.Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.

5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.

6.Prevent condensate drains from freezing:

a.Do not install condensate drains in contact with non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.

b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing.The water seal should be insulated to prevent condensation.

Refrigeration

REFRIGERANT TYPE

The standard refrigerant will be R-22 unless otherwise specified on the customer order. Check the serial plate on the case for information.

PIPING - Remote Cases Only

The refrigerant line outlets are located under the case. Locate first the electrical box, the outlets are then on the same side of the case but at the opposite end. Insulate suction lines to prevent condensation drippage.

IGFP-RGSSFP-0008

REFRIGERATION LINES

LIQUID SUCTION

3/8" O.D.

5/8" O.D.

NOTE: The standard coil is piped at 5/8" (suction); however, the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be

5/8", 7/8", or 11/8". Refer to the particular case you are hooking up.

Refrigerant lines should be sized as shown on the refrig- eration legend furnished by the store.

Install P-traps (oil traps) at the base of all suction line ver- tical risers.

Pressure drop can rob the system of capacity.To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.

CONTROL SETTINGS

See the “Case Specs” section of this guidebook for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product tempera- tures. Product temperature should be measured first thing in the morning, after having been refrigerated overnight. For all multiplexing, defrost should be time terminated. Loadmaster valves are not recommended. Defrost times should be as follows: OFF CYCLE - Three times daily for 46 minutes.The number of defrosts per day and the dura- tion of the defrost cycle may be adjusted to meet condi- tions present at your location.

ACCESS TO TX VALVES & DRAIN LINES

MECHANICAL - Remove the product from the bottom deck pan.Remove pan.Remove refrigeration and drain access pan- els (labeled). TX valve (mechanical only) and drain are lo- cated under each access panel at end of the case.

ELECTRONIC (Remote Only) -The Electronic Expansion valve controller is located within the electrical access panel(s).

ELECTRONIC EXPANSION VALVE (Remote Only)

A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and con- troller manufacturers information sheet. Sensors for elec- tronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case

THERMOSTATIC EXPANSION VALVE LOCATION

This device is located on the same side as the refrigera- tion stub. A Sporlan balanced port expansion valve model is furnished as standard equipment, unless otherwise speci- fied by customer.

4

Image 4
Contents Rgssfp This Booklet Contains Information on Rgssfp Shipping DamageApparent Loss or Damage Concealed Loss or DamageJoint Trim LevelingWaste Outlet and P-TRAP Installing Condensate Drain Control SettingsAccess to TX Valves & Drain Lines Refrigerant TypeWiring Color Code Stat LocationCase Cleaning StockingBallast Location User InformationNON-GLARE Glass Cleaning Plexiglass & Acrylic CareTips & Troubleshooting For Prompt ServiceReplacing Fluorescent Lamps Evaporator FansSpecifications ElectricalcircuitsRgssfpcase Wiringdiagram Electrical Schematics4CASE Rgssfpcase 6CASE8CASE 12CASE IGFP-RGSSFP-0008 Type of Refrigerator Typical Entering Air Temperature AppendicesAppendix D. Recommendations to user Limited Warranty Model Serial Number