Figure 14. EBP Domestic Water Piping with Recirculating Loop.

WARNING

Failure to install a hot water tempering (mixing) valve (12) creates a scalding hazard with potential for serious bodily injury. Some brands of tempering (mixing) valves are not designed as anti-scald valves.

Where domestic water is supplying multiple apartments or large whirlpool tubs, additional storage tank may be connected as shown in Figure 13. The bronze circulator shown must be connected to tank aquastat and must not run continuously. If the circulator is wired to run continuously, unit's domestic water flow switch will keep the unit in domestic water priority, and no water will be allowed to be sent to the heating system.

SECTION 4.

Hydronic Heat Piping

4A. Hydronic Piping

The appliance incorporates its own circulating pump and bypass loop and is capable of providing flow through heating zones, in addition to what it needs for itself. Model size 110 is capable of providing flow for two heating zones (up to 67 feet of ¾" baseboard each), and model 175 is capable of providing flow for four heating zones (up to 67 feet of ¾" baseboard, each).

EDP/EDN boilers installed in radiant (in floor) systems and other low mass boilers should be provided with a buffer/blender tank to assure a controlled supply temperature, and to prevent short cycling. In radiant systems utilizing 3-way tempering valves, a

bypass pipe must be installed between supply and return piping.

1.EBP ONLY: Connect system supply to 1¼" supply connection marked “SUPPLY”.

2.EDP/EDN ONLY: Connect 1¼" thermostatic union to system supply connection in direction designated with union.

3.Pipe the discharge of the relief valve, full size, to a drain or in a manner to prevent injury in the event of pressure relief.

4.Install an air purger in flow supply line as shown in Figures 15, 16 or 17.

5.Install automatic float type air vent on air scoops.

6.Install a diaphragm expansion tank in boiler outlet piping. To ensure sufficient expansion volume for the hydronic system water, due to heat-up and cool-down during normal operation, a #30 or larger expansion tank must be used on EBP combo units.

NOTE: Never install expansion tank and auto fill valve on return.

7.If necessary, install a properly sized circulator with optional isolation valves in supply beyond expansion tank.

Caution

All hot water pipes must be installed with a minimum 1" (25mm) clearance from combustible materials.

8.Connect boiler feed water supply with shut off valve to inlet connection of automatic fill valve. Locate in boiler outlet piping.

9.If codes require, install suitable back flow preventer between automatic fill valve and city main.

10.The appliance may be installed in single and multiple zone systems (using either zone valves

Image 10
Contents Endurance Table of Contents 1A. Introduction General Information1B. Codes and Standards Venting Options Endurance Laars Heating Systems 2E. Air Source For Combustion when not direct vented For Appliances Certified as Direct Vent2G. Securing Special Gas Vent 2F. Connecting Special Gas Vent to the Appliance3A. Gas Piping 3B. Domestic Water Piping EBP only Length Capacity of PipeHydronic Heat Piping 4A. Hydronic PipingHydronic Piping EDP/EBP with Zone Valves Hydronic Piping EBP/EDP for Systems Zoned with Circulators Electrical Connections 4C. Water Quality and TreatmentMultiple Zones with Circulators and Room Thermostats For Your Safety Read Before Operating Fermeture DE L’ALIMENTATION EN GAZ Boiler Start Up To read or change mode6A. Common Vent Test 6B. Filling the System 6C. Firing BurnerMaintenance and Component Description 7F. Transformer 7E. Ignitor / Flame Sensor Assembly7J. Cleaning the Boiler Coil 7G. BlowerServicing 8A. Sequence of Operation8B. Trouble Shooting Fault Codes 8B-1. Fault Code IdentificationPower UP Fault Tree Ignition Fault Tree Space Heating Domestic HOT Water Boiler Temperature Poor flame sensor signal The boiler control EDP/EDN Wiring Diagram EBP Wiring Diagram 10A. Delayed ignition Symptom Evaluations9A. Gas Valve Calibration offset adjustment Gas Valve Calibration10C. Noisy Operation 10B. Short Cycling10D. Insufficient Hot Water EBP only 10E. High Gas Consumption Parts Identification Model EDP/EDNModel EBP Boiler DrainBox Lynnfield, MA Phone Fax