Whirlpool EDP/EDN warranty Poor flame sensor signal The boiler control

Page 28

Page 28

LAARS HEATING SYSTEMS

 

 

 

 

(2)poor flame sensor signal, (3) inadequate gas supply, (4) ignitor failure, (5) blocked or contaminated air source.

1. Poor Combustion: Poor combustion should be

suspected if there is a strong flue gas odor. The

odor may result from either an improper gas/air

ration (high or low CO2) or contamination of the

combustion air supply. If an improper gas/air

ratio is suspected refer to “gas valve calibration

(offset adjustment)” on page 25. If

contamination of the air source is suspected refer

to (5) below.

MEASUREMENTS AT HIGH FIRE

NATURAL GAS

% CO2

9.0 - 9.6

MAX INPUT

175,270

BTU/H

 

OFFSET

(-0.01 to -.10)

IN W.C.

 

 

LP GAS

% CO2

9.7 - 10.1

MAX INPUT

175,270

BTU/H

 

OFFSET

2.

Poor flame sensor signal: The boiler control

 

board will lockout if the flame sensor is

IN W.C.

(-0.01 to -.10)

grounded or if the flame signal it receives is less

than 1 ￿A dc. To check for a grounded sensor,

remove the flame sensor wire (yellow) from the

boiler control board and check for continuity

between the yellow wire terminal and the

combustion chamber bottom pan. If there is

continuity, the flame sensor is grounded. An

alternate way to check for grounding of the

flame sensor is to check the ohms resistance

between the yellow wire terminal and the

combustion chamber bottom pan, using a meter

set for at least 100,000 ohms. The resistance

must be more than 250,000 ohms (some

technicians have been confused by meters which

report infinite resistance with what appears to

them as double zeros; an infinite resistance

reading means there is no grounding of the flame

sensor.) If there is continuity, or the ohms

resistance is less than 250,000 ohms, debris or

moisture in the combustion chamber may be the

cause. To correct, carefully remove the ignitor

and flame sensor assembly. Look for debris on

the assembly where the flame rod exits the

ceramic tube. If debris exists, remove it. If this

area is clean, insert a pencil or other round

object into the flame sensor hole in the bottom

combustion chamber pan and roll it around to

clear any debris that may exist inside the

combustion chamber. Replace the ignitor/flame

sensor assembly, reconnect the yellow wire on

the PCB and start the boiler. If lockout persists,

check the flame signal. To check the flame

signal, disconnect the yellow wire from the

flame sensor, connect a meter, set for microamps

(￿A) DC, between the flame sensor connector

and the yellow wire connector. Start the boiler. If

the meter reading is less than 1.00 ￿A DC, see

(3) “poor combustion” below. (Check for air

leaks at air inlet to blower.)

3. Inadequate gas supply: Before proceeding,

ensure that the gas supply has not been shutoff

or the LP tank (LP boilers) is not empty. Then,

reset the boiler and observe the operational

Table 4. EBP/EDP 175.

Figure 29.

Figure 30. Jumper Wiring for Test and Calibration.

cycle. Approximately 20 seconds after the start of the cycle, the GV LED on the PCB should light. If it does not, reset the boiler and check for 24 VAC at the plug on the PCB. If the voltage is less than 20 VAC, and transformer voltage is 24 VAC replace the PCB. If the voltage is correct, connect a pressure gauge to the offset pressure port on the gas valve. Reset the boiler and

Image 28
Contents Endurance Table of Contents 1A. Introduction General Information1B. Codes and Standards Venting Options Endurance Laars Heating Systems 2E. Air Source For Combustion when not direct vented For Appliances Certified as Direct Vent2G. Securing Special Gas Vent 2F. Connecting Special Gas Vent to the Appliance3A. Gas Piping 3B. Domestic Water Piping EBP only Length Capacity of PipeHydronic Heat Piping 4A. Hydronic PipingHydronic Piping EDP/EBP with Zone Valves Hydronic Piping EBP/EDP for Systems Zoned with Circulators Electrical Connections 4C. Water Quality and TreatmentMultiple Zones with Circulators and Room Thermostats For Your Safety Read Before Operating Fermeture DE L’ALIMENTATION EN GAZ Boiler Start Up To read or change mode6A. Common Vent Test 6B. Filling the System 6C. Firing BurnerMaintenance and Component Description 7E. Ignitor / Flame Sensor Assembly 7J. Cleaning the Boiler Coil7F. Transformer 7G. BlowerServicing 8A. Sequence of Operation8B. Trouble Shooting Fault Codes 8B-1. Fault Code IdentificationPower UP Fault Tree Ignition Fault Tree Space Heating Domestic HOT Water Boiler Temperature Poor flame sensor signal The boiler control EDP/EDN Wiring Diagram EBP Wiring Diagram Symptom Evaluations 9A. Gas Valve Calibration offset adjustment10A. Delayed ignition Gas Valve Calibration10C. Noisy Operation 10B. Short Cycling10D. Insufficient Hot Water EBP only 10E. High Gas Consumption Parts Identification Model EDP/EDNModel EBP Boiler DrainBox Lynnfield, MA Phone Fax