ZTS Series Accessory Definitions

M85

Digital Meter Includes M84 functions plus unbalance 256 samples/cycle data logging, waveform capture and sag/swell capture.

M86

Digital Meter Includes M85 functions plus large graphical screen display with Ethernet communications port.

N1

Running Time Indicator - Door mounted

N2

Operation Counter - Door Mounted

P1

Engine Start Timer (adjustable to 6 sec.)

P2

Engine Start Timer (adjustable to 300 sec.)

Q2

Peak shave/remote load test/area protection - Relay (S.P.D.T.) (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)

Q3

Inhibit transfer to emergency (Source 2) (load add relay) - Relay (S.P.D.T.) (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)

Q7

Inhibit transfer to normal (Source 1) - Relay (S.P.D.T.) (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)

R1-1/R1-3

Over Voltage sensing for normal (Source 1) single (R1-1) or three (R1-3) phase

R15/R15D

Load Shed. Should Source 2 become overloaded, a signal can be given to switch to the dead

or Mid position.

R16

Phase rotation sensing of Normal (Source 1) and Emergency (Source 2)

R26/R26D

Interruptable Power Rate Provisions.

Allow transfer out of Source 1 position to Mid position or dead Source 2. Alarm and Pre-Signal circuit included. (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)

R50

In Phase monitor between Normal (Source 1) and Emergency (Source 2) to allow transfer

S5P

Microprocessor activated auto/manual retransfer selector switch for trnsferring to Normal (Source 1) (includes microprocessor activated YN accessory)

S12P

Microprocessor activated auto/manual retransfer selector switch for trnsferring to Normal (Source 1) (includes microprocessor activated YN & YE accessory)

S13P

Microprocessor activated commit/no commit on transferring to Emergency (Source 2) (with enable/disable)

S14

Keyed selector switch for (retransfer to normal-test-auto)

SW1

Auto/Off/Start Engine control selector - Door mounted (keyed or non-keyed operation available)

SW2

Auto/Off Engine control selector - Door mounted (keyed or non-keyed operation available)

SW3

Source Priority Selector Switch - Door mounted Allows selection of Source 1 or Source 2 to be the Prime Source. Transfer Switch will transfer to selected Prime Source if that Source is available. (keyed or non-keyed operation available)

T

Retransfer to normal adjustable time delay

T3/W3

Pre-signal contact on transfer to Normal (Source 1) or Emergency (Source 2) during test.

U

Engine stop /cool adjustable cool down timer

UMD

Pre and ppost transfer output adjustable time range. Functions in both directions. Includes 2 circuits. Additional circuits available.

VI

Voltage imbalance between phases (3 Phase only)

W

Adjustabvle time delay on transfer to Emergency (Source 2)

YEN

Bypass transfer timers function (soft switch in control)

ZNET

Microprocessor Communication Module

PB-5066 Page 6

Image 6
Contents Product Bulletin Quality System ISO 9001 RegisteredZTS Series Automatic Transfer Switches Available in ALL transfer modes More Enhanced FeaturesMX250 series Microprocessor Controller Technical BenefitsZTS Series Accessory Group Matrix Mstds Mexes Mcons Msens Mspes MpsgsZTS Series Accessory Definitions R1-1/R1-3 M85M86 R15/R15DZTS Series Withstand Ratings Circuit AmpsRated for Total Systems or Motor Loads ZTS Model Transfer Switches ZTS Series Ordering Information Ampere