OAC: AUX output configuration: (AL, Li, UL, Ip, AA, rE, dF, C2)
AL: alarm output; Li: light of the cabinet; UL: for the
in OFF position); Ip: to extract the insert probe (It is actionable only when the controller is in OFF position); AA:
anti - condensation; rE: the IV relay works as a thermostat, with direct action (cooling) (OAH>0), and inverse
actions (heating) (OAH<0); dF: the IV relay is activated during the defrost, at the end of the defrost it remains
ON for the OAt time; C2: second compressor. See 1c2 parameter for different settings.
OAP | AUX output polarity (OP ⎟ CL) OP= normally open; if it is ON the terminals |
closed; if it is ON the terminals | |
OAt | AUX output timer: (0÷255 min) time in which the AUX output stays ON. It is enabled when OAC = Li or |
UL or Ip or AA or dF.
OAS Set point for AUX output (-50÷50; ris.1 °C/ 1°F)
OAH Differential for AUX output:
HEATING: AUX cut IN is OAS Plus Differential (OAH<0). AUX cut OUT is when the temperature reaches the set point OAS.
OAi | Probe selection for the AUX output (rP, EP, iP) rP = thermostat probe, EP = evaporator probe; iP = |
insert probe | |
DEFROST | |
tdF | Defrost type (not present in the XB350C): (rE= electrical heater; in = hot gas). |
dPO Defrost before the holding: no= no defrost; YES= defrost at the start of a holding cycle. | |
IdF | Interval between defrost cycles: (0.1⎟ 24.0; res. 10 min) Determines the time interval between the |
beginning of two defrost cycles. (with 0.0 the defrost is disabled) | |
dtE | Defrost termination temperature (not present in the XB350C): |
measured by the evaporator probe, which terminates the defrost.
MdF Maximum length for defrost: (0÷255 min) When EPP = no (timed defrost) it sets the defrost duration, when EPP = YES (defrost termination based on temperature) it sets the maximum length for defrost.
dFd | Temperature displayed during defrost: (rt , it, SEt, dEF) rt: real temperature; it: temperature at the start |
of defrost; SEt: set point; dEF: “dEF” message | |
Fdt | Drip time (not present in the XB350C): (0 ⎟ 60 min) Time interval between reaching defrost termination |
temperature and the restoring of the controllers' normal operation. This time allows the evaporator to eliminate water drops that might have formed during defrost.
FANS
FnC Fans operating mode during the holding phase:
FSt Fan stop temperature:
AFH Differential for the stop temperature and for the alarm (0.1 ⎟ 25.0 °C; ris.0.1°C/1°F) Fans carry on working when the temperature reaches the
Fnd Fan delay after defrost: (0 ⎟ 255 min) The time interval between end of defrost and evaporator fans start.
ALARM
ALU MAXIMUM temperature alarm: (1 ⎟ 50 °C/°F) When the “SET+ALU” temperature is reached the alarm is enabled, (possibly after the “Ald” delay time).
ALL Minimum temperature alarm: (1⎟50°C/1°F) When the
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and alarm signalling.
EdA Temperature alarm delay at the end of defrost: (0 ⎟ 255 min) Time interval between the detection of the temperature alarm condition at the end of defrost and alarm signalling.
tbA Silencing alarm relay: (Yes= silencing buzzer and alarm relay, no= only buzzer silencing).
OTHER
Ad1 Address 1 for RS485: (0 ⎟ 94)
Ad2 Address 2 for RS485 (0 ⎟ 94)
Lod: Local display: (rP, EP, iP, nr) Select which probe is displayed by the instrument. rP: Thermostat probe. EP: Evaporator probe. iP: Insert probe, nr: During a temperature cycle the insert probe is displayed, during the holding phase the room probe is displayed. If the cycle is made by time the time remaining is displayed (in minutes).
rEd | Remote display: (rP, EP, Ip) select which probe is displayed by the XR REP. rP: thermostat probe; EP: |
evaporator probe; iP: insert probe. | |
Loc | Set point of the holding phase lock (no - YES) It locks the set point of the holding phase. |
11