hussman DBP, 3 Waste Outlet and P-TRAP, Access Panels, Installing Condensate Drain, Hose Reel

Page 6

IGIP-DBP, DBRP 01,03-0210

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture.

A 1-1/2" P-trap and threaded adapter are supplied with each fixture. The P-trap must be installed to prevent air leakage and insect entrance into the fixture.

NOTE: PVC-DWV solvent cement is recommended. Follow the manufacturer’s instructions.

ACCESS PANELS

All electrical and drain access panels are clearly labeled on the deck of the produce stand. The access for con- densing units (in the self contained units) is located on the side of the stand, at the end. Ends of stand are fitted for removal, if condensing unit has to be taken out.

INSTALLING CONDENSATE DRAIN

Poorly or improperly installed condensate drains can se- riously interfere with the operation of this refrigerator, and result in costly maintenance and product losses.Please follow the recommendations listed below when installing condensate drains to insure a proper installation:

1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-trap supplied with the case.

2.When connecting condensate drains, the P-trap must be used as part of the condensate drain to prevent air leakage or insect entrance. Store plumb- ing system floor drains should be at least 14" off the center of the case to allow use of the P-trap pipe section. Never use two water seals in series in any

one line. Double P-traps in series will cause a lock and prevent draining.

3.Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to main- tain the 1/8" pitch and to prevent warping.

4.Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.

5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.

6.Prevent condensate drains from freezing:

a.Do not install condensate drains in contact with non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.

b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing.The water seal should be insulated to prevent condensation.

HOSE REEL

If an optional hose reel is ordered, it will be installed at the factory. The water supply valve is located next to the access panel. Connect the water supply to the valve.

SPRAY HOSE

If an optional quick-disconnect spray hose is ordered, a pressure regulating valve should be installed. If the water pressure exceeds 45 PSI, the valve should be set for 30 to 35 PSI outlet pressure.

6

Image 6
Contents DBP, Dbrp 01,03 Island ProduceApparent Loss or Damage This Booklet Contains Information onShipping Damage Concealed Loss or DamageCut & Plan Views DBRP-03Uncrating the Stand InstallationLocation Exterior LoadingDo not USE Permagum Setting and JoiningLeveling Splash GuardWaste Outlet and P-TRAP Access PanelsInstalling Condensate Drain Hose ReelStat Location Wiring Color Code Ashrae Color CodeStocking Case CleaningCleaning Precautions When Cleaning Important StepsTips & Troubleshooting Replacing Fluorescent LampsElectrical and Refrigeration Specifications DBRP-01Electrical Schematics BALLASTB-232Diagram 22Remotemodelonly Type Typical Entering Refrigerator AIR Temperature AppendicesPotentially hazardous food Rev.0210 IGIP-DBP, Dbrp 01,03-0210 Limited Warranty Model Serial Number