Foster BQCF 40, QC 600, QC 11 manual QC 60 Cycle Parameters, Bqcf 40 Cycle Parameters

Page 8

Hard Chill Time - For general purpose chilling based on time. (Cy2)

 

dbC = no

iS1 = -15°C

iS2 = 2°C

iS3 = -18°C

dbH = no

 

 

 

 

rS1 = -15°C

rS2 = 2°C

rS3 = -30°C

HdS = 3°C

 

 

 

 

Pd1 = 1.1hours

Pd2 = 0.2 hours

Pd3= OFF

 

 

 

 

Hard Chill +-. This program is for specialist chilling only and is not recommended for normal use. (Cy3)

 

 

 

 

 

 

 

 

 

 

 

dbC = no

iS1 = -15°C

iS2 = -18C

iS3 = -18°C

dbH = no

 

 

 

rS1 = -15°C

rS2 = -30°C

rS3 = -15°C

HdS = 3°C

 

 

 

 

Pd1 = 4 hours

Pd2 = OFF

Pd3 = OFF

 

 

 

 

Hard Chill Temperature - For general purpose chilling using the food probe. (Cy4)

 

 

 

 

 

 

 

 

 

 

 

 

 

dbC = no

iS1 = -6°C

iS2 = 3°C

iS3 = -18°C

dbH = no

 

 

 

rS1 = -15°C

rS2 = 2°C

RS3 = -30°C

HdS = 3°C

 

 

 

 

Pd1 = 1.1 hours

Pd2 = 0.2

Pd3 = OFF

 

 

QC 60 Cycle Parameters.

Soft Chill- for the safe chilling of delicate products. (Cy1)

 

dbC = no

iS1 = -10°C

iS2 = 5°C

iS3 = 3°C

dbH = no

 

 

 

 

rS1 = 2°C

rS2 = -2°C

rS3 = -2°C

HdS = 3°C

 

 

 

 

Pd1 = 1.3 hours

Pd2 = OFF

Pd3 = OFF

 

 

 

 

Hard Chill Time - For general purpose chilling based on time. (Cy2)

 

 

 

 

 

 

 

 

 

 

 

 

 

dbC = no

iS1 = -15°C

iS2 = 2°C

iS3 = -18°C

dbH = no

 

 

 

rS1 = -15°C

rS2 = 2°C

rS3 = -30°C

HdS = 3°C

 

 

 

 

Pd1 = 1.1hours

Pd2 = 0.2 hours

Pd3= OFF

 

 

 

 

Hard Chill +-. This program is for specialist chilling only and is not recommended for normal use. (Cy3)

 

 

 

 

 

 

 

 

 

 

 

dbC = no

iS1 = -15°C

iS2 = -18C

iS3 = -18°C

dbH = no

 

 

 

rS1 = -15°C

rS2 = -30°C

rS3 = -15°C

HdS = 3°C

 

 

 

 

Pd1 = 4 hours

Pd2 = OFF

Pd3 = OFF

 

 

 

 

Hard Chill Temperature - For general purpose chilling using the food probe. (Cy4)

 

 

 

 

 

 

 

 

 

 

 

 

 

dbC = no

iS1 = -6°C

iS2 = 3°C

iS3 = -18°C

dbH = no

 

 

 

rS1 = -15°C

rS2 = 2°C

RS3 = -30°C

HdS = 3°C

 

 

 

 

Pd1 = 1.1 hours

Pd2 = 0.2

Pd3 = OFF

 

 

BQCF 40 Cycle Parameters.

Soft Chill- for the safe chilling of delicate products. (Cy1)

 

dbC = no

iS1 = -10°C

iS2 = 5°C

iS3 = 3°C

dbH = no

 

 

 

rS1 = 2°C

rS2 = -2°C

rS3 = -2°C

HdS = 3°C

 

 

 

Pd1 = 1.3 hours

Pd2 = OFF

Pd3 = OFF

 

 

 

Hard Chill Time - For general purpose chilling based on time. (Cy2)

 

 

 

 

 

 

 

 

 

 

 

 

dbC = no

iS1 = -15°C

iS2 = 2°C

iS3 = -18°C

dbH = no

 

 

 

rS1 = -15°C

rS2 = 2°C

rS3 = -30°C

HdS = 3°C

 

 

 

Pd1 = 1.1hours

Pd2 = 0.2 hours

Pd3= OFF

 

 

 

 

 

 

7

 

Image 8 Contents
Page Contents Program Hard Chilling Temperature Longer Term Storage ‘Hold’ Mode ConservationCook Chill Operation Program Soft ChillingQC 11, QC 600 & Bqcf 40 Blast Chill Operating Instructions OperationManual Defrost IntroductionMode Function Temporarily Stopping the CycleIlluminated Page QC 60 Cycle Parameters Bqcf 40 Cycle ParametersFunction Menu Parameter Settings BqcfRPO DiC Digital input operating mode EAL, bAL, dorParameter Definitions FnC Fans operating mode during the holding phase OAtOAS Set point for AUX output -50÷50 ris.1 C/ 1F OAiPrinter Management RPFModel Wiring Diagram Number Fuse Rating Refrigerant R404a Refrigerant QuantityQC 11 Wiring Diagram QC 600 Wiring Diagram Bqcf 40 Wiring Diagram. Sheet 1 Bqcf 40 Wiring Diagram. Sheet2 Email commercial@fosterfrance.com