hussman DBRP 01, DBP, 3 manual Stat Location

Page 7

Rev.0210

Refrigeration

REFRIGERANT TYPE

The standard refrigerant will be R-22 unless otherwise specified on the customer order. Check the serial plate on the case for information.

PIPING

The refrigerant line outlets are located under the case. Locate first the electrical box, the outlets are then on the same side of the case but at the opposite end. Insulate suction lines to prevent condensation drippage.

ACCESS PANELS

All electrical and drain access panels are clearly labeled on the deck of the produce stand. The access for con- densing units (in the self contained units) is located on the side of the stand, at the end. Ends of stand are fitted for removal, if condensing unit has to be taken out.

REFRIGERATION LINES

LIQUID SUCTION

3/8" O.D.

5/8" O.D.

NOTE: The standard coil is piped at 5/8" (suction); however, the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be

5/8", 7/8", or 11/8". Refer to the particular case you are hooking up.

to meet conditions present at your location.

ACCESS TO TX VALVES & DRAIN LINES

MECHANICAL - Remove product from end of case. Remove product racks.Remove refrigeration and drain access panels (labeled).TX valve (mechanical only) and drain are located under each access panel at end of the case.

ELECTRONIC - The Electronic Expansion valve master and slave cylinder(s) are located within the electrical access panel(s).

ELECTRONIC EXPANSION VALVE (OPTIONAL)

A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and con- troller manufacturers information sheet. Sensors for elec- tronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case

THERMOSTATIC EXPANSION VALVE LOCATION

This device is located on the same side as the refrigera- tion stub. A balanced port expansion valve model is fur- nished as standard equipment, unless otherwise specified by customer.

EXPANSION VALVE ADJUSTMENT

Refrigerant lines should be sized as shown on the refrig- eration legend furnished by the store.

Install P-traps (oil traps) at the base of all suction line ver- tical risers.

Pressure drop can rob the system of capacity.To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.

CONTROL SETTINGS

See the “Case Specs” section of this guidebook for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product tempera- tures. Product temperature should be measured first thing in the morning, after having been refrigerated overnight. For all multiplexing, defrost should be time terminated. Loadmaster valves are not recommended. Defrost times should as directed in the Case Specifications section of this guide. The number of defrosts per day should never change.The duration of the defrost cycle may be adjusted

Expansion valves must be adjusted to fully feed the evapo- rator. Before attempting any adjustments, make sure the evaporator is either clear or very lightly covered with frost, and that the fixture is within 10°F of its expected operat- ing temperature.

MEASURING THE OPERATING SUPERHEAT

1.Determine the suction pressure with an accurate pressure gauge at the evaporator outlet.

2.From a refrigerant pressure temperature chart, determine the saturation temperature at the observed suction pressure.

3.Measure the temperature of the suction gas at the thermostatic remote bulb location.

4.Subtract the saturation temperature obtained in step No.2 from the temperature measured in step No.3.

3. The difference is superheat.

5. Set the superheat for 5°F - 7°F.

T-STAT LOCATION

T-Stats are located under access panels on the end of the case.

7

Image 7
Contents Island Produce DBP, Dbrp 01,03Concealed Loss or Damage This Booklet Contains Information onShipping Damage Apparent Loss or DamageDBRP-03 Cut & Plan ViewsExterior Loading InstallationLocation Uncrating the StandSplash Guard Setting and JoiningLeveling Do not USE PermagumHose Reel Access PanelsInstalling Condensate Drain Waste Outlet and P-TRAPStat Location Ashrae Color Code Wiring Color CodeImportant Steps Case CleaningCleaning Precautions When Cleaning StockingReplacing Fluorescent Lamps Tips & TroubleshootingDBRP-01 Electrical and Refrigeration SpecificationsBALLASTB-232 Electrical SchematicsDiagram 22Remotemodelonly Appendices Type Typical Entering Refrigerator AIR TemperaturePotentially hazardous food Rev.0210 IGIP-DBP, Dbrp 01,03-0210 Limited Warranty Model Serial Number