TROUBLESHOOTING
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
TROUBLESHOOTING COMPRESSORS
Trouble | Probable Cause | Remedy |
Basically the compressor problems can be narrowed down to three areas of checkout.
THE COMPRESSOR WILL | A. | No voltage to the compressor |
NOT RUN |
| terminals. |
| B. | Low voltage. |
A.Check circuit.
B.Below 90% of nameplate rated voltage.
| C. Problems in the compressor | C. | See electrical checkout | |
|
| electrical circuit. |
| instructions. |
|
|
|
| |
THE COMPRESSOR STARTS | A. |
| A. Check for proper fan operation | |
BUT TRIPS REPEATEDLY ON |
|
|
| and clean condenser. |
THE OVERLOAD | B. |
| B. | Check the compressor suction |
PROTECTOR |
| |||
|
|
| and discharge pressures. | |
|
|
|
| |
| C. | Voltage. | C. Voltage should be within 10% of | |
|
|
|
| the rated nameplate voltage. |
| D. | High compressor amperage | D. It should never exceed 120% of | |
|
| draw. |
| the rated nameplate amperage. |
|
|
|
| See electrical checkout |
|
|
|
| instructions. |
|
|
|
| |
THE COMPRESSOR RUNS | A. | Compressor not working. | A. Check the compressor suctions | |
BUT WILL NOT |
|
|
| and discharge pressures. See |
REFRIGERATE |
|
|
| chart on page 13. |
|
|
|
|
|
630460154 | 24 |