Cornelius CCM CCU manual Remote Condenser Guidelines, Page

Page 10
Manual background

Remote Condenser Guidelines

The CCM0530R, CCM0630R, CCM0830R, CCM1030R and CCM1530R remote ice makers incorporate the mixing valve in the condenser. This configuration allows up to a 100 foot calculated remote line set run. Reference the diagram below to calculate the maximum 100 foot line set run.

ICE Machine Model Number

Remote Condenser Model Number

CCM1530R

RC15002

 

CCM1030R

RC08002

CCM0830R

RC08002

CCM0630R

RC06002

CCM0530R

RC05001

Limitations for new remote machines that have the headmaster mounted in the condenser.

Maximum Rise is 35 feet.

Maximum Drop is 15 feet.

Maximum equivalent run is 100 feet.

Formula for figuring maximum equivalent run is as follows:

Rise x 1.7 + Drop x 6.6 + horizontal run = equivalent run.

Examples: 35 ft. rise x 1.7 + 40 ft. horizontal = 99.5 equivalent feet line run

35 ft. rise

Manual background 40 ft. horizontal

Manual background 34 ft. horizontal

10 ft. drop

10 ft. drop x 6.6 + 34 ft horizontal = 100 equivalent feet line run

Page 5

Image 10
Contents Installation, Start-upand Maintenance Manual Publication Number Revision Date SeptemberRevision A Nordic Ice MakerPage Keep this manual for future reference How To Use This ManualForward PageInstallation Guidelines Table of ContentsFreight Claim Procedure Start-UpProcedureVisible Loss or Damage Freight Claim ProcedureFreight Claims Important Inspect Promptly Concealed Loss or DamageModel Number Model and Serial Number FormatSample Data Plate Serial NumberAdjustments Installation Guidelines Installation GuidelinesElectrical Specifications Ambient Operating Temperaturesdispenser with the provided Installation GuidelinesAttach the ice machine to the bin or PageRemote Condenser Guidelines Remote Condenser InstallationAir Flow Installation GuidelinesRemote Condenser Guidelines PageElectrical and Plumbing Requirements ON-OFF-WASHSwitch is located in the control boxRemove the grill screws to access the control box PageElectrical and Plumbing Requirements ON-OFF-WASHSwitch is located in the control boxRemove the grill screws to access the control box PageIncludes 50Hz. Units Electrical and Plumbing RequirementsPage Electrical and Plumbing Requirements Includes 50Hz. And 3 Phase UnitsPage Electrical and Plumbing Requirements Includes 50Hz. and 3 Phase UnitsPage Electrical and Plumbing Requirements PageElectrical and Plumbing Requirements PageHow the Ice Machine Works How the CCM Ice Machine WorksPage Bridge Thickness and Timer Adjustment Start-UpProcedure Start-UpProcedurePage Undercounter Models Start-UpProcedure Bin Control OperationBin Control Adjustment PageGeneral Maintenance Procedure General MaintenancePage Ice Machine Cleaning and Sanitizing Instructions Cleaning ProcedurePage Cleaning Agent Cabinet Care Cleaning stainless steelCleaning Activity Method of ApplicationWinterizing Procedure Winterizing Procedures PageService History Service HistoryPage